23
Fig. 42 — Typical Supply Air Smoke Detector Sensor
Location
RETURN AIR SMOKE DETECTOR SENSOR WITHOUT
ECONOMIZER
The sampling tube is located across the return air opening on
the unit basepan. See Fig. 43. The holes in the sampling tube
face downward, into the return air stream. The sampling tube is
connected through tubing to the return air sensor that is mount-
ed on a bracket high on the partition between return filter and
controller location. The sensor is shipped in a flat-mounting lo-
cation. Installation requires that this sensor be relocated to its
operating location and the tubing to the sampling tube be
connected. See installation steps.
Fig. 43 — Typical Return Air Smoke Detector
Location
RETURN AIR SMOKE DETECTOR SENSOR WITH
ECONOMIZER
The sampling tube is inserted through the side plates of the
economizer housing, placing it across the return air opening on
the unit basepan. See Fig. 44. The holes in the sampling tube
face downward, into the return air stream. The sampling tube is
connected using tubing to the return air sensor mounted on a
bracket high on the partition between return filter and control-
ler location. The sensor is shipped in a flat-mounting location.
Installation requires the sensor be relocated to its operating
location and the tubing to the sampling tube be connected. See
installation steps below.
Fig. 44 — Return Air Sampling Tube Location (View
reoriented to show opposite side for clarity.)
Completing Installation of Return Air Smoke
Detector
Use the following steps to complete the installation of the
return air smoke detector.
1. Unscrew the two screws holding the return air sensor
detector plate. See Fig. 45. Save the screws.
Fig. 45 — Return Air Smoke Detector
Shipping Position
2. Remove the return air smoke sensor module and its
detector plate.
SUPPLY AIR
SMOKE DETECTOR
RETURN AIR
SMOKE DETECTOR
(AS SHIPPED)
RETURN AIR
SAMPLING TUBE
SAMPLE TUBE
SCREWS
FLEXIBLE EXHAUST TUBES
Summary of Contents for 50FC A04 Series
Page 96: ...96 APPENDIX D WIRING DIAGRAMS Fig J 50FC 04 06 208 230 1 60 Unit with RTU Open Controller...
Page 97: ...97 APPENDIX D WIRING DIAGRAMS Fig K 50FC 04 06 208 230 3 60 Unit with RTU Open Controller...
Page 98: ...98 APPENDIX D WIRING DIAGRAMS Fig L 50FC 04 06 460 575 3 60 Unit with RTU Open Controller...
Page 99: ...99 APPENDIX D WIRING DIAGRAMS Fig M 50FC 07 208 230 Unit with RTU Open Controller...
Page 100: ...100 APPENDIX D WIRING DIAGRAMS Fig N 50FC 07 460 575 Unit with RTU Open Controller...
Page 101: ...101 APPENDIX D WIRING DIAGRAMS Fig O 50FC 04 06 Power Wiring Diagram 208 230 1 60...
Page 102: ...102 APPENDIX D WIRING DIAGRAMS Fig P 50FC 04 07 Power Wiring Diagram 208 230 3 60...
Page 103: ...103 APPENDIX D WIRING DIAGRAMS Fig Q 50FC 04 07 Power Wiring Diagram 460 575 3 60...
Page 104: ...104 APPENDIX D WIRING DIAGRAMS Fig R 50FC 04 06 SystemVu Control Wiring Diagram All Voltages...
Page 105: ...105 APPENDIX D WIRING DIAGRAMS Fig S 50FC 07 SystemVu Control Wiring Diagram All Voltages...
Page 106: ...106 APPENDIX D WIRING DIAGRAMS Fig T 50FC 04 06 SystemVu Power Wiring Diagram 208 230 1 60...
Page 107: ...107 APPENDIX D WIRING DIAGRAMS Fig U 50FC 04 07 SystemVu Power Wiring Diagram 208 230 3 60...
Page 108: ...108 APPENDIX D WIRING DIAGRAMS Fig V 50FC 04 07 SystemVu Power Wiring Diagram 460 575 3 60...