background image

UNITS WITH MOISTUREMISER DEHUMIDIFICATION
PACKAGE — When thermostat calls for cooling, terminals
G and Y1 and/or Y2 and the compressor contactor(s) C1
(and C2) are energized. The indoor (evaporator) fan motor
(IFM), compressor(s), and outdoor (condenser) fan motors
(OFM) start. The OFMs runs continuously while the unit is
in cooling. As shipped from the factory, MoistureMiser de-
humidification circuit is always energized. If MoistureMiser
circuit modulation is desired, a field-installed, wall-mounted
humidistat is required.

If the MoistureMiser humidistat is installed and calls for

the MoistureMiser subcooler coil to operate, the humidistat
internal switch closes. This energizes and closes the liquid
line solenoid(s) valve coils (LLSV) of the MoistureMiser cir-
cuit, forcing the hot liquid refrigerant of the liquid line to
enter the subcooler coil (see Fig. 33). As the hot liquid passes
through the subcooler coil, it is exposed to the cold supply
airflow coming off from the evaporator coil and the liquid is
further cooled to a temperature approaching the evaporator
coil leaving-air temperature. The state of the refrigerant leav-
ing the subcooler coil is a highly subcooled liquid refriger-
ant. The liquid then enters a thermostatic expansion valve
(TXV) where the liquid is dropped to a lower pressure. The
TXV does not have a pressure drop great enough to change
the liquid to a 2-phase fluid. The TXV can throttle the pres-
sure drop of the liquid refrigerant and maintain proper con-
ditions at the compressor suction valve over a wide range of
operating conditions. The liquid then enters a second fixed
restrictor expansion device for a second pressure drop to a
2-phase fluid. The liquid proceeds to the evaporator coil at
a temperature lower than normal cooling operation. This lower
temperature is what increases the latent capacity of the roof-
top. The 2-phase refrigerant passes through the evaporator
and is changed into a vapor. The air passing over the evapo-
rator coil will become colder than during normal operation
as a result of the colder refrigerant temperatures. However,
as it passes over the subcooler coil, the air will be warmed
slightly.

As the refrigerant leaves the evaporator, the refrigerant passes

a low-pressure switch in the suction line. This low-pressure
switch will deactivate the MoistureMiser package when
the suction pressure reaches 60 psig. The low-pressure
switch is an added safety device to protect against evapo-
rator coil freeze-up. The low-pressure switch will only de-
activate and open the liquid line solenoid valve in the
MoistureMiser circuit. The compressors will continue to run
as long as there is a call for cooling, regardless of the po-
sition of the low-pressure switch. The solenoid valve and
the MoistureMiser package will be reactivated only when
the call for cooling has been satisfied, the low-pressure switch
has closed, and a new call for cooling exists. The crankcase
heaters on the scroll compressors provide additional protec-
tion for the compressors due to the additional refrigerant charge
in the subcooler.

When the humidistat is satisfied, the humidistat internal

switch opens, cutting power to and opening the LLSV. The
refrigerant is routed back through the evaporator and the sub-
cooler coil is removed from the refrigerant loop.

When the thermostat is satisfied, C1 (and C2) is de-

energized and the compressor(s) and OFMs shut off. After a
30-second delay, the IFM shuts off. If the thermostat fan se-
lector switch is in the ON position, the IFM will run
continuously.

SERVICE

When servicing unit, shut off all electrical power to unit
to avoid shock hazard or injury from rotating parts.

Cleaning —

Inspect unit interior at the beginning of

each heating and cooling season or as operating conditions
require.
EVAPORATOR COIL
1. Turn unit power off. Remove evaporator coil access panel.
2. If economizer or accessory two-position damper is in-

stalled, remove economizer or two-position damper by
disconnecting economizer plug and removing mounting
screws (see Fig. 16, 17, or 24). Refer to Accessory Econo-
mizer or Two-Position Damper Installation Instructions
for more details.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher

detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results, back-
flush toward return-air section to remove foreign
material.

5. Flush condensate pan after completion.
6. Reinstall economizer or two-position damper and filters.
7. Reconnect wiring.
8. Replace access panels.
CONDENSER COILS — Inspect coils monthly. Clean con-
denser coils annually, and as required by location and outdoor-
air conditions.

Clean 2-row coils as follows:

1. Turn off unit power.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 34. To hold

top panel open, place coil corner post between top panel
and center post. See Fig. 35.

4. Remove device holding coil sections together at return

end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 36.

5. Use a water hose or other suitable equipment to flush down

between the 2 coil sections to remove dirt and debris. Clean
the outer surfaces with a stiff brush in the normal manner.

6. Secure the sections together. Reposition the coil sections,

and remove the coil corner post from between the top
panel and center post. Install the coil corner post and coil
center post, and replace all screws.

CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and
cooling season, or more often if operating conditions require
it. Replacement filters must be same dimensions as original
filters.
OUTDOOR-AIR INLET SCREEN — Clean screen with steam
or hot water and a mild detergent. Do not use throwaway
filters in place of screens.

28

Summary of Contents for 50HJ008-014

Page 1: ...curb in accordance with instructions shipped with curb See Fig 1 Install insulation cant strips roofing felt and counter flash ing as shown Ductwork must be attached to curb If electric or control pow...

Page 2: ...ttom UNIT SIZE 50HJ A ROOF CURB ACCESSORY 008 014 18 29 356 CRRFCURB003A00 28 09 610 CRRFCURB004A00 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millime...

Page 3: ...of run Do not use a pipe size smaller than the unit connection Step 4 Rig and Place Unit Inspect unit for trans portation damage File any claim with transportation agency Keep unit upright and do not...

Page 4: ...ng to prevent rigging straps from damaging unit 3 Unit weights do not include economizer See Table 1 for econo mizer weights All panels must be in place when rigging 50HJ MAX WEIGHT A B C lb kg in mm...

Page 5: ...20 Motor Frame 56 56 56 56 Fan Rpm Range Std 840 1085 840 1085 860 1080 900 1260 Alt 860 1080 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter A...

Page 6: ...ow 4 Ductwork to be attached to accessory roof curb only 5 Minimum clearance local codes or jurisdiction may prevail a Bottom to combustible surfaces when not using curb 0 in on horizontal discharge u...

Page 7: ...ing units provide a disconnect per the NEC All field wiring must comply with the NEC and local re quirements In Canada electrical connections must be made in accordance with CSA Canadian Standards Ass...

Page 8: ...0 21 7 25 0 33 3 38 5 66 6 77 0 88 4 102 0 104 4 120 3 55 9 55 9 55 9 55 9 55 9 61 4 96 6 109 5 123 7 140 8 143 5 133 5 60 60 60 60 70 70 100 110 125 150 150 150 59 59 59 59 59 59 89 101 114 129 132...

Page 9: ...0 21 7 25 0 33 3 38 5 66 6 77 0 88 4 102 0 104 4 120 3 61 9 61 9 61 9 61 9 61 9 66 4 101 5 114 5 128 7 145 8 148 5 138 5 70 70 70 70 70 70 110 125 150 150 150 150 64 64 64 64 64 64 94 106 119 135 138...

Page 10: ...n Table 3 FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor Evaporator Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection NEC Nati...

Page 11: ...with the air hood package If unit is to be used for vertical dis charge application discard this plate Assembly 1 Determine if ventilation air is required in building If so determine the minimum amoun...

Page 12: ...lenoid Valve S LPS Low Pressure Switch Subcooler only TRAN Transformer Factory Wiring Accessory or Optional Wiring Fig 11 Typical MoistureMiser Dehumidification Package Humidistat Wiring 208 230 V Uni...

Page 13: ...s 9 Remove tape from outdoor air thermostat OAT Fas ten OAT to inside of hood using screws and speed clips provided See Fig 21 Make sure OAT terminals are po sitioned up 10 Replace outdoor air opening...

Page 14: ...Put aside screen retainer and retainer screw for later as sembly Do not attach hood to unit at this time 4 On 012 and 014 units install vertical discharge block off plate over duct openings See Fig 1...

Page 15: ...N 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOOR TEMP F REV 97 3672 CW SETPOINTS CCW CONTACTS S...

Page 16: ...s provided and in stall bottom stop 11 Slide outdoor air inlet screens into screen track on hood side plate While holding screens in place fasten screen retainer to hood using screws provided See Fig...

Page 17: ...pulley hub and tighten setscrew See Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fan shaft 3 Make...

Page 18: ...12 1 88 862 2 15 911 2 46 3100 646 1 15 709 1 39 772 1 70 825 1 99 875 2 28 923 2 58 3200 662 1 25 724 1 50 785 1 80 840 2 11 887 2 41 934 2 71 3300 679 1 35 740 1 61 798 1 91 854 2 24 900 2 54 946 2...

Page 19: ...813 2 39 867 2 74 915 3 06 960 3 40 4200 830 2 55 883 2 91 931 3 24 4250 839 2 63 892 3 00 939 3 34 AIRFLOW Cfm EXTERNAL STATIC PRESSURE in wg 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 908...

Page 20: ...3000 886 1 73 943 1 88 988 1 91 995 1 95 3100 892 1 78 947 2 00 995 2 05 1008 2 07 3200 899 1 85 951 2 06 1000 2 17 1021 2 20 3300 907 1 93 959 2 10 1004 2 33 1036 2 36 3400 915 2 01 966 2 17 1009 2...

Page 21: ...2 3800 959 2 38 1001 2 58 1040 2 78 1075 2 96 3900 969 2 50 1010 2 70 1049 2 91 1085 3 11 4000 979 2 62 1020 2 83 1059 3 04 1095 3 25 4100 989 2 74 1029 2 96 1068 3 18 1105 3 39 4200 1000 2 86 1039 3...

Page 22: ...2300 816 1 65 859 1 94 888 2 24 903 2 55 911 2 85 2400 824 1 72 872 2 01 909 2 32 931 2 64 935 2 96 2500 832 1 79 882 2 09 925 2 40 955 2 72 972 3 06 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11...

Page 23: ...SSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11 2660 839 1 87 891 2 17 936 2 49 973 2 82 999 3 16 2700 846 1 95 898 2 26 946 2...

Page 24: ...7 2 10 988 2 05 995 2 20 3400 853 1 71 899 1 93 951 2 17 995 2 17 1008 2 32 3500 862 1 78 907 2 01 959 2 24 1000 2 33 1021 2 47 3600 871 1 86 915 2 09 965 2 32 1005 2 46 1036 2 59 3700 879 1 95 927 2...

Page 25: ...3 03 1058 3 29 1100 3 53 4400 945 2 68 988 2 89 1028 3 14 1066 3 41 1106 3 67 4500 955 2 82 996 3 02 1037 3 25 1074 3 54 1113 3 81 4600 967 2 96 1005 3 16 1046 3 38 1084 3 66 1121 3 95 4700 980 3 11 1...

Page 26: ...es a re frigerant leak Leak test all refrigerant tubing connec tions using electronic leak detector halide torch or liquid soap solution c Inspect all field and factory wiring connections Be sure that...

Page 27: ...emperature is below the OAT set ting and the thermostat calls for Y1 and G the economizer damper moves to the minimum position when the indoor evaporator fan starts The first stage of cooling is provi...

Page 28: ...witch has closed and a new call for cooling exists The crankcase heaters on the scroll compressors provide additional protec tion for the compressors due to the additional refrigerant charge in the su...

Page 29: ...Fig 33 MoistureMiser Option Operation 29...

Page 30: ...ting dur ing charging procedure NO CHARGE Use standard evacuating techniques After evacuating system weigh in the specified amount of refrigerant refer to Table 1 LOW CHARGE COOLING Use Cooling Chargi...

Page 31: ...harts Fig 38 41 for units with MoistureMiser option and DO NOT use Fig 42 45 for standard units TO USE COOLING CHARGING CHARTS STANDARD UNITS Take the outdoor ambient temperature and read the suction...

Page 32: ...Fig 39 Cooling Charging Chart Standard 50HJ009 Fig 40 Cooling Charging Charts Standard 50HJ012 32...

Page 33: ...harging Charts Standard 50HJ014 Fig 42 Cooling Charging Chart 50HJ008 with Optional MoistureMiser Dehumidification Package Fig 43 Cooling Charging Chart 50HJ009 with Optional MoistureMiser Dehumidific...

Page 34: ...quid line solenoid valve will not operate 1 Solenoid coil defective replace 2 Solenoid valve stuck open replace Subcooler will not deenergize Liquid line solenoid valve will not open Valve is stuck cl...

Page 35: ...Locate restriction and remove Compressor s operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Lo...

Page 36: ...nomizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired properly and no 24 vac exists c...

Page 37: ...hese actions do not occur replace economizer control module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to economizer 1 Disconnect power at TR and...

Page 38: ...programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 96...

Page 39: ......

Page 40: ...LTAGE L1 L2 L2 L3 L3 L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 EVAPORATOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING...

Reviews: