52
d. Press ▼ (Down Arrow) twice to reach the following
display:
e. Press OK; the following display appears:
NOTE: The number in the bracket may be different from what is
shown above.
f. Press OK and then use the ▲ and ▼ (Up and Down
Arrow) keys to scroll to the proper motor horsepower.
Press OK again to set the selected hp.
g. Press ▼ (Down Arrow) once, the following display
appears:
h. Press OK to highlight the voltage value. Use the ▲ and
▼ (Up and Down Arrow) keys to select the nameplate
voltage. Press OK again to set the selected voltage.
i. Press ▼ (Down Arrow) once to display the following:
j. Press OK to highlight the Frequency value and then use
the ▲ and ▼ (Up and Down Arrow) keys to select the
nameplate Hz. Press OK again to set the selected Hz.
k. Press ▼ (Down Arrow) once to display the following:
l. Press OK to highlight the Current value and then use the
▲ and ▼ (Up and Down Arrow) keys to select the Max
Amps value provided. Press OK again to set the selected
Max Amps.
NOTE: The Max Amps is greater than the nameplate value.
Check the VFD Unit Parameters (see Tables 26-28 on pages
55-58) and use the value listed for the given unit in the column
labeled “Motor Current Must-Hold Amps”.
m. Press ▼ (Down Arrow) once to display the following
n. Press OK to highlight the rpm value and then use the ▲
and ▼ (Up and Down Arrow) keys to select the name
-
plate rpm. Press OK again to set the selected rpm.
6. Entering Parameters for 1-71, 1-73, 1-82, and 1-90:
a. Press the Menu key to move the ▼ (triangle icon) so it is
positioned over Main Menu. The display shows the fol
-
lowing:
b. Press ▼ (Down Arrow) once to highlight the bottom
row.
c. Press OK, the display changes to:
d. Press ▼ (Down Arrow) until the following display
appears:
e. Press OK, the following display appears:
f. Press OK to highlight the number and then use the ▲
and ▼ (Up and Down Arrow) keys to select the number
provided in Tables 26-28. Press OK again to set the
selected value.
g. Press ▼ (Down Arrow) twice, the following display
appears:
h. Press OK to highlight the number in the bracket and then
use the ▲ and ▼ (Up and Down Arrow) keys to select
the number provided in Table 26-28. Press OK again to
set the selected value.
i. Press the Back key once, the following display appears:
j. Press ▼ (Down Arrow) once, the following display
appears:
k. Press OK, the following display appears:
l. Press ▼ (Down Arrow) once, the following display
appears:
m. Press OK to highlight the number and then use the ▲
and ▼ (Up and Down Arrow) keys to select the number
provided in Tables 26-28. Press OK again to set the
selected value.
n. Press the Back key once, the following display appears:
o. Press ▼ (Down Arrow) once, the following display
appears:
p. Press OK, the following display appears:
q. Press OK to highlight the number in the bracket then use
the ▲ and ▼ (Up and Down Arrow) keys to select the
number provided in Tables 26-28. Press OK again to set
the selected value.
7. Setting References:
a. Press the Menu key to move the ▼ (triangle icon) so it is
positioned over Main Menu. The display shows the fol
-
lowing:
b. Press ▼ (Down Arrow) three times, the following dis
-
play appears:
1—1* Motor Selection
1—2* Motor Data
1-20 Motor Power
[9] 1.5kW - 2 hp
1-22 Motor Voltage
230V
1-23 Motor Frequency
60Hz
1-24 Motor Current
6.61A
1-25 Motor Nominal Speed
1740rpm
0—** Operation / Display
1—** Load and Motor
1—0* General Settings
1—1* Motor Selection
1—6* Load Depen. Setting
1—7* Start Adjustments
1-71 Start Delay
2.0s
1-73 Flying Start
[1] Enabled
1—6* Load Depen. Setting
1—7* Start Adjustments
1—7* Start Adjustments
1—8* Stop Adjustments
1-80 Function at Stop
[0] Coast
1-82 Min Speed for Functio…
1.0 Hz
1—7* Start Adjustments
1—8* Stop Adjustments
1—8* Stop Adjustments
1—9* Motor Temperature
1-90 Motor Thermal Prote…
[4] ETR trip 1
0—** Operation / Display
1—** Load and Motor
2—** Brakes
3—** Reference / Ramps
Summary of Contents for 48LC Series
Page 5: ...5 Fig 2 Unit Dimensional Drawing Size 08 Unit ...
Page 6: ...6 Fig 2 Unit Dimensional Drawing Size 08 Unit cont ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Size 09 and 12 Units ...
Page 8: ...8 Fig 3 Unit Dimensional Drawing Size 09 and 12 Units cont ...
Page 11: ...11 Fig 6 Roof Curb Details Size 08 12 Units ...
Page 21: ...21 Fig 34 48LC 08 12 Electro mechanical Control Wiring Diagram ...
Page 22: ...22 Fig 35 48LC 08 12 RTU Open Control Wiring Diagram ...
Page 23: ...23 Fig 36 48LC 08 12 SystemVu Control Wiring Diagram ...
Page 25: ...25 Fig 38 48LC 08 12 Typical Power Wiring Diagram SystemVu Control 208 230 v Unit Shown ...
Page 61: ......