
24
Table 1 – Heater Model Number
ACCESSORY
HEATER PART
NUMBER
UNIT MODELS
HEATER/
BASE UNIT VOLTAGE
HEATER KW*
FAN
DISCHARGE
STAGES
CRHEATER270A00
50TCQ-D17—24
208/230---3---60
25
Horizontal
2
CRHEATER271A00
50TCQ-D17—24
208/230---3---60
50
Horizontal
2
CRHEATER272A00
50TCQ-D17—24
208/230---3---60
75
Horizontal
2
CRHEATER273A00
50TCQ-D17—24
460/400---3---60/50
25/17.4
Horizontal
2
CRHEATER274A00
50TCQ-D17—24
460/400---3---60/50
50/34.7
Horizontal
2
CRHEATER275A00
50TCQ-D17—24
460/400---3---60/50
75/52
Horizontal
2
CRHEATER276A00
50TCQ-D17—24
575---3---60
25
Horizontal
2
CRHEATER277A00
50TCQ-D17—24
575---3---60
50
Horizontal
2
CRHEATER278A00
50TCQ-D17—24
575---3---60
75
Horizontal
2
CRHEATER279A00
50TCQ-D17—24
208/230---3---60
25
Vertical
2
CRHEATER240A00
50TCQ-D17—24
208/230---3---60
50
Vertical
2
CRHEATER241A00
50TCQ-D17—24
208/230---3---60
75
Vertical
2
CRHEATER242A00
50TCQ-D17—24
460/400---3---60/50
25/17.4
Vertical
2
CRHEATER243A00
50TCQ-D17—24
460/400---3---60/50
50/34.7
Vertical
2
CRHEATER244A00
50TCQ-D17—24
460/400---3---60/50
75/52
Vertical
2
CRHEATER245A00
50TCQ-D17—24
575---3---60
25
Vertical
2
CRHEATER246A00
50TCQ-D17—24
575---3---60
50
Vertical
2
CRHEATER247A00
50TCQ-D17—24
575---3---60
75
Vertical
2
*
kW rated at 240, 480/400 and 600 volts
C09423
Fig. 35 -- Typical Module Installation
Table 9. Heater Model Number
Bare Heater Model Number
C
R
H
E
A
T
E
R
0
0
1
A
0
0
Heater Sales Package PNO
Includes:
Bare Heater
Carton and packing materials
Installation sheet
C
R
H
E
A
T
E
R
1
0
1
A
0
0
Single Point Boxes and Supplementary Fuses
When the unit MOCP device value exceeds 60--A,
unit--mounted supplementary fuses are required for each
heater circuit. These fuses are included in accessory
Single Point Box, with power distribution and fuse blocks.
The single point kit Fuse Holder and Terminal Block will
be installed into the Unit Control Box----back wall, bottom
left corner. See Fig. 37. The Single Point Box also
includes a set of power taps to complete the wiring
between the Single Point Box and the unit’s main control
box terminals. Refer to accessory heater and Single Point
Box installation instructions for details on tap
connections.