APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
LEGEND
SCREEN NAME
POINT NAME
PASSWORD
LEVEL
EDITABLE
RANGE
DEFAULT
NOTES
Unit
Maintenance
Operating Mode
No Password
re
q
uired
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Start Delay, Dehumidify
Displays unit operating mode
Fan Operating Mode
Auto/Continuous/Always On
Displays how the fan is configured
to operate
Occupancy Status
Unoccupied/Occupied
Displays the current occupancy status
Occupancy Control
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
Displays the origin of the
occupancy control
Outside Air
Temperature
F
Displays OAT (Viewable only if OAT
is a network broadcast)
SPT
F
Displays SPT
SPT Status
Normal/Above Limit/Below
Limit/Sensor Failure
Displays the SPT status
SPT Sensor Status
Inactive/Connected
Displays the connection status
of the Rnet sensor
Condensate Overflow
Normal/Alarm
Displays the status of the
condensate overflow
Cooling Set Point
F
Displays the actual set point
being used for cooling control
Heating Set Point
F
Displays the actual set point
being used for heating control
Set Point Adjustment
F
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Auxiliary Heat Control
Set Point
F
Displays the calculated set point being
used for auxiliary heating control
H
2
O Economizer
Control Set Point
F
Displays the calculated set point being
used for economizer control
Calculated IAQ/
Ventilation Damper
position
%
Displays the ventilation damper
position calculated by the DCV control
Active Compressor
Stages
0/1/2
Displays the actual number of
compressor stages operating
SAT
F
Displays SAT
Reset Filter Alarm
X
No/Yes
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Overflow Contact
Closed/Open
Displays the state of the condensate
overflow switch contact
Occupancy Contact
Closed/Open
Displays the state of the external/
remote occupancy input switch contact
BAS/Keypad Override
X
Inactive/Occupied/
Unoccupied
Inactive
Provides capability to force the
e
q
uipment to operate in an
occupied or unoccupied mode
OAT Input
N/A / Network
Displays if an OAT value is being
received from the Network
System Settings
BACnet
X
See TPI
Keypad Configuration
X
Mapping
Password
X
Changes password
Network
X
See TPI
BACnet Time Master
X
See TPI
Clock Set
X
Changes clock/time setting
Occupancy
Maintenance
Override Schedules
No Password
re
q
uired
Inactive/Active Occupied
Used to display the active and
inactive occupancy control inputs
Pushbutton Override
Inactive/Active Occupied
Keypad Override
Inactive/Active Occupied/Active
Unoccupied
Schedules
Inactive/Active Occupied
Occupancy Contact
Inactive/Active Occupied
BAS on/off
Inactive/Active Occupied
Schedule
Configuration
Local Occupancy
Schedules
User/Admin
Password level
access
X
Disable/Enable
Enable
Used to define which occupancy inputs
are used to determine
occupancy mode.
Local Holiday
Schedules
X
Disable/Enable
Disable
Local Override
Schedules
X
Disable/Enable
Disable
BACnet Occupancy
Schedules
X
Disable/Enable
Disable
°
°
°
°
°
°
°
°
BAS —
Building Automation System
DCV —
Demand Controlled Ventilation
IAQ
—
Indoor Air Quality
OAT
—
Outdoor Air Temperature
RH
—
Relative Humidity
SAT
—
Supply Air Temperature
SPT
—
Space Temperature
TPI
—
Third Party Integration