34
Remote Test/Reset Station’s Trouble LED Does Not
flash When Performing a Dirty Test, But the Control-
ler’s Trouble LED Does:
1. Verify that the remote test/station is wired as shown
in Fig. 47. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the control-
ler’s supervision relay. See “To Configure the Dirty
Sensor Test Operation” for details.
Sensor’s Trouble LED is On, But the Controller’s
Trouble LED is OFF:
Remove JP1 on the controller.
Supply Air Temperature (SAT) Sensor —
On
FIOP--equipped 50HCQ unit, the unit is supplied with a
supply--air temperature (SAT) sensor (p/n:33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor. See
PremierLink
t
Installation, Start--Up and Configuration
Instructions
. for temperature--resistance characteristic.
PREMIERLINK
CONTROL
The PremierLink controller, Fig. 50 is compatible with
Carrier Comfort Network
r
(CCN) devices. This control is
designed to allow users the access and ability to change
factory--defined settings, thus expanding the function of
the standard unit control board. CCN service access tools
include System Pilot
t
, Touch Pilot
t
and Service Tool.
Standard tier display tools Navigator
t
and Scrolling
Marquee are not suitable for use with latest PremierLink
controller (Version 2.x).
The PremierLink control is factory--mounted in the
50TCQ unit’s main control box to the left of the CTB.
Factory wiring is completed through harnesses connected
to the LVTB. Field connections are made at a 16--pole
terminal block (TB1) located on the bottom shelf of the
unit control box in front of the PremierLink controller The
factory--installed PremierLink control includes the
supply--air temperature (SAT) sensor. The outdoor air
temperature
(OAT)
sensor
is
included
in
the
FIOP/accessory EconoMi$er 2 package.
Refer to Fig. 50 for PremierLink connection locations.
NOTE
: Refer to
PremierLink
t
Installation, Start--Up
and Configuration Instructions
. Have a copy of this
manual available at unit start--up.
C08199