background image

50TC

*D

7

Table 1 – Operating Weights

50TC*D

UNITS KG (LB)

Component

D17

D20

D24

D28

Base Unit

770 (1697)

777 (1712)

1862 (845)

1991 (903)

Economizer

111 (245)

111 (245)

245 (111)

245 (111)

Curb

356 mm/14---in

111 (245)

111 (245)

124 (273)

124 (273)

610 mm/24---in

143 (315)

143 (315)

159 (350)

159 (350)

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different

sequences for the steps of unit installation. For example,

on curb--mounted units, some accessories must be

installed on the unit before the unit is placed on the curb.

Review the following for recommended sequences for

installation steps.

Curb--mounted installation —

Install curb
Install field--fabricated ductwork inside curb
Install thru--base service connection fittings (affects

curb and unit)
Rig and place unit
Remove top skid
Install condensate line trap and piping
Make electrical connections
Install other accessories

Pad--mounted installation —

Prepare pad and unit supports
Rig and place unit
Remove duct covers and top skid
Install field--fabricated ductwork at unit duct openings
Install condensate line trap and piping
Make electrical connections
Install other accessories

Frame--mounted installation —

Frame--mounted applications generally follow the

sequence for a curb installation. Adapt as required to

suit specific installation plan.

Step 3 — Inspect unit

Inspect unit for transportation damage. File any claim

with transportation agency.

Confirm before installation of unit that voltage, amperage

and circuit protection requirements listed on unit data

plate agree with power supply provided.

Step 4 — Provide Unit Support

Roof Curb Mount —

Accessory roof curb details and dimensions are shown in

Fig. 4 (size 17 and 20 units) and Fig. 5 (size 24 and 28

units). Assemble and install accessory roof curb in

accordance with instructions shipped with the curb.

NOTE

: The gasketing of the unit to the roof curb is

critical for a watertight seal. Install gasket supplied with
the roof curb as shown in Fig. 4 and Fig. 5. Improperly
applied gasket can also result in air leaks and poor unit
performance.
Curb should be level. This is necessary for unit drain to

function properly. Unit leveling tolerances are show in

Fig. 6. Refer to Accessory Roof Curb Installation

Instructions for additional information as required.

Install insulation, cant strips, roofing felt, and counter

flashing as shown.

Ductwork must be attached to curb and

not to the unit. Thru--the--base power connection must be
installed before the unit is set on the roof curb.

If electric and control wiring is to be routed through the

basepan remove knockouts in basepan located in control

box area, see Fig. 7 for location. Attach the service

connections to the basepans.

Slab Mount (Horizontal Units Only) —

Provide a level concrete slab that extends a minimum of

150 mm (6–in.) beyond unit cabinet. Install a gravel apron

in front of condenser coil air inlet to prevent grass and

foliage from obstructing airflow.

NOTE

: Horizontal units may be installed on a roof curb

if required.

Alternate Unit Support (In Lieu of Curb or Slab

Mount) —

A non--combustible sleeper rail can be used in the unit

curb support area. If sleeper rails cannot be used, support

the long sides of the unit with a minimum of 4 equally

spaced 102 mm x 102 mm (4--in. x 4--in.) pads on each

side. Locate pads so that they support the rails. Make sure

to avoid the fork openings.

Summary of Contents for 50TC*D17 Series

Page 1: ...use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety g...

Page 2: ...Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death Reli...

Page 3: ...50TC D 3 C09105 Fig 1 Unit Dimensional Drawing 17 and 20 Size Units...

Page 4: ...50TC D 4 C09384 Fig 1 Unit Dimensional Drawing 17 and 20 Size Unit cont...

Page 5: ...50TC D 5 C09095 Fig 2 Unit Dimensional Drawing 24 and 28 Size Unit...

Page 6: ...ces unit performance and service access below around and above unit as specified in unit drawings See Fig 3 NOTE Consider also the effect of adjacent units Unit may be installed directly on wood floor...

Page 7: ...p 4 Provide Unit Support Roof Curb Mount Accessory roof curb details and dimensions are shown in Fig 4 size 17 and 20 units and Fig 5 size 24 and 28 units Assemble and install accessory roof curb in a...

Page 8: ...50TC D 8 C09139 Fig 4 Roof Curb Details 17 and 20 Size Units...

Page 9: ...50TC D 9 C09140 Fig 5 Roof Curb Details 24 and 28 Size Units...

Page 10: ...elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space Due to electric heater supply duct will requir...

Page 11: ...openings see Fig 9 and all ductwork should be secured to the flanges Insulate and weatherproof all external ductwork joints and roof or building openings with counter flashing and mastic in accordance...

Page 12: ...air screens by sliding them into the channel formed by the four angles installed in step 2 Make sure that the screens extend a across the entire length of the hood 9 Install side filter supports usin...

Page 13: ...ollow this warning could result in intermittent operation or performance satisfaction Do not connect aluminum wire between disconnect switch and air conditioning unit Use only copper wire See Fig 16 C...

Page 14: ...cate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions If the thermostat contains a logic circu...

Page 15: ...a specific size unit and duct arrangement vertical or horizontal Refer to the label on the unit cabinet for the list of approved heaters Unit heaters are marked with Heater Model Numbers But heaters...

Page 16: ...he plug with the mating low voltage plug located on the heater ORN BRN HR1 Heater contactor first stage HR2 Heater contactor second stage 2 3 12 1 3 VIO ORN VIO BRN 2 Plug Assembly Elec Htr CTB CONTL...

Page 17: ...s internal timeclock This is necessary for broadcast of time of day functions occupied unoccupied NOTE PremierLink controller is shipped in Sensor mode To be used with a thermostat the PremierLink con...

Page 18: ...50TC D 18 C09376 Fig 26 PremierLink Wiring Schematic...

Page 19: ...with field installation of these accessory control devices Enthalpy control outdoor air or differential sensors Space CO2 sensor Outdoor air CO2 sensor Refer to Table 4 for accessory part numbers Fie...

Page 20: ...nication bus OAQ Outdoor Air Quality CO2 CMPSAFE Compressor Safety RH Relative Humidity FILTER Dirty Filter Switch SFS Supply Fan Status Table 6 Thermostat Mode TB1 TERMINAL FIELD CONNECTION INPUT SIG...

Page 21: ...n the return duct Connect this sensor to TB1 1 and TB1 3 per Fig 28 Configure the unit for Thermostat Mode Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration scr...

Page 22: ...for electrical requirements and terminal locations See Fig 34 for typical CO2 sensor wiring schematic To accurately monitor the quality of the air in the conditioned air space locate the sensor near a...

Page 23: ...B s THERMOSTAT R terminal Connect the other side of the NO contact set to TB1 10 Setpoint for Dirty Filter is set at the switch See Fig 38 R TB1 J4 4 PL Filter Switch NO close on rising pressure high...

Page 24: ...d for the entire network See Table 7 for recommended cable Table 7 Recommended Cables MANUFACTURER CABLE PART NO Alpha 2413 or 5463 American A22503 Belden 8772 Columbia 02525 NOTE Conductors and drain...

Page 25: ...de at on board DIP switches The RTU MP control is factory mounted in the 50TC D unit s main control box to the right of the CTB See Fig 44 Factory wiring is completed through harnesses connected to th...

Page 26: ...50TC D 26 C09377 Fig 45 RTU MP System Control Wiring Diagram...

Page 27: ...e of the default input on the specific channel according to schematic Parallel pins J5 1 J2 6 J5 3 J1 10 J5 5 J1 2 are used for field installation The RTU MP controller requires the use of a Carrier s...

Page 28: ...space sensor requires a separate isolated power supply of 24 VAC See Fig 48 for internal connections at the T 59 Connect the SEN terminal BLU to RTU MP J20 1 Connect the COM terminal BRN to J20 2 Conn...

Page 29: ...mA terminal to RTU MP J4 2 and connect the SIG COM terminal to RTU MP J4 3 See Fig 49 SEN COM J4 2 J4 3 IAQ Sensor 24 VAC C08462 Fig 49 RTU MP Indoor CO2 Sensor 33ZCSENCO2 Connections Outdoor Air Qua...

Page 30: ...vide different kinds of information for different applications In the BAS application many different protocols are used depending on manufacturer Protocols do not change the function of a controller j...

Page 31: ...inute auto logout if a screen is idle See Form 48 50H T 2T Appendix A for navigation and screen content Virtual BACview Virtual BACview is a freeware computer program that functions as the BACview6 Ha...

Page 32: ...45 6 60 48 253 CRHEATER274A00 CRHEATER283A00 50 1 34 7 72 1 80 66 253 CRHEATER275A00 CRHEATER284A00 75 2 52 1 84 7 100 95 253 STD 3 1 47 6 60 50 252 CRHEATER273A00 CRHEATER282A00 25 1 17 4 47 6 60 50...

Page 33: ...4 45 6 60 48 253 CRHEATER274A00 CRHEATER283A00 50 1 34 7 72 1 80 66 253 CRHEATER275A00 CRHEATER284A00 75 2 52 1 84 7 100 95 253 STD 3 1 48 6 60 51 261 CRHEATER273A00 CRHEATER282A00 25 1 17 4 48 6 60...

Page 34: ...4 52 6 60 55 281 CRHEATER274A00 CRHEATER283A00 50 1 34 7 76 9 80 71 281 CRHEATER275A00 CRHEATER284A00 75 2 52 1 89 5 100 100 281 STD 3 1 55 0 60 58 274 CRHEATER273A00 CRHEATER282A00 25 1 17 4 55 0 60...

Page 35: ...4 56 5 70 60 304 CRHEATER274A00 CRHEATER283A00 50 1 34 7 76 9 80 71 304 CRHEATER275A00 CRHEATER284A00 75 2 52 1 89 5 100 100 304 STD 3 1 58 9 70 62 297 CRHEATER273A00 CRHEATER282A00 25 1 17 4 58 9 70...

Page 36: ...zed outside air damper EconoMi er IV with control and integrated barometric relief EconoMi er2 without control for external signal and integrated barometric relief Power Exhaust Differential dry bulb...

Reviews: