APPENDIX III. FAN PERFORMANCE (CONT)
Table 21 – 50TC*D25
HORIZONTAL SUPPLY / RETURN
20 TON
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
546
1.57
617
2.10
680
2.67
738
3.29
790
3.93
6500
579
1.90
646
2.46
707
3.07
763
3.71
814
4.39
7000
613
2.28
677
2.87
735
3.51
789
4.19
839
4.89
7500
648
2.71
708
3.34
764
4.01
816
4.72
865
5.46
8000
683
3.20
740
3.86
794
4.57
846
5.30
892
6.08
8500
718
3.76
773
4.45
825
5.18
873
5.95
919
6.75
9000
754
4.37
814
5.10
856
5.87
903
6.67
947
7.50
9500
790
5.06
840
5.82
887
6.51
933
7.45
976
8.31
10000
826
5.82
874
6.50
920
7.44
965
8.30
‐
‐
CFM
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
839
4.60
885
5.29
928
6.01
969
6.75
1008
7.51
6500
862
5.09
907
5.82
950
6.57
990
7.34
1028
8.13
7000
886
5.63
930
6.39
972
7.17
1012
7.97
1050
8.70
7500
911
6.22
954
7.01
995
7.83
1035
8.66
‐
‐
8000
936
6.87
979
7.69
1019
8.54
‐
‐
‐
‐
8500
965
7.58
1004
8.44
‐
‐
‐
‐
‐
‐
9000
990
8.36
‐
‐
‐
‐
‐
‐
‐
‐
9500
‐
‐
‐
‐
‐
‐
‐
‐
‐
‐
10000
‐
‐
‐
‐
‐
‐
‐
‐
‐
‐
Standard Static Motor and Drive – 690 – 680 RPM, Max BHP 4.9
Medium Static Motor and Drive – 835 – 1021 RPM, Max BHP 6.5
High Static Motor and Drive – 941 – 1176 RPM, Max BHP 8.7
– Outside operating range
Boldface
- Field Supplied Drive
Underscore - Field Supplied Drive with High Static Motor
ITALIC Boldface
- Field Supplied Drive with Medium Static Motor
Table 22 – 50TC*D29
HORIZONTAL SUPPLY / RETURN
25 TON
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7500
553
1.92
621
2.46
683
3.07
741
3.72
795
4.42
8000
575
2.21
639
2.77
700
3.39
756
4.07
809
4.78
8500
596
2.52
658
3.10
716
3.73
771
4.43
823
5.16
9000
616
2.86
675
3.44
732
4.10
786
4.80
836
5.55
9500
636
3.22
693
3.82
747
4.48
800
5.20
849
5.97
10000
656
3.60
710
4.21
763
4.89
813
5.62
862
6.40
10500
675
4.02
727
4.64
778
5.32
827
6.07
874
6.86
11000
694
4.46
744
5.09
793
5.79
841
6.50
887
7.34
11500
713
4.93
761
5.57
808
6.27
854
7.03
899
7.84
CFM
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7500
845
5.14
892
5.90
936
6.68
978
7.48
1018
8.31
8000
859
5.53
905
6.31
949
7.11
991
7.94
‐
‐
8500
872
5.93
918
6.73
961
7.56
1003
8.41
‐
‐
9000
884
6.34
930
7.16
973
8.01
‐
‐
‐
‐
9500
896
6.77
941
7.61
984
8.48
‐
‐
‐
‐
10000
908
7.22
953
8.08
‐
‐
‐
‐
‐
‐
10500
920
7.69
963
8.56
‐
‐
‐
‐
‐
‐
11000
931
8.18
‐
‐
‐
‐
‐
‐
‐
‐
11500
943
8.70
‐
‐
‐
‐
‐
‐
‐
‐
Standard Static Motor and Drive – 647 – 791 RPM, Max BHP 4.9
Medium Static Motor and Drive – 755 – 923 RPM, Max BHP 6.5
High Static Motor and Drive – 827 – 1010 RPM, Max BHP 8.7
– Outside operating range
Boldface
- Field Supplied Drive
ITALIC Boldface
- Field Supplied Drive with Medium Static Motor
Summary of Contents for 50TC*17 Series
Page 39: ...39 C10818 Fig 44 RTU OPEN Control Module...
Page 69: ...69 APPENDIX IV WIRING DIAGRAMS C150370 Fig 58 50TC D30 Control Diagram 208 230 3 60...
Page 70: ...70 APPENDIX IV WIRING DIAGRAMS 5 C150368 Fig 59 50TC D30 Control Diagram 460 575 3 60...
Page 71: ...71 APPENDIX IV WIRING DIAGRAMS C150373 Fig 60 50TC D17 D30 Power Diagram 208 230 3 60...
Page 72: ...72 APPENDIX IV WIRING DIAGRAMS C12399 Fig 61 50TC D17 D30 Power Diagram 460 575 3 60...
Page 77: ...77 APPENDIX IV WIRING DIAGRAMS C12690 Fig 66 50TC PremierLinkt System Control Wiring Diagram...
Page 78: ...78 APPENDIX IV WIRING DIAGRAMS C12691 Fig 67 50TC RTU OPEN Wiring Diagram...
Page 79: ...79 APPENDIX IV WIRING DIAGRAMS C12689A Fig 68 50TC SAV VFD System Control Wiring Diagram...