T-318
3
−
43
Table 3-9 DataCORDER Pre-Trip Result Records
Test
No.
TITLE
DATA
1-0
Heater On
Pass/Fail/Skip Result, Change in current for Phase A, B and C
1-1
Heater Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
2-0
Condenser Fan On
Pass/Fail/Skip Result, Water pressure switch (WPS)
−
Open/Closed,
Change in currents for Phase A, B and C
2-1
Condenser Fan Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-0
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-1
Low Speed Evaporator Fan
Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-0
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-1
High Speed Evaporator Fan
Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
5-0
Supply/Return Probe Test
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
5-1
Secondary Supply Probe Test
Pass/Fail/Skip Result
5-2
Secondary Return Probe Test
Pass/Fail/Skip Result
6-0
Compressor On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
6-1
Not Applicable
Not Used
6-2
Suction Modulation Valve
Open and Closed
Pass/Fail/Skip Result, Is current or pressure limit in effect (Y,N)
6-4
Not Applicable
Not Used
6-5
Not Applicable
Not Used
7-0
High Pressure Switch Closed
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
7-1
High Pressure Switch Open
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
8-0
Perishable Heat
Pass/Fail/Skip Result, STS, time it takes to heat to 16
°
C (60
°
F)
8-1
Perishable Pull Down
Pass/Fail/Skip Result, STS, time it takes to pull down to 0
°
C (32
°
F)
8-2
Perishable Maintain
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
9-0
Defrost Test
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
10-0
Frozen Mode Set-up
Pass/Fail/Skip Result, STS, time unit is in heat.
10-1
Frozen Mode Pull Down
Pass/Fail/Skip Result, STS, time to pull down unit to -17.8
°
C (0
°
F).
10-2
Frozen Mode Maintain
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.