Table 13—Model 58MEB Orifice Size and Manifold Pressure for Correct Input (Continued)
For Use with 040 through 120 Size Furnaces Only
(Tabulated Data is Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level) *
A08375B
*Orifice numbers 45 shown in
BOLD
are factory installed.
Percents of derate are based on midpoints of U.S. altitude ranges.
*Orifice numbers 45 shown in
BOLD
are factory installed.
Percents of derate are based on midpoints of U.S. altitude ranges.
COMPONENT TEST
NOTE
:
The furnace control component test allows all
components to run for a short time; except the gas valve and
humidifier terminal HUM are not energized for safety reasons.
The EAC-1 terminal is energized when the blower is energized.
This feature helps diagnose a system problem in case of a
component failure. The component test feature will not operate if
any thermostat signal is present ant the control and not until all
time delays are completed.
To Begin Component Self-Test:
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or
death.
Blower access panel door switch opens 115-v power to
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
!
WARNING
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the COM-24v
terminal on control to the TEST/TWIN 3/16--in. (5 mm)
quick-connect terminal on control until the LED goes off.
Remove jumper from terminals. (See Fig. 36.)
NOTE
: If TEST/TWIN and COM-24v terminals are jumpered
longer than 2 sec, LED will flash rapidly and ignore component
test request.
Component test sequence is as follows:
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step g
of component test sequence.
c. After 7 seconds the hot surface igniter is energized
for 15 sec., then off.
d. Blower motor operates on Continuous-FAN speed for
10 sec.
e. Blower motor operates on HEAT speed for 10 sec.
f. Blower motor operates on COOL speed for 10 sec.
g. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from
blower door switch, and re-install blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting
below room temperature.
8. Verify that furnace restarts by raising thermostat setting
above room temperature.
Step 5—Adjustments
SET GAS INPUT RATE
Furnace gas input rate on rating plate is for installations at
altitudes up to 2000 ft (609.6 M).
In the U.S.A., the input ratings for altitudes above 2000 ft (609.6
M) must be reduced by 2 percent for each 1000 ft (304.8 M)
above sea level.