background image

Step 5—Oil Burner

This furnace is supplied with a high-pressure atomizing retention
head-type burner (for use with grade 1 or 2 Fuel Oil). The Riello
oil burner operates with a prepurge period of 10 sec and a safety
timing of 5 sec. The burner flange is factory installed for an
insertion length of 3-3/4-in. The oil pump is set to operate on a
single line system. To operate on a two-line system the by-pass
plug must be installed.

Step 6—Oil Connections

UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
This burner is shipped with the oil pump set to operate on a
single line system. To operate on a two-line system the
by-pass plug must be installed. Do not operate a single line
system with the by-pass plug installed. Operating a single line
system with the by-pass plug installed will result in damage to
the pump shaft seal. Pump pressure must be set at time of
burner start-up. A pressure gauge is attached to the PRES-
SURE PORT 
for pressure readings. Two PIPE CONNEC-
TORS 
are supplied with the burner for connection lines to
burner pipe connectors. All pump port threads are British
Parallel Thread 
design. Direct connection of NPT threads to
the pump will damage the pump body. Riello manometers
and vacuum gauges do not require any adapters, and can be
safely connected to the pump ports. An NPT (metric) adapter
must be used when connecting other gauge models.

Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.

Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2-pipe system may be used if
desired.

An oil filter should be used with all oil burners and should be
installed as close to burner as possible.

Step 7—Barometric Draft Control

The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control.

Step 8—Electrical Connections

ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in serious injury,
death, or property damage.
The unit cabinet must have an uninterrupted or unbroken
electrical ground to minimize personal injury if an electrical
fault should occur. A green ground screw is provided in
control box for this connection.

115V WIRING

Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility
is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 7 for equipment electrical specifications.

Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70-2001 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or subauthorities having jurisdiction.

FIRE HAZARD
Failure to follow this warning could result in serious injury,
death, or property damage.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.

The control system depends on correct polarity of power supply.
Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig.
4.

A separate line voltage supply MUST be used with a fused
disconnect switch or circuit breaker between main power panel
and unit. (See Fig. 4.)

Metallic conduit (where required/used) may terminate at side panel
of unit. It is not necessary to extend conduit inside unit from side
panel to control box.

When replacing any original furnace wiring, use only 105°C No.
14 AWG copper wire.

24–V WIRING

Instructions for wiring thermostat (field supplied) are packed in
thermostat box. Make thermostat connections as shown in Fig. 5 to
8 at 24-v terminal board on electronic control board. Thermostat
wire connections at R and W are the minimum required for oil
heating operation.

ACCESSORY INSTALLATION

1. General

When installing optional accessories to this appliance, follow
manufacturer’s Installation Instructions included with acces-
sory. Other than wiring for thermostat, wire with a minimum
of type

T

insulation (63°F rise) must be used for accessories.

2. Auxiliary Terminals

The HUM 120 VAC terminals on the electronic control board
are tied directly to the #8 pin of the 9 pin connector and
provide a 120 VAC signal whenever the burner is energized.
(See Fig. 4.) Supplementary 120 VAC and neutral terminals
can be used for accessory wiring. See Electronic Air Cleaner
and Humidifier sections for further information.

3. Electronic Air Cleaner Connections

When using an electronic air cleaner with variable-speed
oil-fired furnaces, use an Airflow Sensor kit. As the air cleaner
is connected to constant 120 VAC power, the airflow sensor
turns on the electronic air cleaner when the furnace blower is
operating.

4. Humidifier/Humidistat Connections

To ensure humidifier will operate properly, use HUM output
of Humidistat Control to control humidifier operation. A
24-VAC signal can be connected from the W and C on
terminal block connections on the electronic board or a 120
VAC signal from the

HUM 120 VAC

terminal when

primary heating source is used. (See Fig. 4-8.)

5. Dehumidify Capability with Standard Humidistat Connection

Latent capabilities for systems using the variable-speed oil-
fired furnaces are better than average systems. If increased
latent capacity is an application requirement, the field wiring
terminal block provides connection terminals for use of a
standard humidistat.

7

Summary of Contents for 58VLR

Page 1: ...4 Blower Removal 14 SAFETY CONSIDERATIONS FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VI CINITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT CARBON MONOXIDE POISONING FIRE EXPLOSION HAZARD Failure to follow this warning coul...

Page 2: ...le Ontario M9W 1R3 Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAU TION These words are used with the safety alert symbol DAN GER identifies the most serious hazards which will result in severe personal injury or death ...

Page 3: ...d or drawing combustion products into the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion This is to minimize the corrosive effects of adhesives sealers and other construction materials It also prevents the entrainment of drywall dust into combustion a...

Page 4: ...e location should not interfere with proper circulation of air within the confined space See NFPA 31 Section 1 5 In addition to air needed for combustion process air shall be provided as required for cooling of equipment or material controlling dew point heating drying oxidation or dilution safety exhaust and odor control In addition to air needed for combustion air shall be supplied for ventilati...

Page 5: ...her within 12 in of floor Each opening must have a free area of at least 1 sq in per 1000 Btuh of total input rating but not less than 100 sq in Refer to Table 4 All Air From Outside the Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating with the outdoors the...

Page 6: ...ation in chimney or vent If dete rioration is discovered chimney must be repaired or vent must be replaced 2 Inspection to ascertain that vent system is clear and free of obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused chimney or vent connections ar...

Page 7: ... electrical connections in accordance with National Electrical Code NEC ANSI NFPA 70 2001 and any local codes or ordinances that might apply For Canadian installations all electrical connections must be made in accordance with Canadian Electrical Code CSA C22 1 or subauthorities having jurisdiction FIRE HAZARD Failure to follow this warning could result in serious injury death or property damage D...

Page 8: ...Fig 4 Wiring Diagram A04182 8 ...

Page 9: ...e Wiring with 1 Speed Air Conditioner Fig 6 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04184 A04185 Fig 7 24 VAC Oil Furnace Wiring with 1 Speed Heat Pump A04186 Fig 8 24 VAC Oil Furnace Wiring with 2 Speed Heat Pump 9 ...

Page 10: ...and vent for 10 seconds establishing the combustion air pattern During this time the solenoid valve holding oil pressure will be approximately 100 psig Solenoid valve opens allowing oil to flow through nozzle At the same time the burner motor s ignition coil produces spark 3 Spark ignites oil droplets 4 Cad cell senses flame and burner continues to fire Ignition transformer ceases sparking 5 After...

Page 11: ...When the thermostat is satisfied the furnace BLWM continues operating at 50 percent heating airflow for an additional 3 min 3 Opening only R Y Y2 circuit switches BLWM to heat pump low heat airflow DEFROST When furnace controls R to W W1 and Y Y2 circuits are closed furnace control CPU starts and burner and BLWM operation is at oil heating airflow during defrost Step 3 Combustion Check In order to...

Page 12: ...rities such as burning to 1 side or pulsating flame patterns should be corrected by changing nozzle Step 4 Fan Adjustment Check This furnace is equipped with a variable speed motor The blower is factory set to deliver the required airflow for 0 75GAL HR US INPUT and 3 0 tons air conditioning for the 58VLR105 See Tables 11A 11B and 11C The blower is factory set to deliver the required airflow for 0...

Page 13: ... R1 JW6 R3 D20 D1 D3 D04 D02 D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will illuminate whenever the limit switch is open 2 The Green LED below the left end of P 1 will flash when the blower motor is operating The LED will flash one time for each 10...

Page 14: ...any heat exchanger gaskets with new gaskets when any heat exchanger plates or covers are re moved could lead to heat exchanger leakage sooting and or a hazardous condition capable of causing personal injury or death This furnace should never be operated without an air filter Disposable filters should be replaced at least once a year If equipped to provide cooling filters should be replaced a minim...

Page 15: ...the CFM is reduced by 15 COOLING MODE OR HEAT PUMP HEATING MODE 2 SPEED LOW 24 VAC INPUT R TO G Y1 AND O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM with SW3 ADJ Dip Switch A Position CFM with SW3 ADJ Dip Switch B Position CFM with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 3 0 580 635 520 B 1 ON 2 OFF 2 5 480 530 435 C 1 OFF 2 ON 2 0 385 425 345 D 1 ON 2 ON 1 5 290 320 260 NOTE In ...

Page 16: ...D O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM with SW3 ADJ Dip Switch A Position CFM with SW3 ADJ Dip Switch B Position CFM with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 5 0 965 1060 865 B 1 ON 2 OFF 4 0 770 845 695 C 1 OFF 2 ON 3 5 675 740 605 D 1 ON 2 ON 3 0 580 635 520 NOTE In Cooling Dehumidification mode with no 24 VAC input to DH the CFM is reduced by 15 DELAY PROFILE FOR ...

Page 17: ...ct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Pac...

Page 18: ...18 ...

Page 19: ...19 ...

Page 20: ...231 58vlr2si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80171 Printed in U S A Form 58VLR 2SI Pg 20 2 05 Replaces 58VLR 1SI ...

Reviews: