Electrical data (cont)
50HX ELECTRIC HEATER PACKAGES — 208/240 V, SINGLE-PHASE,
SINGLE-POINT WIRING CONNECTIONS
UNIT
SIZE
50HX
ELECTRIC HEAT
ACCESSORY KIT
CPHEATER---A00
ELECTRIC HEAT
(kW)*
HEATER
FLA
MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
MAX FUSE
OR HACR
BRKR
MOCP
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
024
001
3.75
5.0
18.1
20.8
42.1
45.6
50
50
—
—
002
5.60
7.5
27.1
31.3
53.4
58.6
60
60
—
—
015
7.50
10.0
36.1
41.7
64.7
71.6
—
—
70
80
030
001
3.75
5.0
18.1
20.8
45.3
48.8
50
50
—
—
014
5.60
7.5
27.1
31.3
56.6
61.8
60
—
—
70
015
7.50
10.0
36.1
41.7
67.9
74.8
—
—
70
80
016
11.30
15.0
54.1
62.0
90.4
100.3
—
—
100
110
036
001
3.75
5.0
18.1
20.8
48.3
51.7
60
60
—
—
014
5.60
7.5
27.1
31.3
59.5
64.8
60
—
—
70
015
7.50
10.0
36.1
41.7
70.8
77.8
—
—
80
80
016
11.30
15.0
54.3
62.0
93.3
103.2
—
—
100
110
017
15.00
20.0
72.2
83.3
116.0
129.9
—
—
125
150
042
001
3.75
5.0
18.1
20.8
52.1
55.5
60
60
—
—
014
5.60
7.5
27.1
31.3
63.3
68.6
—
—
70
80
015
7.50
10.0
36.1
41.7
74.6
81.6
—
—
80
90
016
11.30
15.0
54.1
62.0
97.1
107.0
—
—
100
110
017
15.00
20.0
72.2
83.3
119.8
133.7
—
—
125
150
048
013
3.75
5.0
18.1
20.8
64.2
67.6
—
—
80
80
014
5.60
7.5
27.1
31.3
75.4
80.7
—
—
90
90
015
7.50
10.0
36.1
41.7
86.7
93.7
—
—
100
100
016
11.30
15.0
54.1
62.0
109.2
119.1
—
—
110
125
017
15.00
20.0
72.2
83.3
131.9
145.8
—
—
150
150
060
013
3.75
5.0
18.1
20.8
72.0
75.5
—
—
90
100
014
5.60
7.5
27.1
31.3
83.3
88.5
—
—
100
100
015
7.50
10.0
36.1
41.7
94.6
101.5
—
—
100
110
016
11.30
15.0
54.1
62.0
117.1
126.9
—
—
125
150
017
15.00
20.0
72.2
83.3
139.6
153.5
—
—
150
175
LEGEND
FLA
— Full Load Amps
HACR BRKR — Heating, Air Conditioning and Refrigeration Circuit
Breaker
MOCP
— Maximum Overcurrent Protection (fuses or HACR-
type circuit breaker)
NEC
— National Electrical Code
*Electric heat capacity (kW) is based on heater voltages of 208 v or
240 v. If power distribution voltage to units varies from rated heater
voltage, see Wattage Multiplication Factors table on page 19.
NOTE: In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
22