42PHQ...N
Carrier Korea Operation
The General Information For Multi or T-kit model
The configuration setting by remote controller
• Entering Configuration Mode
• Press the
“MODE”
(
2
) button together with the
“FLAP”
(
3
)button
for 7 continuous seconds while remote is in OFF mode.
LCD will display the following message:
In case of first use or after battery
change, default values will be displayed.
[CFG/HP]
Once user has changed configuration,
the new stored values will be displayed.
• Configuration Procedure
•
MODE”
(
2
) Button - Selects the different configuration
items: AC – HP and Mono – T-Kit – Multi application (please
refer to Example).
•
“ ”
and
“ ”
(
4
) Buttons – Increase or decrease the
displayed value.
Once a value is changed, it flashes until the
“FLAP”
(
3
) button
is pressed.
•
“FLAP”
(
3
) Button - Transmits a configuration message for the
parameter that is displayed.
If user wants to configure more than one parameter, the
“FLAP”
(
3
) button must be pressed step by step until each
parameter is being displayed.
•
“I/O”
(
1
) Button - To exit Configuration Mode, and return the
LCD display back to its previous operating condition (OFF
mode).
If there is no key-in during 30 continuous seconds, the remote will
exit automatically the Configuration mode.
The parameter is set back to its latest transmitted value.
Example :
1) Step: “Enter configuration mode”
• Press
MODE
and
FLAP
buttons together for 7 seconds.
2)
Step:
“Unit configuration”
•
Display : “CFG”
•
Default Value : “HP”
•
Available Value :
HP – Heat Pump
AC – Cool Only
3) Step: “Transmit and Go to next step”
• Press
FLAP
button and then
MODE
button.
4)
Step:
“Application selection“
•
Display : “GFd”
•
Default Value : “1”
•
Available Value :
1–238 : Mono (1x1)
239 : T-Kit
240 : Multi
5) Step: “Transmit and Exit configuration mode”
• Press
FLAP
button and then
I/O
button.
6) Step: “System reset”
• After changing configuration by remote,
TURN OFF AND
THEN ON ELECTRIC POWER
SUPPLY
to the system to
make configuration effective.
The Operating Test for Multi or T-kit model
This procedure is used to check the operation after unit installation.
Press the EMER. button continuously for 5-10 seconds.
The unit will now be in TEST mode.
Press the EMER. button once more after checking, to return to
normal operation.
If there is any input signal (remote control signal or EMER. button
press) during test operation, the TEST mode will return to normal
operation.
The setting conditions of the TEST operation for Multi or T-kit model
are as follows.
- Operation LED : ON
- Timer LED : Blink ON for 0.5 seconds and OFF for 0.5
seconds four(for T-kit model) and three
times(for Multi model)
- Operating mode :
Cool mode for 3 minutes, firstly and then
Heat mode for 2 minutes and
Cool mode until test mode is exited
- Fan speed : High
- Timer mode : Disabled
- Discharge air direction : SWING
햲
햳
햵
햴