11

58MCB

AIR DELIVERY—CFM (With Filter)*

*

A filter is required for each return-air supply.

For horizontal and downflow applications, use “1 side or bottom” or “bottom only” as airflow reference.

UNIT SIZE

RETURN-AIR 

SUPPLY

SPEED

EXTERNAL STATIC PRESSURE (In. wc)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

040-08

1 side

or

bottom

High

Med-Low

Low

1075

850
740

1040

825
700

995
780
650

945
740
620

895
685
565

840
635
515

760
560
455

670
480
385

040-12

1 side

or

bottom

High

Med-High

Med-Low

Low

1470
1315
1125

930

1415
1280
1110

925

1400
1235
1085

910

1285
1180
1045

850

1215
1115

990
830

1120
1035

915
770

995
930
830
705

890
825
740
635

060-08

1 side

or

bottom

High

Med-Low

Low

1100

890
745

1065

865
710

1005

810
670

945
765
625

900
705
565

805
620
505

730
540
425

610
475
360

060-12

1 side

or

bottom

High

Med-High

Med-Low

Low

1430
1270
1070

915

1375
1260
1055

895

1325
1215
1045

885

1275
1160
1015

865

1200
1105

975
840

1135
1035

920
800

1040

950
850
720

935
850
750
650

060-16

1 side

or

bottom

High

Med-High

Med-Low

Low

1700
1500
1325
1205

1695
1465
1295
1170

1640
1435
1265
1145

1580
1385
1230
1110

1545
1355
1190
1080

1450
1300
1150
1035

1380
1250
1105

990

1310
1185
1050

950

080-12

1 side

or

bottom

High

Med-High

Med-Low

Low

1535
1395
1200
1040

1470
1350
1175
1020

1405
1300
1125

990

1330
1225
1065

960

1245
1155
1030

910

1160
1080

970
860

1065

985
890
785

935
880
780
680

080-16

1 side

or

bottom

High

Med-High

Med-Low

Low

1750
1495
1310
1135

1685
1455
1260
1105

1635
1405
1225
1075

1575
1355
1170
1040

1525
1305
1125

995

1445
1250
1095

995

1380
1185
1040

910

1310
1120

980
860

080-20

1 side

or

bottom

High

Med-High

Med-Low

Low

2200
2100
1815
1560

2175
2025
1760
1555

2085
1945
1720
1515

2025
1865
1670
1460

1925
1785
1620
1435

1820
1700
1550
1390

1735
1620
1480
1340

1635
1540
1405
1270

both sides or

1 side and

bottom

High

Med-High

2360
1965

2280
1925

2210
1870

2130
1830

2035
1760

1960
1710

1875
1670

1790
1575

100-16

1 side

or

bottom

High

Med-High

Med-Low

Low

1740
1500
1340
1195

1705
1470
1315
1175

1660
1445
1300
1165

1615
1410
1270
1130

1570
1375
1235
1100

1500
1330
1200
1070

1425
1280
1140
1030

1355
1210
1095

975

100-20

1 side

or

bottom

High

Med-High

Med-Low

Low

2250
2020
1725
1490

2175
1950
1690
1480

2090
1900
1660
1460

2020
1840
1630
1440

1930
1790
1575
1380

1855
1710
1520
1340

1760
1640
1460
1295

1670
1545
1370
1230

both sides or

1 side and

bottom

High

Med-High

2360
1960

2315
1940

2265
1930

2200
1900

2130
1850

2055
1800

1965
1740

1890
1660

120-20

bottom only

High

Med-High

Med-Low

Low

2350
2100
1770
1545

2250
2015
1720
1520

2160
1955
1675
1465

2070
1875
1620
1415

2000
1810
1575
1365

1885
1710
1515
1325

1790
1650
1450
1265

1635
1540
1365
1185

both sides or

1 side and

bottom

High

Med-High

2435
2040

2360
2000

2285
1950

2220
1905

2130
1835

2050
1790

1965
1725

1875
1650

1 side only

High

Med-High

2255
1985

2190
1930

2115
1890

2045
1840

1965
1780

1890
1720

1800
1645

1710
1560

140-20

bottom only

High

Med-High

Med-Low

Low

2285
2020
1675
1460

2210
1970
1650
1445

2140
1920
1620
1430

2065
1870
1590
1400

1990
1805
1560
1370

1910
1730
1510
1320

1830
1660
1450
1275

1745
1590
1390
1230

both sides or 

1 side and 

bottom

High

Med-High

2310
1975

2255
1945

2185
1900

2120
1860

2045
1835

1965
1775

1880
1720

1800
1640

1 side only

High

Med-High

2140
1930

2080
1850

2025
1800

1945
1740

1875
1725

1795
1660

1725
1580

1625
1495

Summary of Contents for 58MCB040

Page 1: ...ryconfiguredforupflow applicationbutcaneasilybemadeready for downflow or horizontal installation With the exception of the 140 size all sizes can be installed with 2 pipe or 1 pipe venting The 140 size can be installed only as a 2 pipe system Horizontal applications offer the ad vantage of reduced space requirements by locating the furnace in an attic or crawlspace freeing space formerly ded icate...

Page 2: ... indicator light to assist in trouble shooting Controltimesblowerstartafter main burners ignite to eliminate cold air blowing into rooms Warranties 20 year Warranty on the heat exchangers Five year Warranty on entire unit Contact your dealer for details Direct or Non direct Venting The 58MCB can be installed as a 1 pipe Non Direct vent or 2 pipe Direct vent furnace except the 140 size which can be...

Page 3: ...products through furnace and out vent system Combustion inducer pulls hot flue gases through the heat exchangers maintaining negative pressure for added safety Condensate drain connection collects moisture condensed during the combustion process Heavy duty blower circulates air across the heat exchangers to transfer heat into the home Air filter and retainer may be used for side or bottom return a...

Page 4: ... HEATING BLOWER CONTROL Off Delay Selectable 90 120 150 or 180 sec BURNERS Monoport 2 2 3 3 3 4 4 4 5 5 6 6 GAS CONNECTION SIZE 1 2 in NPT GAS VALVE Redundant Manufacturer White Rodgers Minimum Inlet Pressure In wc 4 5 Natural Gas Maximum Inlet Pressure In wc 13 6 Natural Gas IGNITION DEVICE Hot Surface UNIT SIZE 040 08 040 12 060 08 060 12 060 16 080 12 080 16 080 20 100 16 100 20 120 20 140 20 G...

Page 5: ...ay Programmable TSTATCCPHP01 B For use with 1 spd Air Conditioner deg F C Auto Changeover 7 Day Programmable TSTATCCP2S01 B For use with 2 spd Air Conditioner deg F C Auto Changeover 7 Day Programmable TSTATCCSAC01 For use with 1 spd Air Conditioner deg F C 5 2 Day Programmable TSTATCCPDF01 B For use with multi stage applications deg F C Auto Changeover 7 Day Programmable TSTATCCPRH01 B For multi ...

Page 6: ...etter condition Moisturizing house hold air also helps to retain nor mal body heat and provides comfort at lower temperatures A93086 CONCENTRIC VENT Direct Vent 2 Pipe Application A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the other allowing venting through the inner pipe and combustion air to be drawn i...

Page 7: ... CONDENSATE DRAIN TRAP LOCATION DOWNFLOW HORIZONTAL RIGHT OR ALTERNATE 1 2 IN DIA GAS CONN NOTES Minimum return air opening at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendation for equivalent diameters 1 For 800 CFM 16 in round or 14 1 2 X 12 in rectangle 2 For 1200 CFM 20 in round or 14 1 2 X 19 1 2 in rectangle 3 For 1600 CFM 22 in round or 14 1 2 X 23 ...

Page 8: ...19 20 1 4 20 3 8 2 24 1 2 Furnace with or without Cased Coil Assembly or KCAKC Coil Box 22 1 8 19 23 3 4 20 3 8 1 LOCATING TAB LOCATING TAB 1 2 3 4 4 3 2 1 B D Assembled Disassembled A97427 A88207 C A 1 1 4 TYP PLENUM OPENING FACTORY SUPPLIED FIELD INSTALLED INSULATION A96211 FIELD SUPPLIED 2 IN DIAMETER PVC PIPE FIELD SUPPLIED 2 IN DIAMETER PVC 90 ELBOW COMBUSTION AIR DISC FACTORY SUPPLIED IN LOO...

Page 9: ... Vent 2 Pipe Application All Model Sizes CONDENSATE TRAP 1 2 OD INDUCER HOUSING DRAIN CONNECTION 1 4 OD COLLECTOR BOX TO TRAP RELIEF PORT 5 8 OD COLLECTOR BOX DRAIN CONNECTION 1 2 IN PVC OR CPVC SCREW HOLE FOR UPFLOW OR DOWN FLOW APPLICATIONS OPTIONAL 1 4 2 7 8 1 8 7 SLOT FOR SCREW HORIZONTAL APPLICATION OPTIONAL WIRE TIE GUIDES WHEN USED 1 2 1 3 4 1 3 4 FRONT VIEW SIDE VIEW FURNACE DOOR FURNACE D...

Page 10: ...cial base No KGASB0201ALL Coil Assembly Part No CD5 or CK5 or Coil Casing PartNo KCAKC Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing Clearance shown is for air inlet and air outlet ends 120 and 140 size furnaces require 1 inch bottomclearance to combustible materials Ø Clearance in inches Dégagemen...

Page 11: ...860 080 20 1 side or bottom High Med High Med Low Low 2200 2100 1815 1560 2175 2025 1760 1555 2085 1945 1720 1515 2025 1865 1670 1460 1925 1785 1620 1435 1820 1700 1550 1390 1735 1620 1480 1340 1635 1540 1405 1270 both sides or 1 side and bottom High Med High 2360 1965 2280 1925 2210 1870 2130 1830 2035 1760 1960 1710 1875 1670 1790 1575 100 16 1 side or bottom High Med High Med Low Low 1740 1500 ...

Page 12: ...NA 2 2 70 67 66 61 61 61 80 000 2 Pipe or 2 in Concentric 2 2 49 44 30 25 25 15 2 1 2 2 1 2 70 70 70 70 70 70 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 35 26 16 16 6 NA 3 3 70 70 70 70 66 61 120 000 2 Pipe or 3 in Concentric 3 NA 14 9 NA NA NA NA NA 3 63 62 62 61 61 61 3 no disk NA 70 70 63 56 50 43 4 no disk 4 no disk 70 70 70 70 70 70 140 000 2 Pipe or 3 in Concentric 3 one disk NA 20 15 10 ...

Page 13: ...55 54 49 48 47 80 000 2 Pipe or 2 in Concentric 2 2 41 36 23 18 17 8 2 1 2 2 1 2 70 70 70 70 70 70 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 29 21 12 11 NA NA 3 3 70 67 62 57 52 47 120 000 2 Pipe or 3 in Concentric 3 no disk NA 42 35 29 22 15 9 NA 3 53 52 50 49 48 47 4 no disk 4 no disk 70 70 70 70 70 70 140 000 2 Pipe or 3 in Concentric 3 no disk NA 12 8 NA NA NA NA 4 no disk NA 42 37 32 27 2...

Page 14: ...40 000 2 Pipe or 2 in Concentric 1 1 2 1 1 2 42 37 32 27 25 20 2 2 57 55 53 51 49 47 60 000 2 Pipe or 2 in Concentric 2 2 45 40 38 33 31 29 80 000 2 Pipe or 2 in Concentric 2 2 30 25 14 9 7 NA 2 1 2 2 1 2 57 55 53 51 49 47 100 000 2 Pipe or 3 in Concentric 2 1 2 2 1 2 21 13 5 NA NA NA 3 3 54 49 44 39 34 29 120 000 2 Pipe or 3 in Concentric NA 3 39 37 35 33 31 29 4 no disk 4 no disk 10 5 NA NA NA N...

Page 15: ... 20 140 20 CERTIFIED TEMP RISE RANGE F 30 60 15 45 45 75 30 60 20 50 40 70 30 60 20 50 45 75 30 60 40 70 50 80 CERTIFIED EXT STATIC PRESSURE Heating 0 10 0 10 0 12 0 12 0 12 0 15 0 15 0 15 0 20 0 20 0 20 0 20 In wc Cooling 0 50 0 50 0 50 0 50 0 50 0 50 0 50 0 50 0 50 0 50 0 50 0 50 AIRFLOW CFM Heating 850 1125 885 1065 1320 1190 1285 1785 1315 1690 1720 1970 Cooling 895 1215 900 1200 1545 1245 152...

Page 16: ... SIZE 14 14 14 14 14 14 14 12 14 12 12 12 MAXIMUM WIRE LENGTH Ft 44 37 44 38 29 36 28 31 27 30 30 30 MAXIMUM FUSE SIZE OR CKT BKR Amps 15 15 15 15 15 15 15 20 15 20 20 20 TRANSFORMER 24v 40va EXTERNAL CONTROL POWER AVAILABLE Heating 12va Cooling 21va AIR CONDITIONING BLOWER RELAY Standard A02174 115 V FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE N...

Page 17: ... FRONT OF FURNACE A05065 COMBUSTION AIR INLET NON DIRECT VENT 1 PIPE APPLICATION COMBUSTION AIR PIPE DIRECT VENT 2 PIPE APPLICATION A C COIL OUTDOOR UNIT VENT PIPE HUMIDIFIER GAS FIRED WATER HEATER ELECTRONIC AIR CLEANER AIRFLOW FRONT OF FURNACE COMBUSTION AIR INLET NON DIRECT 1 PIPE APPLICATION A05064 Typical installations Basement Upflow Application A05064 ...

Page 18: ...ACE A05067 COMBUSTION AIR INLET NON DIRECT VENT 1 PIPE APPLICATION COMBUSTION AIR PIPE ELECTRONIC AIR CLEANER FURNACE CONDENSATE DRAIN REFRIGERATION PIPING AIR CONDITIONING COIL AIRFLOW VENT PIPE FRONT OF FURNACE A05066 DIRECT VENT 2 PIPE APPLICATION COMBUSTION AIR INLET NON DIRECT VENT 1 PIPE APPLICATION Attic Horizontal Application Crawlspace Horizontal Application A05067 A05066 ...

Page 19: ...19 58MCB ...

Page 20: ...with sealed bearings of _____ hp and shall be multiple speed direct drive Blower motor shall be soft mounted to the blower scroll to reduce vibration transmission Filters Furnace shall have reusable type filters Filter shall be ______ in x ______in Casing Casing shall be of 030 in thickness minimum pre painted gal vanized steel Inducer Motor Inducer motor shall be soft mounted to reduce vibration ...