background image

6

AIR DELIVERY -- CFM (BOTTOM RETURN WITH FILTER)

UNIT SIZE

RETURN-AIR

SPEED

TAPS

2

EXTERNAL STATIC PRESSURE (IN.W.C.)

RETURN AIR

CONNECTION

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

040---10

SIDE/BOTTOM

Black

1100

1055

1010

960

905

850

795

740

685

620

Yellow

955

915

875

830

790

740

695

645

590

530

Blue

820

795

765

730

695

655

615

570

515

460

Red

730

710

680

655

625

595

555

515

465

400

060---10

SIDE/BOTTOM

Black

1340

1295

1245

1190

1130

1065

1005

895

815

725

Yellow

1035

1010

980

945

910

865

795

730

665

605

Blue

845

825

810

785

755

710

670

625

570

515

Red

5

770

750

730

710

675

640

600

560

510

455

060---14

SIDE/BOTTOM

Black

1665

1615

1550

1485

1420

1345

1270

1190

1105

985

Yellow

1340

1320

1295

1260

1215

1165

1110

1045

925

850

Orange

1050

1045

1035

1015

995

960

915

845

785

725

Blue

985

980

975

950

930

900

845

795

740

690

Red

5

735

720

700

675

650

620

595

560

520

480

080---16

SIDE/BOTTOM

Black

1870

1810

1740

1670

1600

1525

1440

1355

1270

1180

Yellow

1525

1495

1460

1415

1365

1305

1240

1170

1090

990

Orange

1375

1355

1330

1300

1260

1210

1155

1090

1025

940

Blue

1045

1040

1030

1010

985

960

920

875

825

745

Red

5

880

865

850

835

810

785

750

715

665

605

080---20

BOTTOM or

TWO-SIDES

3,4

Black

2390

2320

2230

2125

2025

1920

1825

1720

1600

1475

Yellow

2010

1970

1925

1875

1805

1730

1655

1560

1460

1350

Orange

1670

1660

1650

1620

1585

1550

1485

1410

1330

1225

Blue

1500

1500

1495

1485

1460

1425

1380

1320

1255

1165

Red

1270

1260

1255

1245

1225

1195

1160

1125

1065

1000

100---14

SIDE/BOTTOM

Black

1780

1735

1685

1625

1565

1495

1415

1325

1240

1145

Blue

1605

1565

1520

1465

1410

1340

1265

1190

1110

1020

Yellow

1345

1310

1270

1225

1175

1120

1060

995

920

835

Orange

5

1130

1090

1045

1000

945

895

840

775

715

635

Red

5

900

855

800

750

695

640

590

525

470

405

100---20

BOTTOM or

TWO-SIDES

3,4

Black

2510

2420

2330

2240

2145

2040

1920

1805

1675

1520

Yellow

2030

2010

1970

1925

1870

1805

1725

1630

1525

1400

Orange

1655

1660

1650

1635

1615

1575

1520

1450

1360

1270

Blue

1520

1520

1520

1520

1500

1475

1430

1360

1290

1200

Red

1265

1255

1250

1240

1225

1205

1175

1135

1085

1025

120---20

BOTTOM or

TWO-SIDES

3,4

Black

2470

2375

2280

2175

2065

1940

1820

1695

1580

1475

Blue

2275

2210

2125

2045

1945

1835

1715

1605

1500

1395

Yellow

1690

1685

1670

1640

1590

1525

1455

1385

1295

1210

Orange

5

1460

1465

1450

1430

1400

1355

1315

1255

1185

1105

Red

5

1310

1300

1290

1265

1245

1210

1165

1120

1060

985

NOTE

:

1. A filter is required for each return---air inlet. Airflow performance includes a 3/4---in. (19 mm) washable filter media such as contained in a factory---author-

ized accessory filter rack. See accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c.. available external static

pressure.

2. Blower speed taps are not always in the same order. Factory default blower connections are as follows:

a. Heating airflow --- BLUE (also used for Continuous Fan)

b. Cooling airflow --- BLACK (enabled when the Y terminal is energized)

ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.

3. Airflows over 1800 CFM require bottom return, two---side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is required.
4. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
5. Highlighted areas indicate that this airflow range is beyond the range allowed for heating.

THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOL-

ING.

59SC

2A

Summary of Contents for 59SC2A

Page 1: ...exchanger S High quality corrosion resistant prepainted steel cabinet with hemmed edges for safety S Factory configured ready for upflow applications S Direct vent sealed combustion single pipe venting or ventilated combustion air S PSC blower motor single speed inducer motor and single stage gas valve S Self diagnostics with SuperBrite LED S Approved for Twinning applications 60 14 through 120 60...

Page 2: ...gn with more than ten years of field proven performance and success These innovations paired with the continuation of a crimped no weld seam create an efficient robust design for this essential component The condensing heat exchanger a stainless steel fin and tube design is positioned in the furnace to extract additional heat Stainless steel coupling box componentry between heat exchangers has exc...

Page 3: ...tration System Field Supplied Filter Used for Certified Watt Data KGAWF1606UFR KGAWF1306UFR KGAWF1406UFR KGAWF1506UFR Electrical Data 040 10 060 10 060 14 080 16 080 20 100 14 100 20 120 20 Input Voltage Volts Hertz Phase 115 60 1 Operating Voltage Range Min Max 104 127 Maximum Input Amps Amps 6 8 7 0 8 4 9 6 14 5 7 6 14 6 14 9 Unit Ampacity Amps 9 5 9 7 11 5 13 0 19 1 10 4 19 2 19 6 Minimum Wire ...

Page 4: ...16 040 40 000 BTU 060 60 000 BTU 080 80 000 BTU 100 100 000 BTU 120 120 000 BTU Not all familes have these models 140 140 000 BTU A12040 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS VALVE MAIN LIMIT SWITCH BEHIND GAS VALVE REPRESENTATIVE DRAWING ONLY SOME MODELS MAY VARY IN APPEARANCE ELECTRICAL JUNCTION BOX IF REQUIRED LOCATION MAY VARY MEDIA CABINET OPERATING INSTRUCTIONS...

Page 5: ... designed system airflow and static pressure Use optional IAQ Device Duct Adapters as required 6 Available from Replacement Components group 7 Kit coming soon Expected availability 2Q2012 1 CSA requires that a termination kit be used See latest PD for pipe and kit size selection The qualified installer or agency must use only factory authorized kits when modifying these furnaces EZ Flex Cabinet Si...

Page 6: ...60 995 920 835 Orange 5 1130 1090 1045 1000 945 895 840 775 715 635 Red 5 900 855 800 750 695 640 590 525 470 405 100 20 BOTTOM or TWO SIDES 3 4 Black 2510 2420 2330 2240 2145 2040 1920 1805 1675 1520 Yellow 2030 2010 1970 1925 1870 1805 1725 1630 1525 1400 Orange 1655 1660 1650 1635 1615 1575 1520 1450 1360 1270 Blue 1520 1520 1520 1520 1500 1475 1430 1360 1290 1200 Red 1265 1255 1250 1240 1225 1...

Page 7: ...45 13 7 198 60 4 232 70 7 NA NA 60 000 27 8 2 127 38 7 222 67 7 250 76 2 NA 80 000 17 5 2 64 19 5 165 50 3 222 67 7 249 75 9 100 000 NA 22 6 7 104 31 7 223 68 0 250 76 2 120 000 NA NA 11 3 4 93 28 3 237 72 2 140 000 4 NA NA NA 80 24 4 185 56 4 3001 to 4000 914 to 1219 40 000 39 11 9 184 56 1 214 65 2 NA NA 60 000 23 7 0 119 36 3 210 64 0 235 71 6 NA 80 000 15 4 6 59 18 0 155 47 2 210 64 0 232 70 7...

Page 8: ...t equals the Maximum Equivalent Vent Length MEVL from Table 1 or Table 3 minus the number of elbows multiplied by the deduction for each elbow in Table 2 Standard vent terminations and concentric vent terminations count for zero deductions See Vent Manufacturers data for equivalent lengths of flexible vent piping DO NOT ASSUME that one foot of flexible vent pipe is equivalent to one foot of standa...

Page 9: ...8 63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51 8 120 000 NA NA NA 56 17 1 164 50 0 140 000 4 NA NA NA 23 7 0 42 12 8 9001 to 10 000 2743 to 3048 40 000 5 1 5 110 33 5 115 35 1 NA NA 60 000 NA 76 23 2 142 43 3 156 47 5 NA 80 000 NA 31 9 4 103 31 4 1...

Page 10: ...0 2 33 8 27 1 6 1 21 3 47 9 40 5 32 6 20 30 Ft 20 25 23 14 1 20 70 94 77 57 20 70 113 94 71 M 6 1 7 6 7 0 4 3 0 3 6 1 21 3 28 7 23 5 17 4 6 1 21 3 34 4 28 7 21 6 40 40 Ft 20 14 12 3 0 20 70 71 56 38 20 70 86 70 50 M 6 1 4 3 3 7 0 9 0 0 6 1 21 3 21 6 17 1 11 6 6 1 21 3 26 2 21 3 15 2 100000 20 10 Ft N A 25 99 89 78 N A 25 110 233 265 N A 25 110 235 229 M N A 7 6 30 2 27 1 23 8 N A 7 6 33 5 71 0 80 ...

Page 11: ...eat exchangers motors and controls 60 80 27 C 16 C SUPPLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sides of Supply Plenum 1 in 25 mm Sides 0 0 mm Vent 0 0 mm Top of Furnace 1 in 25 mm Recommended COMBUSTION AIR PIPE FOR NON DIRECT 1 PIPE VENT APPLI...

Page 12: ... Coil Assembly or Coil Box 22 1 8 562 0 19 482 6 23 3 4 603 3 20 3 8 517 5 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric Vent Kit A93086 A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the other allowing venting through the inner pi...

Page 13: ...NAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower ope...

Page 14: ...14 DIMENSIONAL DRAWING A11593 59SC2A ...

Page 15: ...l have reusable type filters Filter shall be ______ in mm X ________ in mm An accessory highly efficient Media Filter is available as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted galvanized steel Draft Inducer Motor Draft inducer motor shall be single speed design Primary Heat Exchangers Primary heat exchangers shall be 3 Pass corrosion resist...

Page 16: ...10 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 01 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 59SC2A 01PD Replaces New 59SC2A ...