22
Single Point Boxes and Supplementary Fuses
When the unit MOCP device value exceeds 60-A, unit-mount-
ed supplementary fuses are required for each heater circuit.
These fuses are included in accessory single point boxes, with
power distribution and fuse blocks. The single point box will
be installed directly under the unit control box, just to the left
of the partition separating the indoor section (with electric
heaters) from the outdoor section. The single point box has a
hinged access cover. See Fig. 35. The single point box also in-
cludes a set of power taps and pigtails to complete the wiring
between the single point box and the unit’s main control box
terminals. Refer to the accessory heater and single point box
installation instructions for details on tap connections on the
field-installed electric heat accessory.
All fuses on 50HCQ units are 60-A. (Note that all heaters are
qualified for use with a 60-A fuse, regardless of actual heater
ampacity, so only 60-A fuses are necessary.)
Single Point Boxes without Fuses
Refer to accessory heater and single point box installation in-
structions for details on tap connections.
Fig. 35 — Typical Single Point Installation
Table 5 — Heater Model Number
ALLIED PA
MODEL NO.
ERIAL NO.
CORP.
11
13
21
23
OD
22.2
3
1
23
ISTED AIR
NDITIONING
UIP ACCESS
346N
.
P / N
2-
5610-4
REV
1
1
1
3
2
1
2
3
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
FOAM
BUSHING
DRIP BOOT
BRACKET
MOUNTING
SCREWS
HEATER
RELAYS
POWER
WIRES
HEATER
MOUNTING
SCREWS
BARE HEATER
MODEL NUMBER
C
R
H
E
A
T
E
R
0
0
1
A
0
0
Heater Sales Package
P/N includes:
C
R
H
E
A
T
E
R
1
0
1
A
0
0
Bare Heater
Carton and packing
materials
Installation sheet
Summary of Contents for 50HCQ07
Page 4: ...4 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 09 Size Units ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 09 Size Units cont ...
Page 24: ...24 Fig 37 Electro Mechanical Control Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Page 25: ...25 Fig 38 Electro Mechanical Control Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Page 26: ...26 Fig 39 Electro Mechanical Control Wiring 50HCQ 08 09 208 230v 460v 575v ...
Page 27: ...27 Fig 40 Electro Mechanical Power Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Page 28: ...28 Fig 41 Electro Mechanical Power Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Page 29: ...29 Fig 42 Electro Mechanical Power Wiring 50HCQ 08 09 208 230v 460v 575v ...
Page 30: ...30 Fig 43 PremierLink Wiring Schematic 50HCQ07 09 208 230v 460v 575v ...
Page 31: ...31 Fig 44 RTU Open System Control Wiring ...
Page 49: ......