5

16. Connect the air quality plug marked “ECB-J5” from the

unit electrical harness into the Economizer Control Board
plug J5. Be sure to connect the plug with the proper orien-
tation such that the locking tabs capture the plug.

17. Connect plug marked “ECB-J4” from the unit electrical

harness into the Economizer Control Board plug J4. Be
sure to connect the plug with the proper orientation such
that the locking tabs capture the plug.

18. Route the wires from the harness installed during Steps 6-

8 into the control box. (See Fig. 11.) The wires should be
routed into the box through the hole located at the bottom
right corner of the control box, behind the field connec-
tion terminal blocks. Use the other bushing provided to
install the wires so that the control box does not damage
them.

19. Connect the plug marked “ECB-J8 (16-18)” to the J8

connector on the Economizer Control Board, plug J8,

pins 16 through 18. Connect the plug marked “ECB-J7”
to the J7 plug on the Economizer Control Board.

20. Several wires will need to be connected to the BACK-

SIDE of the terminal strips TB4 and TB5. The wires are
marked with the appropriate locations. Connect the wires
as marked to the back of the TB4 terminal strip, locations
1 and 7. Connect the wires as marked to the back of the
TB5 terminal strip, locations 6, 7, 8 and 9. Connect the
red power wire marked “CB1” to the CB1 circuit breaker
on the load side.

21. Secure all wires so that they do not rub any sharp edges or

interfere with any moving parts.

22. Replace the control box cover using the screws saved

from Step 13.

23. Power can now safely be restored to the unit.

FU2

FU1

FU3

FU4

WIRE ROUTING

PLASTIC
BUSHING

CB1

CB2

CB3

ECB

TB2

TB4

TB3

TB5

Fig. 11 — Wiring Installation into Control Box

LEGEND

FU

Fuse

CB

Circuit Breaker

ECB —

Economizer Control Board

TB

Terminal Block

Summary of Contents for 48HG014-028

Page 1: ...nnel When working on air conditioning equipment observe precau tions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations INSTALLATION 1 Remove two manual dampers and one mist eliminating ...

Page 2: ...stic bushing being careful not to damage the wires Route the harness across the back of the top member of the frame as shown and attach to the frame us ing the wire ties provided See Fig 4 RETURN END OF UNIT FRAME SUPPORT BRACKETS SIDE PANEL REMOVED WIRE ROUTING PLASTIC BUSHING EXISTING WIRE TIES PLASTIC BUSHING Fig 1 Return End of Unit Fig 2 Frame Support Brackets Side Panel Removed Fig 3 Slide E...

Page 3: ... unit panels can now be replaced using the screws saved from the earlier steps Be sure to inspect all panel seals prior to re assembly and replace any seals that appear damaged 12 The control wiring can now be completed 13 Open the hinged control box compartment on the unit and remove the control box cover Save the screws for use lat er Be sure not to place sharp objects on any surface that could ...

Page 4: ...J4 CEPL130346 01 STATUS LEN J1 J2 J4 J3 J5 J6 J7 J8 J9 J10 CCN YELLOW LED CCN CARRIER COMFORT NETWORK INSTANCE JUMPER RED LED STATUS MAIN BASE BOARD PART NUMBER GREEN LED LEN LOCAL EQUIPTMENT NETWORK Fig 8 Economizer Board Mounting Location Fig 9 Economizer Control Board Fig 10 Main Base Board ...

Page 5: ...lug marked ECB J8 16 18 to the J8 connector on the Economizer Control Board plug J8 pins 16 through 18 Connect the plug marked ECB J7 to the J7 plug on the Economizer Control Board 20 Several wires will need to be connected to the BACK SIDE of the terminal strips TB4 and TB5 The wires are marked with the appropriate locations Connect the wires as marked to the back of the TB4 terminal strip locati...

Page 6: ...then Use the arrow keys to scroll down to the Economizer High Temperature Lockout setting ECL H and press twice Use the arrow keys to increase or decrease the economizer lockout temperature and press and then Use the arrow keys to scroll down to the Economizer Low Temperature Lock out setting ECL L and press twice Use the ar row keys to increase or decrease the economizer lockout temperature and p...

Page 7: ...connections Damper is jammed Identify the obstruction and safely remove Economizer operation is limited to minimum position Minimum position is set incorrectly Adjust minimum position setting Outdoor air temperature is above economizer high temperature lockout Adjust the high temperature lockout setting if it is incorrect otherwise economizer is operating correctly Outdoor air temperature is below...

Page 8: ...any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80034 Printed in U S A Form 48 50HG 5SI Pg 8 8 01A 6 01 Replaces New Copyright 2001 Carrier Corporation Book 1 1 4 4 Tab 1a 1b 6a 6b 3 2 3 3 3 4 3 5 3 6 3 7 ...

Reviews: