Vertical Packaged Terminal Air Conditioners

HVAC Guide Specifications — 52V

Size Range: 

9,000 to 24,000 Nominal Btuh

Carrier Model Numbers: 

    52VCR (Cooling Only with R-410A Refrigerant)
    52VER (Cooling with Electric Heat and 
                   R-410A Refrigerant)
    52VQR (Heat Pump with R-410A Refrigerant)
    52VWR (Cooling with Hot Water Heat and
                      R-410A Refrigerant)

Part 1 — General

1.01 SYSTEM DESCRIPTION

Packaged, self-contained, vertical through-the-wall
air-cooled terminal heat pump with electric heat,
straight cool with electric heat, or straight cool with
hot water heat unit. Available with wall sleeve, room
cabinet, electric refrigeration system, electric heat-
ing, outside-air grille. Fully charged with R-410A
refrigerant and filled with oil. 

1.02 QUALITY ASSURANCE

System shall be approved and certified by UL. Chas-
sis capacity and efficiency performance shall be
rated in accordance with AHRI Standard 390, latest
edition.

Part 2 — Products

2.01 EQUIPMENT

A. Electrical Characteristics:

1. Refer to schedule on drawings for electrical

characteristics.

2. Disconnect switch shall be factory-installed on

equipment.

B. Cabinet:

Cabinet shall be constructed of 20 gage galvanized
steel, with removable front and side panels. Shall be
fully insulated for sound attenuation and reduced air
infiltration. Adjustable fresh air shall be available to
meet code requirements for fresh air introduction.
Removable front panels shall be provided for access
to controls and unit.

C. Refrigeration System:

1. Direct expansion refrigeration cooling coil shall

have 

3

/

8

-in. OD high-efficiency rifled copper

tubes mechanically bonded to high-efficiency
aluminum fins. All coils shall be factory leak
tested at 350 psig.

2. Hermetically sealed compressor with internal

spring isolation, external isolation, permanent
split capacitor motor and overload protection.

3. Accumulator (heat pump only).
4. Condenser coil and fan.

D. Air System:

Air system shall have centrifugal forward-curved
evaporator fans with three-speed permanent split
capacitor motor, optional filter grille.

E. Heating Coil:

1. Electric heating coil shall be 2 to 10 kW

electric.

2. Hot water heating coil shall have 

3

/

8

-in. OD

high-efficiency rifled copper tubes mechanically
bonded to high-efficiency aluminum fins. All
coils shall be factory leak tested at 350 psig.

F. Condensate Drain:

Condensate drain shall be connected to a common
drain riser. Should the main drain become plugged,
the wall sleeve design shall divert the water to the
outside of the building.

G. Condenser Fan:

Condenser fan shall be a propeller type with sepa-
rate split capacitor motor. 

H. Adjustable Fresh Air:

Outside air intake shall be adjustable to meet code
requirements for fresh air introduction.

I. Wall Sleeves:

Wall sleeves shall be constructed of 20 gage galva-
nized steel to provide weathertight seal with dispos-
able weather guard for installation and baked
enamel finish inside and outside. Sleeve shall allow
water to overflow front edge of sleeve if the primary
drain becomes clogged.

J. Grille:

Grille shall be anodized corrosion-resistant alumi-
num, and custom painted. 

K. Controls:

1. Control module shall be a remote thermostat

with heat anticipator, heat-off-cool switch, on-
auto fan switch. 

2. Evaporator coil freeze protection shall be pro-

vided. During the cooling mode, should the
evaporator coil experience freezing conditions
that could result in ice build-up on the coil and
subsequent compressor damage, a tempera-
ture sensor attached to the coil shall deenergize
the compressor.

3. Low ambient lockout shall be provided to lock

out compressor at ambient temperatures below
40 F to extend compressor life.

4. Random restart shall be provided. When power

is turned on after a power outage, a built-in ran-
dom restart (3 to 4 minutes) shall prevent all
units from restarting simultaneously. Simultane-
ous restarting can damage electrical compo-
nents.

5. Compressor restart delay shall be provided. A

3-minute delay shall ensure that system pres-
sures are allowed to equalize before a compres-
sor restart.

6. Fan delay shall be provided. In the cooling

mode, the fan motor delay shall allow the fan to
continue to operate up to 45 seconds after
thermostat is satisfied.

Guide specifications

Summary of Contents for 52VCR09

Page 1: ...d with a weather guard Flush type exterior architectural louvers Features Benefits Carrier s 52V vertical packaged unit offers design flexibility quality reliabilty and multi function controls Solid s...

Page 2: ...ch sleeve includes a factory installed weather guard to cover the sleeve opening during construction Unique sleeve drain conden sate system A factory installed drain line connects the evaporator drain...

Page 3: ...24 000 Heater Type 00 None ooling Only VE Cooling with Electric Heat VQ Heat Pump VW Cooling with Hot Water Heat Heat Options 02 2 kW Electric Heat sizes 09 and 12 only 03 3 kW Electric Heat 04 4 kW...

Page 4: ...db 60 F wb indoor entering air temperature and 47 F db 43 F wb air entering outdoor unit ELECTRIC HEATER RATINGS 52VER ELECTRIC HEATING AND 52VQR HEAT PUMP UNITS UNIT COOLING CAPACITY Btuh EER 52VCR...

Page 5: ...9 14 7 20 6 32 4 2 0 9 13 6 19 1 30 0 52VWR18 3 Row Coil 760 4 4 7 21 1 29 5 46 3 3 2 7 20 2 28 3 44 5 2 1 3 18 8 26 3 41 3 680 4 4 7 19 7 27 6 43 4 3 2 7 18 9 26 5 41 6 2 1 3 17 6 24 7 38 8 52VWR24 2...

Page 6: ...opening during construction Exterior grilles architectural louvers The exterior grilles attach to the outside face of the wall sleeve and pro vide protection for the unit Interior panel The interior...

Page 7: ...OUTLET CONDENSER INLET 20 66 41 1 4 20 20 LOW VOLTAGE ELECTRICAL KNOCKOUT SERVICE PULLOUT RETURN AIR 6 1 8 10 52VCR VER COOLING ONLY AND COOLING WITH ELECTRIC HEAT UNITS 52VQR09 24 HEAT PUMP UNITS NOT...

Page 8: ...N AIR SERVICE PULLOUT ELECTRICAL KNOCKOUT BLOWER MOTOR 12 3 3 4 1 1 2 3 3 4 2 16 12 3 4 FILTER HOT WATER INLET 1 HOT WATER COIL 52VWR12 24 COOLING WITH HOT WATER HEAT UNITS a52 1342 NOTES 1 Hot water...

Page 9: ...D EXTERIOR GRILLE WALL SLEEVE DIMENSIONS in LEGEND WALL THICKNESS PART NO H W D T 5 8 in 52VX SS 1 43 3 4 21 3 8 26 9 52VX RS 1 52VX RH 1 8 12 in 52VX SS 2 43 3 4 21 3 8 30 13 52VX RS 2 52VX RH 2 12 1...

Page 10: ...C 400 390 380 370 360 350 335 320 LOW H 310 300 290 280 270 260 250 240 18 HIGH 740 730 715 700 685 670 650 630 MEDIUM C 670 660 645 630 615 600 585 570 LOW H 560 550 545 530 515 500 485 470 24 HIGH 9...

Page 11: ...10 200 19 22 20 25 05 4 5 3 38 15 350 11 500 22 25 25 25 18 0 87 1 8 6 5 43 0 72 1 10 00 12 12 20 20 03 3 2 25 10 200 7 700 15 17 20 20 04 4 3 13 600 10 200 19 22 20 25 05 4 5 3 38 15 350 11 500 22 2...

Page 12: ...500 22 25 25 25 06 6 4 50 20 500 15 350 28 33 30 35 08 8 6 00 27 300 20 500 37 43 40 45 10 9 6 75 30 700 23 000 42 48 45 50 24 2 8 1 3 9 9 54 0 74 1 8 03 3 2 25 10 200 7 700 17 19 20 20 04 4 3 00 13...

Page 13: ...C AND MUST BE REMOVED WHEN INSTALLING THE FRONT DESK SWITCH CAP GRN LOCKOUT COOLING GND COM RV LO TEMP LOCKOUT NO BRN RV DEFROST OUTDOOR COM INDOOR BRN GRN RED WHT BLK FD RC R G Y W R G Y W2 C C LEAD...

Page 14: ...ll energize NOTE All three functions are disabled if the 3 minute time delay is active The unit will operate until the thermostat is satisfied Any time that power is applied to the unit and the ther m...

Page 15: ...off Fan operation will be as specified above Reversing valve will remain active Reversing valve heat pump only Type B valves will energize in Heating mode Reversing valve will turn on 15 seconds prior...

Page 16: ...16 RETURN AIR 6 in MIN TO CONDENSATE DRAIN 52V UNIT 1 4 in MIN 1 2 BUBBLE SEALANT WALL SLEEVE EXTERIOR GRILLE a52 1347 Typical installation...

Page 17: ...nditioning systems be properly sized and installed for each application in order to achieve the desired temperature and humidity levels within the space to be conditioned It is strongly recommended th...

Page 18: ...r motor optional filter grille E Heating Coil 1 Electric heating coil shall be 2 to 10 kW electric 2 Hot water heating coil shall have 3 8 in OD high efficiency rifled copper tubes mechanically bonded...

Page 19: ...and hurricane wall sleeve shall be available for coastal areas 2 A thermostat with adjustable high and low tem perature limits shall be available 3 Interior panel shall be available for field install...

Page 20: ...ue or change at any time specifications or designs without notice and without incurring obligations Pg 20 Catalog No 04 52520003 01 Printed in U S A Form 52V 3PD Replaces 52V 2PD Carrier Corporation S...