59
APPENDIX II. PHYSICAL DATA (CONT)
Table 13 PHYSICAL DATA
−
HORIZONTAL (cont)
(COOLING)
15
−
25 TONS
RTPF (Round Tube/Plate Fin Coil Design)
50TC-D25
50TC-E25
50TC-D29
50TC-E29
Refrigeration System
# Circuits / # Comp. / Type
2 / 2 / Scroll
2 / 2 / Scroll
2 / 2 / Scroll
2 / 2 / Scroll
R-410a charge A/B (lbs)
23.8/23.1
30.0/30.7
24.9/27.7
35.1/35.4
Metering device
TXV
TXV
TXV
TXV
High-press. Trip / Reset (psig)
630 / 505
630 / 505
630 / 505
630 / 505
Low-press. Trip / Reset (psig)
54 / 117
27 / 44
54 / 117
27 / 44
Material
Cu / Al
Cu / Al
Cu / Al
Cu / Al
Tube Diameter
3/8" RTPF
3/8" RTPF
3/8" RTPF
3/8" RTPF
Rows / FPI
4 / 15
4 / 15
4 / 15
4 / 15
total face area (ft2)
26
26
26
26
Condensate drain conn. size
3/4"
3/4"
3/4"
3/4"
Humidimizer Coil
Material
n/a
Cu / Al
n/a
Cu / Al
Tube Diameter
n/a
3/8" RTPF
n/a
3/8" RTPF
Rows / FPI
n/a
1 / 17
n/a
1 / 17
total face area (ft2)
n/a
26
n/a
26
Evap. fan and motor
HORIZONTAL
Standard Static
Motor Qty / Belt Qty / Driver Type
1/1/ Belt
1/1/ Belt
1/1/ Belt
1/1/ Belt
Max BHP
4.9
4.9
4.9
4.9
RPM range
690-863
690-863
647-791
647-791
motor frame size
56
56
56
56
Fan Qty / Type
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
Fan Diameter (in)
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
Medium Static
- High Eff.
Motor Qty / Belt Qty / Driver Type
1/1/ Belt
1/1/ Belt
1/1/ Belt
1/1/ Belt
Max BHP
6.5/ 6.9/ 7.0/ 8.3
6.5/ 6.9/ 7.0/ 8.3
6.5/ 6.9/ 7.0/ 8.3
6.5/ 6.9/ 7.0/ 8.3
RPM range
835-1021
835-1021
755-923
755-923
motor frame size
184T
184T
184T
184T
Fan Qty / Type
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
Fan Diameter (in)
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
High Static-
High Eff.
Motor Qty / Belt Qty / Driver Type
1/1/ Belt
1/1/ Belt
1/1/ Belt
1/1/ Belt
Max BHP
10.5/11.9/11.9/11
10.5/11.9/11.9/11
10.5/11.9/11.9/11
10.5/11.9/11.9/11
RPM range
941-1176
941-1176
827-1010
827-1010
motor frame size
213T
213T
213T
213T
Fan Qty / Type
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
2 / Centrifugal
Fan Diameter (in)
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
18 x 15/15 X 11
Summary of Contents for 50TC*17 Series
Page 39: ...39 C10818 Fig 44 RTU OPEN Control Module...
Page 69: ...69 APPENDIX IV WIRING DIAGRAMS C150370 Fig 58 50TC D30 Control Diagram 208 230 3 60...
Page 70: ...70 APPENDIX IV WIRING DIAGRAMS 5 C150368 Fig 59 50TC D30 Control Diagram 460 575 3 60...
Page 71: ...71 APPENDIX IV WIRING DIAGRAMS C150373 Fig 60 50TC D17 D30 Power Diagram 208 230 3 60...
Page 72: ...72 APPENDIX IV WIRING DIAGRAMS C12399 Fig 61 50TC D17 D30 Power Diagram 460 575 3 60...
Page 77: ...77 APPENDIX IV WIRING DIAGRAMS C12690 Fig 66 50TC PremierLinkt System Control Wiring Diagram...
Page 78: ...78 APPENDIX IV WIRING DIAGRAMS C12691 Fig 67 50TC RTU OPEN Wiring Diagram...
Page 79: ...79 APPENDIX IV WIRING DIAGRAMS C12689A Fig 68 50TC SAV VFD System Control Wiring Diagram...