Carrier 50HX024 Product Data Download Page 17

DRY COIL AIR DELIVERY* — HORIZONTAL AND VERTICAL DISCHARGE

(DEDUCT 10% FOR 208 V) — UNITS 024-042

UNIT

SIZE

50HX

MOTOR

SPEED

230 AND 460 V HORIZONTAL DISCHARGE

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

280

275

265

255

250

245

240

Cfm

820

810

755

700

660

600

560

Med

Watts

365

360

350

345

340

330

320

310

300

Cfm

1025

1010

975

940

900

850

800

720

630

High

Watts

490

480

470

460

445

430

410

390

380

Cfm

1300

1255

1200

1150

1080

1005

915

790

620

030

Low

Watts

Cfm

Med

Watts

365

360

360

350

350

Cfm

1060

1020

980

935

880

High

Watts

490

485

475

460

450

430

Cfm

1270

1220

1170

1100

1020

920

036

Low

Watts

410

400

390

380

370

360

Cfm

1275

1240

1195

1150

1095

1040

Med

Watts

550

535

520

505

485

470

455

435

415

Cfm

1575

1520

1470

1410

1345

1280

1210

1125

1025

High

Watts

680

655

625

595

570

530

495

Cfm

1720

1625

1530

1430

1320

1190

995

042

Low

Watts

490

480

470

460

450

430

410

390

Cfm

1400

1380

1340

1300

1250

1200

1140

1070

Med

Watts

590

580

560

545

525

505

480

450

420

Cfm

1600

1560

1540

1470

1430

1360

1300

1220

1120

High

Watts

700

670

640

600

560

500

Cfm

1780

1670

1600

1480

1340

1100

*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter or electric heater. Deduct

wet coil, filter, and electric heater pressure drops to obtain external static pressure available for ducting.

NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling ca-

pacity. Indoor coil frosting may occur at airflows below this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

DRY-COIL AIR DELIVERY* — HORIZONTAL AND

VERTICAL DISCHARGE FOR INTEGRATED

CONTROL MOTOR UNITS AT 230 V

— UNITS 048 AND 060

(Deduct 10% from Cfm for 208-V operation)

UNIT

SIZE

50HX

FAN ONLY

(Cfm)

COOLING

(Cfm)

HEATING

(Cfm)

048

1530

1575

1575

060

1750

1800

2000

*Air delivery values are for dry coil at 230 v. Airflow is independent of

external static pressure within

6

5% of table values up to 0.8 in. wg.

Air delivery is preset at factory.

NOTE: Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Indoor coil icing
may occur at airflows below this point. Water blow-off may occur at air-
flows above 450 cfm per 12,000 Btuh of rated cooling capacity.

WET COIL PRESSURE DROP

UNIT

SIZE

50HX

AIRFLOW

(cfm)

PRESSURE DROP

(in. wg)

024

600

0.012

700

0.022

800

0.027

900

0.039

030

900

0.039

1000

0.057

1200

0.072

036

1000

0.051

1200

0.061

1400

0.068

1600

0.075

042

1000

0.030

1200

0.048

1400

0.057

1600

0.078

048

1400

0.068

1600

0.075

1800

0.088

060

1700

0.082

1900

0.095

2100

0.108

2300

0.123

17

Summary of Contents for 50HX024

Page 1: ...ed for minimum instal lation expense 50HX units are available in a vari ety of standard sizes with voltage options to meet residential and light commercial requirements Unit is installed easily on a rooftop or a ground level pad The optional base rail unit provides an elevated base Convertible duct configuration on the 50HX is designed for easy use in either downflow or horizontal dis charge appli...

Page 2: ... time temperature based defrost cycles to maintain unit efficiency This highly reliable system checks for coil icing conditions at preset time intervals and initiates a defrost cycle only if required The defrost cycle ends as soon as defrosting is accomplished The Chronotemp defrost board may be configured for 30 50 or 90 minutes Indoor air quality is improved with cleanable foil faced insulation ...

Page 3: ...ed parts Easily accessible refrigerant access ports on all discharge suc tion and liquid lines permit easy and accurate measurements Model number nomenclature ARI capacities COOLING AND HEATING CAPACITIES AND EFFICIENCIES UNIT 50HX NOMINAL TONS STANDARD CFM NET COOLING CAPACITIES AT 95 F Btuh SEER NET HEATING CAPACITIES At 47 F Btuh COP At 47 F Btuh NET HEATING CAPACITIES At 17 F Btuh COP At 17 F ...

Page 4: ...entrifugal Direct Drive Speeds 3 3 3 3 Variable Variable Rpm High Speed 1075 1075 1100 1100 Diameter 10 10 10 10 10 10 Width in 9 9 9 9 10 10 Nominal Airflow Cfm 800 1000 1300 1400 1600 1800 Motor Hp 1 4 1 4 1 2 1 2 1 0 1 0 INDOOR COIL Rows Fins in 3 15 3 15 4 15 4 15 4 15 4 15 Face Area sq ft 3 6 3 6 4 5 4 5 4 5 4 5 OUTDOOR FAN Propeller Direct Drive Cfm 2200 2200 2200 2400 2400 2400 Rpm 1100 110...

Page 5: ...2 stage cooling control with remote commu nication ability Low ambient kit Motormastert II device allows the use of mechanical cooling down to outdoor ambient tem peratures as low as 0 F Electric heaters provide heat in the unit when required Each package has a heater module that slides into keyed mounting slots in the fan inlet Heater sizes range from 5 0 to 20 0 kW An available single point powe...

Page 6: ... Ungrounded Surfaces Control Box Side 36 914 4 Unit and Block or Concrete Walls and Other Grounded Surfaces Control Box Side 42 1066 8 REQ D CLEARANCES FOR SERVICING in mm Indoor Coil Access Side 30 762 0 Control Box Access Side 30 762 0 Except for NEC Requirements Unit Top 36 914 4 Side Opposite Ducts 30 762 0 REQ D CLEARANCES TO COMBUSTIBLE MAT L in mm Unit Top 0 Duct Side of Unit 0 Side Opposit...

Page 7: ...grounded Surfaces Control Box Side 36 914 4 Unit and Block or Concrete Walls and Other Grounded Surfaces Control Box Side 42 1066 8 REQ D CLEARANCES FOR SERVICING in mm Indoor Coil Access Side 30 762 0 Control Box Access Side 30 762 0 Except for NEC Requirements Unit Top 36 914 4 Side Opposite Ducts 30 762 0 REQ D CLEARANCES TO COMBUSTIBLE MAT L in mm Unit Top 0 Duct Side of Unit 0 Side Opposite D...

Page 8: ... CLEARANCES FOR SERVICING in mm Indoor Coil Access Side 30 762 0 Control Box Access Side 30 762 0 Except for NEC Requirements Unit Top 36 914 4 Side Opposite Ducts 30 762 0 REQ D CLEARANCES TO COMBUSTIBLE MAT L in mm Unit Top 0 Duct Side of Unit 0 Side Opposite Ducts 0 Bottom of Unit 0 Vertical Discharge First 12 in 304 8 mm of Supply Duct 1 25 4 LEGEND K O Knock Out MAT L Material NEC National El...

Page 9: ...7 REQ D CLEARANCES FOR SERVICING in mm Indoor Coil Access Side 30 762 0 Control Box Access Side 30 762 0 Except for NEC Requirements Unit Top 36 914 4 Side Opposite Ducts 30 762 0 REQ D CLEARANCES TO COMBUSTIBLE MAT Ll in mm Unit Top 0 Duct Side of Unit 0 Side Opposite Ducts 0 Bottom of Unit 0 Vertical Discharge First 12 inches 304 8 mm of Supply Duct 1 25 4 LEGEND K O Knock Out MAT L Material NEC...

Page 10: ...et up for unit being installed 2 Seal strip must be applied as required for unit being installed 3 Dimensions in are in millimeters 4 Roof curb is made of 16 gage steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Insulated panels 1 in thick fiberglass 1 lb density 10 ...

Page 11: ...ity value since deductions for outdoor coil frost and defrosting have already been made No correction is required The required heating capacity is 28 550 Btuh There fore 13 250 Btuh 28 550 15 300 additional elec tric heat is required Determine additional electric heat capacity in kW 13 250 Btuh 3 9 kW of heat required 3414 Btuh kW Enter the 50HX Electric Heater Packages 208 240 V Single Phase Sing...

Page 12: ...4 3 47 3 44 3 38 3 41 50HX036 3 TONS Temp F Outdoor Ent Air Indoor Air Cfm BF 1050 0 02 1150 0 02 1200 0 03 1350 0 03 Indoor Air Ewb F 72 67 63 62 72 67 63 62 72 67 63 62 72 67 63 62 85 TC 40 4 36 4 33 7 32 4 40 8 36 8 34 1 32 7 41 1 37 0 34 2 32 9 41 4 37 3 34 6 33 4 SHC 19 0 24 7 24 0 29 8 19 9 25 8 25 1 31 3 20 3 26 4 25 6 31 9 21 5 27 9 27 1 33 3 kW 3 23 3 18 3 15 3 14 3 27 3 22 3 19 3 18 3 30...

Page 13: ...1 48 0 42 8 39 3 40 3 SHC 24 7 31 7 30 4 37 6 26 0 34 0 32 6 39 1 27 3 36 2 34 6 40 3 kW 5 77 5 67 5 60 5 59 5 84 5 74 5 67 5 68 5 90 5 80 5 74 5 77 50HX060 5 TONS Temp F Outdoor Ent Air Indoor Air Cfm BF 1800 0 03 2000 0 04 2250 0 04 Indoor Air Ewb F 72 67 63 62 72 67 63 62 72 67 63 62 85 TC 66 8 60 0 55 7 54 1 67 5 60 7 56 3 55 4 68 2 61 2 56 8 57 1 SHC 34 3 44 2 42 6 53 3 35 8 46 7 45 0 55 4 37...

Page 14: ...Outdoor Coil F db at 70 rh 10 0 10 17 20 30 40 47 50 60 70 875 60 Cap 7 8 6 8 12 3 10 1 14 5 13 1 17 1 15 6 18 2 16 4 21 8 19 1 25 7 24 6 28 4 28 4 29 3 29 3 32 1 32 1 35 0 35 0 kW 2 10 2 13 2 15 2 19 2 20 2 25 2 31 2 36 2 37 2 42 2 47 70 Cap 6 8 5 9 10 1 9 0 13 3 12 1 16 0 14 6 17 1 15 5 21 0 18 4 25 0 24 0 27 9 27 9 28 7 28 7 31 6 31 6 34 5 34 5 kW 2 25 2 32 2 37 2 40 2 42 2 48 2 57 2 63 2 65 2 ...

Page 15: ... 3 15 80 Cap 8 9 8 3 12 0 11 2 15 4 14 6 17 9 16 4 19 4 17 6 23 4 20 6 28 3 28 3 32 8 32 8 35 2 35 2 40 2 40 2 44 7 44 7 kW 2 63 2 73 2 83 2 89 2 92 3 02 3 17 3 27 3 30 3 39 3 46 50HX042 31 2 TONS Cfm Std Air Return Air F db Temperature Air Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 30 40 47 50 60 70 1250 60 Cap 9 9 9 2 14 1 13 0 18 4 16 8 21 4 19 5 23 1 20 8 28 7 25 2 35 6 34 1 40 4 40 4 4...

Page 16: ...door Coil F db at 70 rh 10 0 10 17 20 30 40 47 50 60 70 1800 60 Cap 15 9 14 8 22 0 20 2 28 0 25 6 32 2 29 4 34 5 31 1 41 9 36 7 51 3 49 1 57 8 57 8 61 2 61 2 72 4 72 4 83 6 83 6 kW 4 20 4 22 4 24 4 26 4 27 4 29 4 36 4 40 4 43 4 53 4 64 70 Cap 13 9 12 9 20 4 18 8 27 0 24 6 31 5 28 7 33 7 30 4 41 1 36 0 50 2 48 1 56 6 56 6 59 8 59 8 70 8 70 8 81 7 81 7 kW 4 39 4 49 4 60 4 67 4 68 4 72 4 79 4 83 4 87...

Page 17: ...er Deduct wet coil filter and electric heater pressure drops to obtain external static pressure available for ducting NOTES 1 Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12 000 Btuh of rated cooling ca pacity Indoor coil frosting may occur at airflows below this point 2 Dashes indicate portions of table that are beyond the blower motor capacity or are not recomm...

Page 18: ... to contactor C starting the compressor COMP and outdoor fan motor OFM Circuit R G is made at the same time starting the indoor fan motor IFM after a 1 second delay When the thermostat is satisfied contacts open deener gizing C The COMP and OFM stop and the IFM stops after a short time delay Heating On a call for heat thermostat makes circuits R Y and R G When compressor time delay 5 2 minutes is ...

Page 19: ...ent refer to NEC Articles 430 and 440 the over current protective device for the unit shall be fuse or HACR breaker The UL Canada units may be fuse or circuit breaker 2 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2 Use the following formula to determine the percent of voltage imbalance Voltage Imbalance max voltage deviation fro...

Page 20: ...11 30 15 0 54 1 62 0 67 9 78 1 70 80 017 15 00 20 0 72 1 83 3 90 1 104 2 100 110 048 013 3 75 5 0 18 1 20 8 22 5 26 0 25 30 014 5 60 7 5 27 1 31 3 33 7 39 1 35 40 015 7 50 10 0 36 1 41 7 45 1 50 8 50 60 016 11 30 15 0 54 1 62 0 67 9 78 1 70 80 017 15 00 20 0 72 1 83 3 90 1 104 2 100 110 060 013 3 75 5 0 18 1 20 8 22 5 26 0 25 30 014 5 60 7 5 27 1 31 3 33 7 39 1 35 40 015 7 50 10 0 36 1 41 7 45 1 5...

Page 21: ...varies from rated heater voltage see Wattage Multiplication Factors table on page 19 NOTE In compliance with NEC requirements for multimotor and com bination load equipment refer to NEC Articles 430 and 440 the over current protective device for the unit shall be fuse or HACR breaker 50HX ELECTRIC HEATER PACKAGES 480 V 3 PHASE DUAL POINT WIRING CONNECTIONS UNIT SIZE 50HX ELECTRIC HEAT ACCESSORY KI...

Page 22: ...81 6 80 90 016 11 30 15 0 54 1 62 0 97 1 107 0 100 110 017 15 00 20 0 72 2 83 3 119 8 133 7 125 150 048 013 3 75 5 0 18 1 20 8 64 2 67 6 80 80 014 5 60 7 5 27 1 31 3 75 4 80 7 90 90 015 7 50 10 0 36 1 41 7 86 7 93 7 100 100 016 11 30 15 0 54 1 62 0 109 2 119 1 110 125 017 15 00 20 0 72 2 83 3 131 9 145 8 150 150 060 013 3 75 5 0 18 1 20 8 72 0 75 5 90 100 014 5 60 7 5 27 1 31 3 83 3 88 5 100 100 0...

Page 23: ...o units varies from rated heater voltage see Wattage Multiplication Factors table on page 19 NOTE In compliance with NEC requirements for multimotor and com bination load equipment refer to NEC Articles 430 and 440 the over current protective device for the unit shall be fuse or HACR breaker 50HX ELECTRIC HEATER PACKAGES 480 V 3 PHASE SINGLE POINT WIRING CONNECTIONS UNIT SIZE 50HX ELECTRIC HEAT AC...

Page 24: ...rrent Protection NEC National Electrical Code OFM Outdoor Fan Motor QT Quadruple Terminal Block RVS Reversing Valve Solenoid TB Terminal Block TDR Time Delay Relay TRAN Transformer Field Splice Marked Wire Terminal Marked Terminal Unmarked Terminal Block Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only not to...

Page 25: ...and wiring SLAB MOUNT LEGEND Power Wiring Control Wiring Outdoor Airflow Indoor Airflow Separate disconnect per National Electrical Code NEC is required for elec tric heater when single point connection is not used 25 ...

Page 26: ...Typical piping and wiring cont CURB MOUNT 26 ...

Page 27: ...r side with aluminum foil faced fiberglass insulation 3 Cabinet panels shall be easily removable for servicing 4 Unit shall have a factory installed sloped non corrosive condensate drain 5 Unit insulation conforms to ASHRAE 62P 6 Unit shall have a single piece top cover C Fans 1 Indoor Blower Indoor Fan a Fan shall be 3 speed sizes 024 042 or vari able speed sizes 048 and 060 direct drive as shown...

Page 28: ...Outdoor Thermostat Kit Thermostat allows for staging of electric heaters based on outdoor air temperature 3 Electronic Programmable Thermostat Thermostat provides 2 stage heating and 2 stage cooling control with remote communication ability 4 Controls Upgrade Package High and low pressure switches protect the com pressor against improper refrigerant pressures 5 Low Ambient Kit Permits cooling oper...

Reviews: