background image

50TC

*D

14

Thru--Base Connections —

All units are equipped with the ability to bring utilities

through the base.

The electrical entrance is located in the control box area

and can be accessed through the control box access panel.

An embossed area is provided with three knock outs. High

voltage is brought through the multi knock out by

removing the appropriate size for the size of the fitting

required. A 22 mm (

7

/

8

--in.) knock out is provided for low

voltage.

All required fittings are field supplied. Install fittings

when access to both top and bottom of the base pan is

available.

Units without Thru--Base Connections —

1. Install conduit, liquid tight, between disconnect and

control box.

2. Pull correctly rated high voltage wires through the

conduit.

3. Install power lines to terminal connections as shown

in Fig. 17.

All Units —

Voltage to compressor terminals during operation must be

within voltage range indicated on unit nameplate. On

3--phase units, voltages between phases must be balanced

within 2% and the current within 10%. Use the following

formula to determine the percent of voltage imbalance.

% Voltage Imbalance   =  100 x

max voltage deviation from average voltage

average voltage

C09103

Operation on improper line voltage or excessive phase

imbalance constitutes abuse and may cause damage to

electrical components. Such operation would invalidate

any applicable Carrier warranty.

Field Control Wiring —

The 50TC*D unit requires an external temperature control

device. This device can be a thermostat (field--supplied)

or a PremierLink controller (available as factory--installed

option or as field--installed accessory, for use on a Carrier

Comfort Network or as a stand alone control) or the

RTU--MP Controller for Building Management Systems

using non--CCN protocols (RTU--MP is available as a

factory--installed option only).

Thermostat —

Install a Carrier--approved accessory thermostat according

to installation instructions included with the accessory.

For complete economizer function, select a two--stage

cooling thermostat. Locate the thermostat accessory on a

solid wall in the conditioned space to sense average

temperature in accordance with the thermostat installation

instructions.

If the thermostat contains a logic circuit requiring 24--v

power, use a thermostat cable or equivalent single leads of

different colors with minimum of seven leads. If the

thermostat does not require a 24--v source (no “C”

connection required), use a thermostat cable or equivalent

with minimum of six leads. Check the thermostat

installation instructions for additional features which

might require additional conductors in the cable.

For wire runs up to 15 m (50 ft.), use no. 18 AWG

(American Wire Gage) insulated wire (35

_

C minimum).

For 15 to 23 m (50 to 75 ft.), use no. 16 AWG insulated

wire (35

_

C minimum). For over 23 m (75 ft.), use no. 14

AWG insulated wire (35

_

C minimum). All wire sizes

larger than no. 18 AWG cannot be directly connected to

the thermostat and will require a junction box and splice

at the thermostat.

   Typical
Thermostat
Corrections

Central

Terminal

 Board

W1

Y2

Y1

R

W2

G

C

X

W1

Y2

Y1

R

W2

G

C

X

T–STAT

C

W2

G

W1

O/B/Y2

R

Y1

(Note 1)

(Note 2)

(Note 3)

Note 1:  Typical multi-function marking. Follow manufacturer’s configuration 
 

instructions to select Y2.

Note 2:  Y2 to Y2 connection required on single-stage cooling units when 
 

integrated economizer function is desired

Note 3:  W2 connection not required on units with single-stage heating.

 

   

Field Wiring

C09257

Fig. 18 -- Typical Low--Voltage Control Connections

Unit without thru--base connection —

Correctly rated low voltage wire can be routed through the

rubber grommet located on the corner post adjacent to the

control box access panel. Route wire through the grommet

and then route the wire behind the corner post utilizing the

factory provided wire ties secured to the control box. This

will insure separation of the field low voltage wire and the

high voltage circuit. Route the low voltage wire to the

central terminal board. See Fig. 19.

NOTE

: If utilizing the through the base connections,

route the low voltage wire through the wire ties to the

central terminal board.

Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage

and 0.14 amp for second--stage heating, when available.

Summary of Contents for 50TC*D17 Series

Page 1: ...use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety g...

Page 2: ...Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death Reli...

Page 3: ...50TC D 3 C09105 Fig 1 Unit Dimensional Drawing 17 and 20 Size Units...

Page 4: ...50TC D 4 C09384 Fig 1 Unit Dimensional Drawing 17 and 20 Size Unit cont...

Page 5: ...50TC D 5 C09095 Fig 2 Unit Dimensional Drawing 24 and 28 Size Unit...

Page 6: ...ces unit performance and service access below around and above unit as specified in unit drawings See Fig 3 NOTE Consider also the effect of adjacent units Unit may be installed directly on wood floor...

Page 7: ...p 4 Provide Unit Support Roof Curb Mount Accessory roof curb details and dimensions are shown in Fig 4 size 17 and 20 units and Fig 5 size 24 and 28 units Assemble and install accessory roof curb in a...

Page 8: ...50TC D 8 C09139 Fig 4 Roof Curb Details 17 and 20 Size Units...

Page 9: ...50TC D 9 C09140 Fig 5 Roof Curb Details 24 and 28 Size Units...

Page 10: ...elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space Due to electric heater supply duct will requir...

Page 11: ...openings see Fig 9 and all ductwork should be secured to the flanges Insulate and weatherproof all external ductwork joints and roof or building openings with counter flashing and mastic in accordance...

Page 12: ...air screens by sliding them into the channel formed by the four angles installed in step 2 Make sure that the screens extend a across the entire length of the hood 9 Install side filter supports usin...

Page 13: ...ollow this warning could result in intermittent operation or performance satisfaction Do not connect aluminum wire between disconnect switch and air conditioning unit Use only copper wire See Fig 16 C...

Page 14: ...cate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions If the thermostat contains a logic circu...

Page 15: ...a specific size unit and duct arrangement vertical or horizontal Refer to the label on the unit cabinet for the list of approved heaters Unit heaters are marked with Heater Model Numbers But heaters...

Page 16: ...he plug with the mating low voltage plug located on the heater ORN BRN HR1 Heater contactor first stage HR2 Heater contactor second stage 2 3 12 1 3 VIO ORN VIO BRN 2 Plug Assembly Elec Htr CTB CONTL...

Page 17: ...s internal timeclock This is necessary for broadcast of time of day functions occupied unoccupied NOTE PremierLink controller is shipped in Sensor mode To be used with a thermostat the PremierLink con...

Page 18: ...50TC D 18 C09376 Fig 26 PremierLink Wiring Schematic...

Page 19: ...with field installation of these accessory control devices Enthalpy control outdoor air or differential sensors Space CO2 sensor Outdoor air CO2 sensor Refer to Table 4 for accessory part numbers Fie...

Page 20: ...nication bus OAQ Outdoor Air Quality CO2 CMPSAFE Compressor Safety RH Relative Humidity FILTER Dirty Filter Switch SFS Supply Fan Status Table 6 Thermostat Mode TB1 TERMINAL FIELD CONNECTION INPUT SIG...

Page 21: ...n the return duct Connect this sensor to TB1 1 and TB1 3 per Fig 28 Configure the unit for Thermostat Mode Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration scr...

Page 22: ...for electrical requirements and terminal locations See Fig 34 for typical CO2 sensor wiring schematic To accurately monitor the quality of the air in the conditioned air space locate the sensor near a...

Page 23: ...B s THERMOSTAT R terminal Connect the other side of the NO contact set to TB1 10 Setpoint for Dirty Filter is set at the switch See Fig 38 R TB1 J4 4 PL Filter Switch NO close on rising pressure high...

Page 24: ...d for the entire network See Table 7 for recommended cable Table 7 Recommended Cables MANUFACTURER CABLE PART NO Alpha 2413 or 5463 American A22503 Belden 8772 Columbia 02525 NOTE Conductors and drain...

Page 25: ...de at on board DIP switches The RTU MP control is factory mounted in the 50TC D unit s main control box to the right of the CTB See Fig 44 Factory wiring is completed through harnesses connected to th...

Page 26: ...50TC D 26 C09377 Fig 45 RTU MP System Control Wiring Diagram...

Page 27: ...e of the default input on the specific channel according to schematic Parallel pins J5 1 J2 6 J5 3 J1 10 J5 5 J1 2 are used for field installation The RTU MP controller requires the use of a Carrier s...

Page 28: ...space sensor requires a separate isolated power supply of 24 VAC See Fig 48 for internal connections at the T 59 Connect the SEN terminal BLU to RTU MP J20 1 Connect the COM terminal BRN to J20 2 Conn...

Page 29: ...mA terminal to RTU MP J4 2 and connect the SIG COM terminal to RTU MP J4 3 See Fig 49 SEN COM J4 2 J4 3 IAQ Sensor 24 VAC C08462 Fig 49 RTU MP Indoor CO2 Sensor 33ZCSENCO2 Connections Outdoor Air Qua...

Page 30: ...vide different kinds of information for different applications In the BAS application many different protocols are used depending on manufacturer Protocols do not change the function of a controller j...

Page 31: ...inute auto logout if a screen is idle See Form 48 50H T 2T Appendix A for navigation and screen content Virtual BACview Virtual BACview is a freeware computer program that functions as the BACview6 Ha...

Page 32: ...45 6 60 48 253 CRHEATER274A00 CRHEATER283A00 50 1 34 7 72 1 80 66 253 CRHEATER275A00 CRHEATER284A00 75 2 52 1 84 7 100 95 253 STD 3 1 47 6 60 50 252 CRHEATER273A00 CRHEATER282A00 25 1 17 4 47 6 60 50...

Page 33: ...4 45 6 60 48 253 CRHEATER274A00 CRHEATER283A00 50 1 34 7 72 1 80 66 253 CRHEATER275A00 CRHEATER284A00 75 2 52 1 84 7 100 95 253 STD 3 1 48 6 60 51 261 CRHEATER273A00 CRHEATER282A00 25 1 17 4 48 6 60...

Page 34: ...4 52 6 60 55 281 CRHEATER274A00 CRHEATER283A00 50 1 34 7 76 9 80 71 281 CRHEATER275A00 CRHEATER284A00 75 2 52 1 89 5 100 100 281 STD 3 1 55 0 60 58 274 CRHEATER273A00 CRHEATER282A00 25 1 17 4 55 0 60...

Page 35: ...4 56 5 70 60 304 CRHEATER274A00 CRHEATER283A00 50 1 34 7 76 9 80 71 304 CRHEATER275A00 CRHEATER284A00 75 2 52 1 89 5 100 100 304 STD 3 1 58 9 70 62 297 CRHEATER273A00 CRHEATER282A00 25 1 17 4 58 9 70...

Page 36: ...zed outside air damper EconoMi er IV with control and integrated barometric relief EconoMi er2 without control for external signal and integrated barometric relief Power Exhaust Differential dry bulb...

Reviews: