4.6
FAN MOTOR
This operation can only be undertaken once the electrical supply has been switched off (consignation).
Under this condition only, the access to fan motors is authorized.
Remarks :
If a fan motor needs to be changed, care should be taken to unplug all purge holes during reinstallation (to enable the condensation to
escape).
5-
OPTION : WATER SPRAYING SYSTEM
Water characteristics :
pH
6 < pH < 8
Hardness (CaCO3)
30 à 100 ppm
Alkalinity (CaCO3)
250 ppm max
Pressure
1.5 bar
Water spray option includes:
> Copper pipes with water duct (sprayer)
> Brass ducts (quantity will be confirmed at the order)
> Water devices:
-
Manometer
-
Solenoid valve
-
filter
-
Pressure switch
-
Ambient temperature sensor
-
Adjustment hand valve.
> An ambient thermostat:
You have to install a drain valve at lowest point of the installation (manual operation to be done prior winter with opened solenoid valve ) Way
of control method: When all the fans of the heat exchanger are in operation and ambient temperature is over the ambient thermostat set
point, Water spray system is engaged.
Summary of Contents for ADAGIO 60 SOPRANO 90
Page 17: ...20 3 5 ...
Page 29: ......