![Carrier AiroVision 39 HQ Assembly/Installation, Commissioning, Maintenance Manual Download Page 25](http://html1.mh-extra.com/html/carrier/airovision-39-hq/airovision-39-hq_assembly-installation-commissioning-maintenance-manual_2562128025.webp)
25
Fig. 49.
Negative pressure siphon
Fig. 51.
U-folded negative pressure siphon
Fig. 52.
Negative pressure siphon installation
Fig. 50.
Positive pressure siphon
P [Pa]: Negative pressures in the unit. Calculation
should be done without using (-) sign.
R [mm]: Distance from lower point of the pipe to
ground at condensation tray outlet.
There is no inconvenience if R value is set higher
than the value found by calculation.
Positive pressure siphon should be filled with water
before starting up the unit.
Negative pressure siphon may only be applicable for
negative drain.
Negative pressure siphon can be set up as in Figure
49.
In Figure 52, parts and assembly order of siphon are
given.
Only negative pressure siphon is delivered from the
factory. A positive pressure siphon should be made
using a U-bended pipe as shown in Fig. 50.
The ball inside the negative pressure siphon provides
drained water fill the siphon by preventing air suction.
This ball also blocks suction discharges that may be
produced during pressure shocks.
Water drain direction marked with an arrow on the
negative pressure siphon.
Application types according to the pressure and si-
phon types are shown in Fig. 53.
R= + 50
P
10
H1 ≥ (max positive pressure at cooling coil, Pa) / 10
+ 50 mm
H2: 50 mm
H1 = (max positive pressure at cooling coil, Pa) / 10
+ 50 mm
H2 ≥ 1/2 x H1
Install negative pressure siphon not supplied from
the factory according to Fig. 51.
Summary of Contents for AiroVision 39 HQ
Page 2: ...2 Code No B 8 1 3i Book Publication Date 081018 Revision No 081018 ...
Page 5: ...5 39 HQ Air Handling Units AiroVision Assembly Installation Commissioning Maintenance Manual ...
Page 6: ...6 ...
Page 23: ...23 ...
Page 31: ...31 ...
Page 40: ...40 APPENDIX 1 CELL INFO AND CONNECTION ORDER ...
Page 41: ...41 APPENDIX 2 FRONT WITHDRAWAL FILTER DETAIL ...
Page 42: ...42 APPENDIX 2 FRONT WITHDRAWAL POUCH FILTER INSTALLATION ...
Page 43: ...43 APPENDIX 2 SIDE WITHDRAWAL COMBINED FILTER INSTALLATION ...
Page 44: ...44 APPENDIX 2 SIDE WITHDRAWAL FILTER INSTALLATION F8 F9 ...
Page 45: ...45 APPENDIX 2 SIDE WITHDRAWAL FILTER INSTALLATION F7 ...
Page 46: ...46 APPENDIX 3 1 Side Withdrawal Filter ...
Page 47: ...47 APPENDIX 3 2 Front Withdrawal Filter ...
Page 48: ...48 APPENDIX 3 3 Pleated Filter ...
Page 51: ...51 ...
Page 52: ......