42 HWS

E N G L I S H

System configuration and operating test

System configuration

Once the electrical connections have been completed, enter
the system configuration.
Check the correct switch position (see "Electrical connection")
(models without electric heater). Incorrect positioning of the
switch causes major system operation problems.
For information on the remote controller refer to the operation
and maintenance manual.

To configure the system proceed as follows:
• Place batteries in the controller, observing the polarity direction

indicated.

• Energize the system by switching main switch in the ON position.

• Press the button for the selection of the operating mode 

together with the button for the clock time adjustment for at least
two seconds (the latter is recessed and located next to the battery
compartment, use a pointed tool to activate).

• The controller readout will display the letters “ld:un”.

• If the controller readout will display the letters “CA:P” or “Ad:dr”,

press button 

 until the letters “ld:un” will be displayed.

• Now, by pressing buttons for the temperature adjustment

 

 

display one of the figures shown in the following table according
to the model size in use.

Model size

Figure to select

07 - 09 - 12

1

18 - 24

2

• To send the transmission of the message to the unit, press the

starting button 

, and then the button for the selection of the

fan speed 

 

for at least two seconds.

• The controller will automatically turn off and configuration is

completed.

Operating test

• Energize the system by putting the mains supply switch to the ON

position.

• Position the operating switch located in the electrical board inside

the unit on “Test”.

1) The air conditioner will operate in the cooling mode for a

maximum period of 30 minutes without thermostatic control of
the room temperature and without the time delay protection
against frequent compressor cycling.

2) The air distribution louver will operate in the “SWING” mode.

3) Red indicator on the unit will light up.

• During test operation, the installer must check that the 3

conditions above are fulfilled.

• Slide the switch under the unit panel from the “Test” to the

“Normal” position to exit test program.

• During the test program, any signal sent to the unit by the remote

controller will stop the test and put the air conditioner in the mode
shown on display.

Summary of Contents for 42 HWS 07

Page 1: ...42 HWS 42 HWS 07 09 12 42 HWS 18 24 INSTALLATION MANUAL...

Page 2: ...and maintenance instructions for the indoor unit and the installation instructions for the indoor and the outdoor unit are given in the manuals for each unit Contents Page Dimensions and weight 2 Nomi...

Page 3: ...7 42HWS009 703IJ 40 48 42HWS012 703IJ 40 48 42HWS018 03IJ 40 60 1 42HWS024 03IJ 40 85 1 Heat pump 42HWS007 703IJ 40 37 37 42HWS009 703IJ 40 48 48 42HWS012 703IJ 40 48 48 42HWS018 03IJ 40 60 1 60 1 42H...

Page 4: ...ection 4 Batteries 2 Remote control operation 5 Installation manual 1 Unit installation 6 Owner s manual 1 Use and maintenance 7 Template 1 Indoor unit positioning Minimum clearances mm 20 20 80 Table...

Page 5: ...g units which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resulting from unapproved cou...

Page 6: ...cause condensate dripping Flattening or kinking the refrigerant pipes or condensate pipes Excessive height difference between outdoor and indoor units see installation manual of outdoor unit Unnecessa...

Page 7: ...unit centre line which is indicated with a vertical line on the mounting plate Drill holes and install the plate using the 4 screw anchors and screws provided Check that no vibrations can occur by mov...

Page 8: ...d in the opposite way Condensate drain pipe and refrigerant tubes Fasten the electric wires and refrigerant tubes together Allow an additional length to the electric wires for easy connection to the u...

Page 9: ...ting with anti freeze oil Finger tighten the fitting several turns then tighten it fully with two wrenches by applying the tightening torque indicated in the table Connection to the unit Insufficient...

Page 10: ...cable must be H07 RN F or higher type while the indoor outdoor unit interconnecting wires must be A05 RN F type or higher synthetic rubber insulation with Neoprene coating according to EN 60335 2 40 a...

Page 11: ...Y Compressor interlocking contact O Reversing valve control heat pump only W2 Outdoor fan signal heat pump only S1 Outdoor coil sensor heat pump only S2 Outdoor coil sensor heat pump only Indoor unit...

Page 12: ...ons for the temperature adjustment display one of the figures shown in the following table according to the model size in use Model size Figure to select 07 09 12 1 18 24 2 To send the transmission of...

Page 13: ...r When installation and tests are completed explain the Operation and Maintenance Manual to the owner with particular attention to the main operating modes of the air conditioner such as Turning the u...

Reviews: