Dimensions
SIZES 018-036 WITHOUT BASE RAIL
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT
CORNER WT (Lb/Kg)
UNIT HEIGHT (in./mm)
DIMENSION (in./mm)
Lb
Kg
A
B
C
D
E
F
50HS018
208/230-1-60
233
106
66/30
45/20
95/43
42/19
24.1/613
18.2/462
50HS024
208/230-1-60
256
117
68/31
46/21
97/44
45/20
24.1/613
18.2/462
50HS030
208/230-1-60, 208/230-3-60
268
122
66/30
58/26
91/41
53/24
24.1/613
18.2/462
50HS036
208/230-1-60, 208/230-3-60, 460-3-60
288
131
71/32
63/29
96/44
58/26
28.1/714
22.2/563
UNIT
CENTER OF GRAVITY (in./mm)
X
Y
Z
50HS018
20.7/525
19.2/487
10.6/270
50HS024
20.4/517
19.3/491
10.6/270
50HS030
20.3/515
20.1/510
10.6/270
50HS036
20.1/511
20.2/513
12.4/314
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side . . . . . . . . . . . . . . . . . . . 30 (762)
Control Box Access Side . . . . . . . . . . . . . . . . . . 30 (762)
(Except for NEC requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side Opposite Ducts
. . . . . . . . . . . . . . . . . . . . 30 (762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge, First 12 in. (305) of Supply Duct
. . . . . 1 (25)
NEC REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side
. . . . . . . . . . . . . 42 (1067)
Unit and Ungrounded Surfaces, Control Box Side . . . . . .36 (914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . . . 42 (1067)
LEGEND
CG
— Center of Gravity
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in (
) are in mm.
5