47
Red LED-Status
C08452
Fig. 59
−
Integrated Gas Control (IGC) Board
Table 14 – IGC Connections
TERMINAL LABEL
POINT DESCRIPTION
SENSOR LOCATION
TYPE OF I/O
CONNECTION
PIN NUMBER
INPUTS
RT, C
Input power from TRAN 1
control box
24 VAC
—
SS
Speed sensor
gas section
analog input
J1, 1‐3
FS, T1
Flame sensor
gas section
switch input
—
W
Heat stage 1
LCTB
24 VAC
J2, 2
RS
Rollout switch
gas section
switch input
J2, 5‐6
LS
Limit switch
fan section
switch input
J2, 7‐8
CS
Centrifugal switch (not used)
—
switch input
J2, 9‐10
OUTPUTS
L1, CM
Induced draft combustion motor
gas section
line VAC
IFO
Indoor fan
control box
relay
J2, 1
GV
Gas valve (heat stage 1)
gas section
relay
J2, 11‐12