Installation
Please refer to the Safety information manual.
This device is destined for installation in sheltered
t
buildings, if possible insulated.
It should not be installed in very humid rooms (for
example laundry rooms) or where it may be subjected to
water projections or spray.
The module is fixed to the wall, make sure the support is
t
sufficiently strong.
Fix the module using screws/wall plug fixings adapted to
t
the wall structure and the module weight.
When possible, allow a space of minimum 70 cm below
t
and 30 cm on each side of the module for piping
connections and ease of maintenance.
See paragraphs Water connections.
t
In case of installation with fan coils, a minimum water
t
quantity of 3 liters / kW is required; install a buffer tank
if required.
Installation recommendations
Features
2 zone kit
Dimensions
Unit
H (mm)
mm
485
W (mm)
mm
450
D (mm)
mm
330
Packing
H (mm)
mm
565
W (mm)
mm
530
D (mm)
mm
410
Weight
Unit
kg
Gross
kg
Hydraulic data
Hydraulic connections
inch
1'' M
Operating water pressure
kPa / bar
100 / 1
Maximum pressure
kPa / bar
300 / 3
Hydraulic components
Pump
Nr
2
Type
water cooled
Nr of speed
3
Static pressure
kPa
70
3 way valve
Nr
1
Kv
6,3
Type
modulating
Switching time (90°)
sec
240
Actuator type
3 point - SPDT
230 V
Collector Volume
lt
1
Bleed valve - gas separator
x
Manometer
x
Draining valve
√
Safety valve
kPa / bar
x
Operating Range
Outdoor temperature
water temperature
room temperature
Heating and cooling
°C
same as hydronic module
Electrical data
Power supply
Voltage
V
230
Frequency
Hz
50
Phases
1
Operating voltage limits
V
207-253
Power consumption
W
260
L010129H25_gb.indd 11