background image

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment

can be hazardous due to system pressures and electrical com-
ponents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment. When
working on air-conditioning equipment, observe all precau-
tions in the literature, tags, and labels attached to the unit,
and other safety precautions that may apply.

Before performing installation, service, or maintenance
operations on unit, turn off main power switch. Elec-
trical shock could cause personal injury.

Table 1 — Accessory Condensate Pump Kit

Contents

ITEM

QTY

Condensate Pump Assembly

1

Detection Unit

1

Detection Unit Mounting Bracket

1

Transparent Detection Unit Vent Tubing

1

1

9

Rubber Hose

1

4.5’ Low Voltage Power Cord

1

16’ Transparent Suction/Discharge Tubing

1

Be sure that the correct kit is selected for installation. Use

part number 53DS-900---062 (115 v) for size 009 cooling
units only and heat pump high wall units. Use part number
53DS-900---064 (230 v) for size 012,018, and 024 cooling
units only and heat pump high wall units.

INSTALLATION

NOTE: For ease of installation, it is recommended that the
detection unit assembly be installed prior to installation of
the fan coil unit.
1. Unpack contents of condensate pump accessory package.

Attach 1-in. hose and transparent vent tubing to detection
unit (see Fig. 2 and 3). Slide mounting bracket onto bot-
tom of detection unit. Uncoil 4.5 ft low voltage power
cord.

2. Remove fan coil mounting bracket from back of unit. Con-

nect detection unit with 1 in. hose to fan coil unit con-
densate drain line (see Fig. 3). Detection unit must be
installed horizontally for proper operation of float switch.
It is recommended that mounting bracket be ce-
mented to inside of the unit located adjacent to the
fan coil drain as depicted on Fig. 3. 
Attach one end of
transparent tubing to detection unit. Connect one end of
low voltage power cord to telephone jack on detection
unit and route cord and transparent tubing through knock-
out on right side of the fan coil unit enclosure (see Fig 3).
Detection unit must be mounted on same plane as con-
densate pan to properly detect condensate level.

3. Determine mounting location of pump assembly unit (for

best operation, it is recommended pump assembly be
mounted in a vertical position with flow arrow on unit
pointing up (see Fig. 1). DO NOT EXCEED 8.2 FT
MAXIMUM LIFT. 
Connect other end of low voltage
power cord from detection unit to telephone jack on pump
assembly. For suction line connection measure distance
between detection unit and pump assembly unit and cut
proper length of transparent tubing and connect between
detection unit and pump assembly.

CONDENSATE
PUMP ASSEMBLY

16' TRANSPARENT
SUCTION/DISCHARGE TUBING

DETECTION UNIT
MOUNTING BRACKET

1" RUBBER HOSE

DETECTION
UNIT

TRANSPARENT
DETECTION
UNIT VENT TUBING

4.5' LOW VOLTAGE
POWER CORD

Fig. 2 — Accessory Condensate Kit Parts

2

Summary of Contents for 53DS-900-062

Page 1: ... closed NC or normally open NO alarm con tacts user optional but recommended The normally closed NC alarm contact is a dry contact rated for 8 amps at 250 volts In the event of a problem such as a clogged filter or pump discharge line the alarm contact can be wired to shut down the entire system and or initiate an audible or visual alarm See Fig 1 The pump will operate whenever the condensate leve...

Page 2: ...ion unit see Fig 2 and 3 Slide mounting bracket onto bot tom of detection unit Uncoil 4 5 ft low voltage power cord 2 Remove fan coil mounting bracket from back of unit Con nect detection unit with 1 in hose to fan coil unit con densate drain line see Fig 3 Detection unit must be installed horizontally forproperoperation of float switch It is recommended that mounting bracket be ce mented to insid...

Page 3: ...wer to your equipment The normally open NO contacts can be used to initiate a vi sual or audible alarm If you do not observe condensate being discharged through the discharge tubing check to be sure lines are not kinked or obstructed and installation parameters have been followed CLEANING AND MAINTENANCE Disconnect all power to unit to avoid possible electrical shock during installation Set unit p...

Page 4: ...ufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3e 2f PC 111 Catalog No 534 009 Printed in U S A Form 40QN 3SI Pg 4 5 99 Replaces New ...

Reviews: