Table 13 — Evaporator-Fan Motor Data — High-Static Motors
LEGEND
BHP —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of
the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 14 — Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)
LEGEND
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air
cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and
watts.
Table 15 — Accessory Electric Heaters
Static Pressure Drop (in. wg) — 50HJ008-014
GENERAL FAN PERFORMANCE NOTES
NOTES:
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
the fan motors up to the ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance refer to
Evaporator-Fan Motor Data, Tables 12 and 13.
2. Values include losses for filters, unit casing, and wet coils. See
Tables 14 and 15 and Fig. 43 for accessory/FIOP static pressure
information.
3. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
4. Interpolation is permissible. Do not extrapolate.
UNIT
50HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
008,009
Three
4.20
3775
208/230
12.2
460
5.5
575
5.5
012
Three
5.25
4400
208/230
17.3
460
8.5
575
8.5
COMPONENT
CFM
2250 2500
2750
3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250
Vertical EconoMi$er IV and EconoMi$er 2
0.06 0.075
0.09
0.115 0.13
0.15
0.17 0.195 0.22
0.25 0.285 0.325 0.36
—
Horizontal EconoMi$er IV and EconoMi$er 2
—
0.1
0.125
0.15
0.18
0.21
0.25 0.275
0.3
0.34 0.388
—
—
—
FIOP —
Factory-Installed Option
COMPONENT
CFM
2200 2500 3000
3500
4000 4500 5000 5500
6000
1 Heater Module
0.02
0.03
0.05 0.065
0.08
0.10
0.12
0.14 0.155
2 Heater Modules
0.03
0.05
0.07 0.09
0.12
0.14
0.16
0.19 0.21