32
ECONOMI$ER
®
(FACTORY OPTION)
The EconoMi$er X system is an expandable economizer con-
trol system, which includes a W7220 economizer module (con-
troller) with an LCD and keypad (see Fig. 45). The W7220 can
be configured with optional sensors.
Fig. 45 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-alone
economizer module wired directly to a commercial set-back
space thermostat and sensors to provide outside air dry-bulb
economizer control.
The W7220 economizer module can be connected to optional
sensors for single or differential enthalpy control. The W7220
economizer module provides power and communications for
the sensors.
The W7220 economizer module automatically detects sensors
by polling to determine which sensors are present. If a sensor
loses communications after it has been detected, the W7220
economizer controller indicates a device fail error on its LCD.
System Components
The EconoMi$er X system includes an economizer module,
20k mixed air sensor, damper actuator, and either a 20k out-
door air temperature sensor or S-Bus enthalpy sensors.
Economizer Module
The module is the core of the EconoMi$er X system. The mod-
ule is mounted in the unit’s control box, and includes the user
interface for the system. The W7220 economizer module pro-
vides the basic inputs and outputs to provide simple economiz-
er control. When used with the optional sensors, the economiz-
er module provides more advanced economizer functionality.
S-Bus Enthalpy Control Sensors
The sensor is a combination temperature and humidity sensor
which is powered by and communicates on the S-Bus. Up to
three sensors may be configured with the W7220 economizer
module.
CO
2
Sensor (optional)
The sensor can be added for Demand Controlled Ventilation
(DCV).
Specifications
W7220 Economizer Module
The module is designed for use with 2 to 10 Vdc or bus com-
municating actuator. The module includes terminals for CO
2
sensor, Mixed Air sensor, and an Outdoor Dry Bulb sensor. En-
thalpy and other options are available with bus sensors.
User Interface
The interface provides status for normal operation, setup parame-
ters, checkout tests, and alarm and error conditions with a 2-line
16 character LCD display and four button keypad.
Electrical
• Rated Voltage —
20 to 30 Vac RMS, 50/60 Hz
• Transformer — 100 va maximum system input
• Nominal Power Consumption (at 24 Vac, 60 Hz) — 11.5
VA without sensors or actuators
• Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
• External Sensors Power Output — 21 Vdc ± 5% at 48mA
Inputs
Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb
change over or an OA bus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional Re-
turn Air (RA) bus sensor can be added to the system for differen-
tial enthalpy or dry bulb changeover. For differential dry bulb
changeover a 20k ohm sensor is required in the OA and a bus sen-
sor in the RA. DIP switch on RA bus sensor must be set in the RA
position.
Dry Bulb Temperature (optional) and Mixed Air (required),
20k NTC
2-wire (18 to 22 AWG)
Temperature range –40 to 150°F (–40 to 65°C)
Temperature accuracy –0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG)
Temperature: range –40 to 150°F (–40 to 65°C)
Temperature accuracy –0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) S-Bus sensors may be connected to the
W7220 economizer module. For outdoor air (OA), return air (RA)
and discharge (supply) air (DA).
4 Binary Inputs —
1-wire 24 Vac + common GND (see Fig. 46
for wiring details).
24 Vac power supply —
20 to 30 Vac 50/60Hz; 100 VA Class 2
transformer.
Outputs
Actuator Signal
2-10 Vdc; minimum actuator impedance is 2k ohm; bus
two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature
–40 to 150°F (–40 to 65°C).
Exception of display operation down to –4°F with full
recovery at –4°F from exposure to –40°F
Storage Temperature
–40 to 150°F (–40 to 65°C)
Shipping Temperature
–40 to 150°F (–40 to 65°C)
Relative Humidity
5% to 95% RH non-condensing
IMPORTANT: All inputs and outputs must be Class 2
wiring.
Summary of Contents for 50HCQD07
Page 4: ...4 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 09 Size Units ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 09 Size Units cont ...
Page 24: ...24 Fig 37 Electro Mechanical Control Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Page 25: ...25 Fig 38 Electro Mechanical Control Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Page 26: ...26 Fig 39 Electro Mechanical Control Wiring 50HCQ 08 09 208 230v 460v 575v ...
Page 27: ...27 Fig 40 Electro Mechanical Power Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Page 28: ...28 Fig 41 Electro Mechanical Power Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Page 29: ...29 Fig 42 Electro Mechanical Power Wiring 50HCQ 08 09 208 230v 460v 575v ...
Page 30: ...30 Fig 43 PremierLink Wiring Schematic 50HCQ07 09 208 230v 460v 575v ...
Page 31: ...31 Fig 44 RTU Open System Control Wiring ...
Page 49: ......