GUIDE SPECIFICATIONS
GENERAL

System Description

Furnish a ______________________ (upflow) gas--fired

condensing furnace for use with natural gas or propane (factory--
authorized conversion kit required for propane); furnish cold air

return plenum; furnish external media cabinet for use with
accessory media filter or standard filter.

Quality Assurance

Unit will be designed, tested and constructed to the current ANSI
Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z

21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star

R

and Blue Flame

R

labels.

Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the

latest AHRI Consumer’s Directory of Certified Efficiency
Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and

handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only. Warranty certificate available upon

request.

Equipment

Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and

dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,

and have infinitely variable speed from 300--1300 RPM
operating only when 24--VAC motor inputs are provided. Blower

motor shall be direct drive and soft mounted to the blower scroll

to reduce vibration transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(X) ________ in. An accessory highly efficient Media Filter is

available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted

galvanized steel.

Performance 96

Two--Stage/Variable Speed Gas Furnace

58UVB

ECM Inducer Motor
ECM Inducer motor shall be variable speed design, soft mounted

to assembly to reduce vibration transmission.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass 20 gauge corrosion--
resistant aluminized steel of fold--and--crimp sectional design and

applied operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a flow--through design

having a patented interior laminate coating of polypropylene for
greater corrosion resistance with fold--and--crimp design and

applied operating under negative pressure.
Controls
Controls shall include a micro--processor--based integrated

electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control,

a self--test feature that checks all major functions of the furnace,
and a replaceable automotive--type circuit protection fuse.

Multiple operational settings available, including separate blower

speeds for low heat, high heat, low cooling, high cooling and
continuous fan. Continuous fan speed may be adjusted from the

thermostat. Cooling airflow will be selectable between 350 or 400
CFM per ton of air conditioning. Features will also include

temporary reduced airflow in the cooling mode for improved

dehumidification when a Thermidistat is selected as the
thermostat.

Operating Characteristics

Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be 95% AFUE.
Air delivery shall be ________________ cfm minimum at 0.50
in. wc. external static pressure.
Dimensions shall be: depth_________in.; width __________in.;
height___________in. (casing only). Height shall be

_________in. with A/C coil and _________________in. overall

with plenum.

Electrical Requirements

Electrical supply shall be 115 volts, 60 Hz, single--phase

(nominal). Minimum wire size shall be ________AWG;
maximum fuse size of HACR--type designated circuit breaker

shall be _________ amps.

Special Features

Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.

Copyright 2010 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:58UVB---2PD

Replaces: 58UVB--1PD

Printed in U.S.A.

Edition date: 09/10

58U

VB

Summary of Contents for 58UVB PERFORMANCEt 96

Page 1: ...s the Performance 96 ideal for use with split system cooling including 2 stage units A Carrier electronic air cleaner humidifier Thermidistatt comfort ventilator and Comfort Zonet II will provide year round comfort and efficiency Designed for durability comfort and reliability the Performance 96 is the ultimate in versatile efficient comfort PERFORMANCE 96 FEATURES BENEFITS IdealHumidity Technolog...

Page 2: ...iver correct airflow independent of variations in system restrictions For example dirty filter or zone damper changes during a cycle A special dehumidification function allows direct input from a thermidistat or humidistat This input adjusts system airflow for greater humidity removal and increased cooling comfort during summer months Direct Venting The Performance 96 must be installed as a 2 pipe...

Page 3: ...ed polypropylene laminated steel to ensure durability 8 Pressure switches ensure adequate flow of flue products through furnace and out vent system 9 Inducer motor Pulls hot flue gases through the heat exchangers maintaining negative pressure for added safety 10 Condensate drain connection Collects moisture condensed during combustion process 11 Heavy duty blower Circulates air across the heat exc...

Page 4: ...r Model EACA X X X X X Mechanical Air Cleaner Model FILCAB or EZXCAB X X X X X Humidifier Model HUM X X X X X Heat Recovery Ventilator Model HRV X X X X X Energy Recovery Ventilator Model ERV X X X X X UV Lights Model UVL X X X X X EZ Flex Media Filter with end caps 16 in 9 pack EXPXXLMC0016 X EZ Flex Media Filter with end caps 20 in 9 pack EXPXXLMC0020 X X X EZ Flex Media Filter with end caps 24 ...

Page 5: ...K52EA123 X X X Gas Orifice Kit Size 42 Qty 50 KGAHA0150N42 See Installation Instructions for model altitude and heat value usages Gas Orifice Kit Size 43 Qty 50 KGAHA0250N43 Gas Orifice Kit Size 44 Qty 50 KGAHA0350N44 Gas Orifice Kit Size 45 Qty 50 KGAHA0450N45 Gas Orifice Kit Size 46 Qty 50 KGAHA0550N46 Gas Orifice Kit Size 47 Qty 50 KGAHA1550N47 Gas Orifice Kit Size 48 Qty 50 KGAHA850N48 Gas Ori...

Page 6: ...eed Air Conditioner _F _C Auto Changeover 7 Day Programmable TB PAC For use with 1 speed Air Conditioner _F _C Auto Changeover 5 2 Programmable TP PRH For use with two stage applications _F _C Auto Changeover 7 Day Programmable TP PRH For multi use stage configurations _F _C Auto Changeover 7 Day Programmable Model HP 2 Stage thermostat must be field converted to air conditioner operation Hybrid H...

Page 7: ... ECM BLOWER HARNESS CONNECTOR PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR EAC 1 TERMINAL 115 VAC 1 0 AMP MAX 115 VAC L1 LINE VOLTAGE CONNECTIONS 115 VAC L2 NEUTRAL CONNECTIONS PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR 24 V THERMOSTAT TERMINALS DATE CODE XXXXN FACTORY TEST A09679 A93086 Concentric Vent Direct Vent 2 Pipe Only A concentric vent kit allows vent and combustion air pipes to terminate ...

Page 8: ...in a constant comfortable temperature level in the home For the ultimate in home comfort Carrier s 2 4 or 8 zone systems allow temperature control of individual zones of the home This is accomplished through a series of electronic dampers and remote room sensors The 4 zone system is shown A04336 Energy Heat Recovery Ventilator Carrier s energy or heat recovery ventilators exhaust stale indoor air ...

Page 9: ... 40 70 High 35 65 40 70 35 65 45 75 45 75 Certified Ext Static Pressure ESP in wc Heating 0 12 0 15 0 15 0 20 0 20 Cooling 0 50 0 50 0 50 0 50 0 50 Airflow CFM Heating Low 635 700 860 945 880 970 1105 1215 1325 1455 Heating High 1070 1245 1490 1525 1900 Cooling Max 1400 1372 1975 1950 2060 Output Capacity Btuh ICS Low 37 000 50 000 50 000 63 000 75 000 High 56 000 75 000 75 000 94 000 113 000 AFUE...

Page 10: ...1110 1110 1110 1110 1110 1110 1110 1110 High Heat 1525 0 1 0 1525 1525 1525 1525 1525 1525 1525 1510 1495 1470 2 Ton A C Cooling 700 0 0 50 700 690 690 690 690 2 1 2 Ton A C Cooling 875 0 0 50 835 845 855 860 865 3 Ton A C Cooling 1050 0 1 0 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 3 1 2 Ton A C Cooling 1225 0 1 0 1170 1190 1205 1220 1225 1225 1225 1225 1225 1225 4 Ton A C Cooling 1400 0 ...

Page 11: ...46 1 KGAVT0801CVT 38 7 8 987 4 3 78 2 4 1 2 114 3 21 1 8 536 6 7 3 8 189 3 6 1 2 165 1 Dimension A will change proportionally as dimension D is lengthened or shortened Dimension D may be lengthened to 60 in 1524 mm maximum Dimension D may also be shortened by cutting the pipes provided in the kit to 12 in 304 8 mm minimum CONDENSATE TRAP CONDENSATE TRAP INSIDE BLOWER SHELF ALTERNATE DRAIN TUBE LOC...

Page 12: ... 1 2 IN DIA 13mm GAS CONN 7 8 IN DIA 22mm POWER CONN 1 2 IN DIA 13 mm THERMOST AT ENTRY 2 IN 51 mm VENT CONN 14 1 2 TYP SIDE INLET 9 7 16 TYP 26 15 16 TYP CONDENSATE DRAIN LOCATION UPFLOW 30 1 2 9 16 TYP CONDENSATE DRAIN LOCATION UPFLOW E INLET 11 16 11 16 D 13 16 13 16 OUTLET A AIRFLOW 26 1 4 26 1 4 CONDENSATE DRAIN ALTERNATE 1 2 IN DIA GAS CONN 684 mm 667 mm 622 mm 567 mm 368 mm 32 mm 25mm 591 m...

Page 13: ...CE COM R W C Y R G GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING Connect Y Y2 terminal as shown for proper operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be replaced use same type or equivalent wire 208 230 OR 460 VOLT THREE PHASE 208 230 VOLT SINGLE PHASE WHT BLK WHT B...

Page 14: ...centric 1 1 2 42 12 8 37 11 2 32 9 8 27 8 2 22 6 7 17 5 2 2 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 80 000 2 Pipe or 2 In Concentric 1 1 2 25 7 6 20 6 1 15 4 6 10 3 0 5 1 5 NA 2 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 100 000 2 Pipe or 2 In Concentric 2 38 11 6 33 10 1 28 8 5 23 7 0 18 5 5 13 4 0 2 1 2 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 120 000 2 Pipe or 3 In Concentri...

Page 15: ...7 56 17 1 51 15 5 46 14 0 100 000 2 Pipe or 2 In Concentric 2 27 8 2 22 6 7 17 5 2 12 3 7 7 2 1 NA 2 1 2 62 18 9 60 18 3 58 17 7 56 17 1 55 16 8 53 16 2 120 000 2 Pipe or 3 In Concentric 3 one disk 43 13 1 41 12 5 39 11 9 37 11 3 35 10 7 34 10 4 ALTITUDE UNIT SIZE BTUH Termination Type Pipe Dia IN NUMBER OF 90_ ELBOWS 1 2 3 4 5 6 9001 to 10000 60 000 2 Pipe or 2 In Concentric 1 1 2 27 8 2 22 6 7 1...

Page 16: ...3 19 2 20_F 28 9_C 2 51 11 3 4 27 8 3 31 9 4 39 11 9 45 13 7 100 20 20_F 6 7_C 2 1 2 64 41 12 5 70 21 3 70 21 3 70 21 3 70 21 3 0_F 17 8_C 2 1 2 64 21 6 4 42 12 8 48 14 6 59 18 0 68 20 7 20_F 28 9_C 2 1 2 64 11 3 4 28 8 5 33 10 1 41 12 5 49 14 9 120 20 20_F 6 7_C 3 76 49 14 9 70 21 3 70 21 3 70 21 3 70 21 3 0_F 17 8_C 3 76 26 7 9 51 15 5 58 17 7 70 21 3 70 21 3 20_F 28 9_C 3 76 15 4 6 35 10 7 40 1...

Page 17: ...17 TYPICAL INSTALLATIONS COMBUSTION AIR PIPE A C COIL OUTDOOR UNIT VENT PIPE HUMIDIFIER GAS FIRED WATER HEATER ELECTRONIC AIR CLEANER AIRFLOW FRONT OF FURNACE A06511 58UVB ...

Page 18: ...mbly to reduce vibration transmission Primary Heat Exchangers Primary heat exchangers shall be 3 Pass 20 gauge corrosion resistant aluminized steel of fold and crimp sectional design and applied operating under negative pressure Secondary Heat Exchangers Secondary heat exchangers shall be of a flow through design having a patented interior laminate coating of polypropylene for greater corrosion re...

Reviews: