2

INSTALLATION

48/50A Units — 

The CO

2

 sensor is to be installed in the

predrilled holes located above the auxiliary control box (see

Fig. 2).

1. Shut off unit power supply.
2. Open the hinged auxiliary control box access door and

secure.

3. Remove the sensor and cover from the sensor mounting

plate.

4. Secure mounting plate to bracket (48/50A) with no. 8

screws (see Fig. 3).

5. Wire the electrical harness to the sensor as shown in

Fig. 3 and 4.

6. Remove the blankout plate from the partition, just above

the auxiliary control box.

7. Attach the sensor to the mounting plate.
8. Mount the bracket to the partition using 2 sheet metal

screws (see view F in Fig. 2).

9. Connect the electrical harness (PL18).

10. Restore power to unit.

48/50P and 48/50Z Units — 

The CO

2

 sensor is to be

installed in the predrilled holes located in the power exhaust

section. See Fig. 5-11.

1. Shut off unit power supply.
2. Open the power exhaust section doors/panels to gain

access.

3. Remove the sensor and cover from the sensor mounting

plate.

4. Secure mounting plate to the bracket with no. 8 screws. 
5. The electrical wire harness for the CO

2

 sensor is factory

installed. Locate the four wires in the power exhaust

section. Wire the electrical harness to the sensor as shown

in Fig. 4.

6. Attach the sensor to the mounting plate.

Mount the bracket to the appropriate location:

size 030-050 units with power exhaust, see Fig. 5 and 6.

size 030-050 units with economizer only, see Fig. 7.

size 030-050 units with no economizer or power exhaust,

see Fig. 8.

48/50P055-100 and 48/50Z055-105 units with power ex-

haust, see Fig. 9.

48/50P055-100 and 48/50Z055-105 units with economiz-

er only, see Fig. 10.

48/50P055-100 and 48/50Z055-105 units with no econo-

mizer or power exhaust, see Fig. 11.

CO

2

SENSOR

AUXILIARY
CONTROL BOX

PARTITION

BRACKET
(48/50A)

ELECTRICAL
HARNESS

Fig. 2 — 48/50A CO

2

 Sensor Mounting Location

VIEW F