background image

- 2 - 

 

INTRODUCTION 

This document  contains  general  installation 

instructions  for the 42TW unit Fan Coils. Refer 

to   the   unit-wiring   diagram   installed   on   the 

blower  housing  or specific  manufacturer 

literature  for any other type of factory-mounted 

controls. 

See  drawings  for unit  configurations, 

dimensions,    clearances,    and  pipe 

connections.  Refer  to unit  wiring  label  for  all 

electrical  connections;  follow NEC  (National 

Electrical Code) and local codes. 

 

RECEIVING 

42TW  fan coil units  are shipped  individually 

packed  in carton  boxes.    When  cartons  are 

individually  off  loaded  from  the  truck,  do  not 

roll,  nor  throw,  or drop  the  carton  to  avoid 

damage  to  the  contents.   Store  boxes  upright 

as  the  symbols  on  the  boxes  indicated.    Do 

not stack units more than 6 units high for size 

11-16 and 8 units high for other sizes. 

 

INSPECTION 

Check  the  shipment  against  shipping  list  and 

remove  unit from  the  carton  and  take  off 

protective   covering.     If   the   unit   has   been 

 

damaged,    file  claim   with    transportation 

company and notify Carrier immediately. 

 

PROTECTION 

Protection  unit  from  damage  caused  by  job 

site  debris.    Do  not  allow  dust,  debris  and 

water  to  get  into  the  unit.   These  will  damage 

unit’s  component  and  unit’s  performance  will 

be affected. 

 

PRELIMINARY  CHECK 

Following  is  a checklist  which  should  be 

checked  before  the installation  is started.   The 

installer  should  be  familiar  with  each  of  the 

following  requirements  before  the  actual 

installation. 

 

-    

Space   requirement   and   clearance,   See 

Fig.3. 

-    

Ceiling or mounting strength. 

-    

Piping connections. 

-    

Condensate drain connection. 

-    

Power supply and wiring. 

-    

Air duct connections. 

 

 

 

 

Table.1  - Physical Data - 42TW3, 42TD3 – 2 Pipe  System 

 

Model  42TW3 

Model  42T 

D

Size 

03 

05 

06 

07 

09 

11 

12 

16 

CFM* 

348 

592 

692 

780 

883  1181  1385 

1572 

Cooling  Capacity  (kw)* 

3.4 

6.1 

7.5 

8.9 

9.9 

11.5  14.5 

16.9 

Colling  Capacity  (kbtuh) 

11.7 

20.7 

25.6  30.4  33.8  39.2  49.5 

57.7 

SHR 

0.75 

0.74 

0.72  0.71  0.71  0.75  0.73 

0.73 

Power  Supply 

208-230, 1 ph, 60 Hz / 220-240, 1 ph, 50 Hz / 110-127, 1 ph, 60 Hz 

Motor  HP( Nominal) 

1/15 

1/10 

1/15 

1/10 

Input  Watts  ( Med Speed, 25 Pa ESP) 

56 

64 

70 

80 

80 

130 

146 

160 

Number  of Motors 

1, 3 Speed 

2, 3 Speed 

Coil  Material 

Smooth copper tubes/ Aluminum fins with double wavey fin 

Coil  Face Area, m^2 

0.11 

0.15 

0.21  0.26  0.31  0.31  0.44 

0.52 

Coil  Connection Type 

Sweat Type 

Coil  Connection  Size 

5/8 Inch 

7/8 Inch 

Number  of Rows 

Fin Denisty/  Inch 

14 

Drain  Diameter 

5/8 Inch 

Blower  type 

Direct drive forward curved centerifugal fan 

Blower  Number 

Blower  Diameter  / Width,  mm 

156/220  156/170 

156/220 

156/170 

156/220 

Filter  Type 

Washable Aluminum Filter 

Width,  mm 

640 

800 

1010  1220  1430  1430  1430 

1640 

Depth,  mm 

590 

Height,  mm 

275 

375 

Net Weight,  kg 

18 

23 

28 

32 

39 

43 

49 

56 

* At 26.7/19 c approch 6.7c water inlet/12.7c water outlet, High speed @ 0 Static 

Summary of Contents for 42TD Series

Page 1: ...rvicing air conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified service personnel should install repair or service air conditioning equi...

Page 2: ...hould be checked before the installation is started The installer should be familiar with each of the following requirements before the actual installation Space requirement and clearance See Fig 3 Ce...

Page 3: ...outlet High speed 0 Static Table 3 Physical Data 42TW4 42TD4 4 Pipe System Model 42TW4 Model 42TD4 Size 03 04 05 06 08 10 11 14 CFM 313 533 623 702 795 1065 1247 1416 Cooling Capacity kw 3 4 5 3 6 9 8...

Page 4: ...0 38 0 29 0 44 0 34 0 24 Watts 109 91 73 93 75 56 86 67 48 10 Amps 0 84 0 75 0 65 0 72 0 62 0 53 0 64 0 54 0 44 Watts 164 145 127 140 121 103 124 105 86 11 Amps 1 03 0 84 0 65 0 86 0 70 0 53 0 78 0 61...

Page 5: ...7 1055 1091 16 2062 1575 1268 1770 1295 1530 H At High Fan Speed M At Medium Fan Speed L At Low Fan Speed Table 6 b Fan Performance 42TW 4 SI 42TW4 Air Flow m 3 hr Ex Static Pres Pa 0 12 5 25 37 5 Uni...

Page 6: ......

Page 7: ...age against available power supply For special installation consult local building and electrical codes INSTALLATION PLACING UNIT IN POSITION 1 Select the unit location Allow adequate space for free a...

Page 8: ...unit to operate within duct external static pressure limits as shown on job submittals Units designed to operate with ductwork may be damaged if operated without intended ductwork attached Units provi...

Page 9: ...inutes to prevent overloading 2 Operation Mode Selection Key Toggles the operation mode Cool Dry Heat or Fan only 3 Fan Speed Selection Key Toggles the fan speed Auto High Medium or Low Note Fan key i...

Page 10: ...n Sleep function for healthy sleep to control automatically the room temperature and stop automatically the operation of the air conditioner after certain set off time Sleep mode is valid in cool or h...

Page 11: ...WIRING SCHEMATIC 42TW TD COOL HEAT...

Page 12: ...WIRING SCHEMATIC 42TW TD COOL HEAT WITHOUT CONTROL...

Page 13: ...fan assembly remove front or bottom panel Fan assembly may be removed from its tracks if unit has a long conduit lead Use a stiff brush or vacuum to remove dirt and debris from scroll Wipe all fan sur...

Page 14: ...t protected from direct foreign matter Cooling Heating Connections 13 Connect field piping to unit 14 Pressure test all piping for leaks 15 Install drain line traps as required 16 Insulate all piping...

Page 15: ...NOTES...

Page 16: ...Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Reviews: