
16
C10013
Fig. 23 -- Mounting Position for Field Disconnects
(up to 100A)
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate.
If the 208/230-v unit is
to be connected to a 208-v power supply, the control
transformer must be rewired by moving the black wire
with the
1
/
4
-inch female spade connector from the 230--v
connection and moving it to the 200-v
1
/
4
-inch male
terminal on the primary side of the transformer.
Refer to
unit label diagram for additional information.
Field power wires are connected to the unit at line--side
pressure lugs at the main terminal block (TB1) or at
factory--installed option non--fused disconnect switch.
Max wire size is #2 AWG (copper only). (See Fig. 25.)
NOTE
: TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points off
the optional disconnect switch. These leads are for factory
run--test purposes only; remove and discard before
connecting field power wires to unit connection points.
Make field power connections directly to line connection
pressure lugs only.
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and furnace. Use only copper wire.
(See Fig. 24.)
!
WARNING
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 24 -- Disconnect Switch and Unit
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
11
13
13
L1
L2
L3
TB1
208/230-3-60
460-3-60
575-3-60
Disconnect
per
NEC
C10015
Fig. 25 -- Power Wiring Connections
All Units —
All field wiring must comply with the NEC and local
requirements.
Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate. See Fig. 25 and the unit label
diagram for power wiring connections to the unit power
terminal blocks and equipment ground. Maximum wire
size is #2/0 AWG per pole.
Provide a ground--fault and short--circuit over--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Tables 29 and 30. On 3--phase units, voltages between
phases must be balanced within 2% and the current within
10%. Use the formula shown in the legend for Tables 29
and 30 (see Note 3 on page 58) to determine the percent
of voltage imbalance.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical
components.
Such
operation
would
invalidate any applicable Carrier warranty.
CAUTION
!
Summary of Contents for 50TCQD
Page 5: ...5 C14192 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Page 6: ...6 C14193 Fig 2 Unit Dimensional Drawing 14 Size Unit cont ...
Page 10: ...10 C10365 Fig 6 Roof Curb Details ...
Page 17: ...17 a50 9707 Fig 26 Typical 50TCQ Control Wiring Diagram ...
Page 18: ...18 a50 9708 Fig 27 Typical 50TCQ Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Page 43: ...43 a50 9710 Fig 50 PremierLinkt Controller Wiring Schematic ...
Page 51: ...51 a50 9711 Fig 66 RTU Open Controller System Wiring Diagram ...