APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
LEGEND
SCREEN NAME
POINT NAME
PASSWORD
LEVEL
EDITABLE
RANGE
DEFAULT
NOTES
Equipment
Status
Operating Mode
No Password
Re
q
uired
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
Displays unit operating mode
SPT
F
Displays SPT
SAT
F
Displays SAT
Condenser Leaving
Temperature
F
Displays leaving condenser
water temperature
Condenser Entering
Temperature
F
Displays entering condenser
water temperature (Value
will not update when compressor
is operating)
Fan
Off/Low Speed/
Medium Speed
High Speed/On
Displays fan speed status
Compressor Capacity
0 - 100%
Displays compressor capacity
Damper Position
0 - 100%
Displays current damper position
(Viewable only if Ventilation DMP
Type = 2 position or DCV)
H
2
O Economizer
0 - 100%
Displays position of economizer valve
Auxiliary Heat
0 - 100%
Displays position of auxiliary
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
1 stage Elect or Modulating)
Space RH
0 - 100%
Displays space RH% (Viewable only if
Humidity Sensor = Installed)
Dehumidification
Inactive/Active
Displays if dehumidification is active
(Viewable only if Factory
Dehumidification Reheat = Installed)
IAQ CO
2
0 - 9999 ppm
Displays the space CO
2
level
Alarm Status
SPT Alarm Status
No Password
Re
q
uired
Normal/Alarm
Displays current space
temperature condition
Alarming SPT
F
Displays the SPT that
exceeded the alarm limit (when SPT
alarm above is in Alarm)
SPT Alarm Limit
F
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
SPT Sensor Alarm
Status
Normal/Alarm
Displays the status of the Rnet
SPT sensor - ALARM is displayed
should the sensor fail to communicate
with the control module
IAQ Alarm Status
Normal/Alarm
Current IAQ/ventilation condition
Compressor Alarm
Status
Normal/Alarm
Current compressor condition
SAT Alarm Status
Normal/Alarm
Current SAT condition
Condensate Overflow
Alarm Status
Normal/Alarm
Current status of the condensate
drain (overflow switch)
Condenser Water Tem-
perature Alarm Status
Normal/Alarm
Current status of the
condenser water
Filter Alarm Status
Normal/Alarm
Current filter condition
Space RH Alarm Status
Normal/Alarm
Current space RH condition
OAT Alarm Status
Normal/Alarm
Current status of the OAT
broadcast function
Airside Linkage Status
Normal/Alarm
Current linkage status if enabled
Condenser Water
Linkage
Normal/Alarm
Current linkage status if enabled
Sensor
Calibration
SAT
Admin Password
level access only
F
Display SAT
SAT Offset
X
-9.9 - 10.0 F
0 F
Used to correct sensor reading
Leaving Condenser
Water Temperature
F
Displays Leaving Condenser
Water Temperature
Leaving CW Offset
X
-9.9 - 10.0 F
0 F
Used to correct sensor reading
Rnet Sensor
Temperature
F
Displays SPT
Rnet Offset
X
-9.9 - 10.0 F
0 F
Used to correct sensor reading
RH
%
Displays Space RH value
RH Sensor Offset
X
-15% - 15%
0 %
Used to correct sensor reading
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
BAS —
Building Automation System
DCV —
Demand Controlled Ventilation
IAQ
—
Indoor Air Quality
OAT
—
Outdoor Air Temperature
RH
—
Relative Humidity
SAT
—
Supply Air Temperature
SPT
—
Space Temperature
TPI
—
Third Party Integration