27
Table 10 — Fan Rpm at Motor Pulley Setting*; Standard Motor/Drive
*Approximate fan rpm shown.
Table 11 — Fan Rpm at Motor Pulley Setting*; High-Static Motor/Drive
*Approximate fan rpm shown.
Table 12 — Evaporator-Fan Motor Data — Standard Motor
LEGEND
BHP —
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of
the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
50HJ
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
008,009
1085
1060
1035
1010
985
960
935
910
890
865
840
—
—
012
1080
1060
1035
1015
990
970
950
925
905
880
860
—
—
014
1130
1112
1087
1062
1037
1012
987
962
987
912
887
862
830
UNIT
50HJ
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
008
1080
1025
1007
988
970
952
933
915
897
878
860
—
—
009
1080
1025
1007
988
970
952
933
915
897
878
860
—
—
012
1130
1112
1087
1062
1037
1012
987
962
937
912
887
862
830
UNIT
50HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
008,009
Three
2.90
2615
208/230
8.6
460
3.9
575
3.9
012
Three
3.70
3775
208/230
12.2
460
5.5
575
5.5
014
Three
5.25
4400
208/230
17.3
460
8.5
575
8.5