background image

7

Step 6 — Position  and  Connect Controller — 

Wired controllers should be installed in a position that main-
tains good temperature control:

• Position the thermostat approximately 48 in. above floor

level.

• Do not position thermostat where it can be directly

affected by the unit’s discharge airstream.

• Avoid external walls and drafts from windows and doors.

• Avoid positioning near shelves and curtains as these

restrict air movement.

• Avoid heat sources such as direct sunlight, heaters, dim-

mer switches, and other electrical devices.

REMOTE WIRED CONTROLLER (PROGRAMMA-
BLE) —  To connect a remote programmable wired controller
(thermostat) to the indoor unit, use 4-core shielded cable and 4-
pin connector from electrical box of indoor unit (see Fig. 6).
For  setup  instructions,  refer  to  the  controller  installation
manual. 

REMOTE WIRED CONTROLLER (NON-PROGRAM-
MABLE) — To connect remote non-programmable wired
controller (thermostat) to the indoor unit, use 5-core shielded
cable and 5-pin connector from unit display panel (see Fig. 7).
For setup instructions, refer to  the  controller  installation
manual.

ALARM

ON/OF

F

P

Q (E)

X

Y (E)

L2

REMOTE ON/OFF

a40-1752

Fig. 5 — 40WAV018-048 Typical Wiring Diagram

                                LEGEND

CS

— Water Level Switch

EEV

— Electronic Expansion Valve

FM

— Indoor Fan

PUMP

— Pump Motor

T1

— Inlet Air Temperature

T2

— Coil Temperature

T2B

— Evap. Outlet Temperature in Cooling Mode

TR

— Transformer

XP1-10 — Plug
XS1-10 — Jack
XT1-2

— Terminal Block

----------

Optional Component or Field Wiring

WIRED REMOTE 
CONTROLLER

4-PIN CONNECTOR
FROM ELECTRICAL BOX

INDOOR

UNIT

a40-1726

Fig. 6 — Remote Wired Controller

(Programmable) Wiring

Summary of Contents for 40WAV

Page 1: ...and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death CAUTION is used to...

Page 2: ...d charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed Failure to follow these proce dures may result in damage to equipment For information about replacement...

Page 3: ...ank Equipment Type Capacity Btuh 018 18 000 024 24 000 030 30 000 036 36 000 048 48 000 A40 1917 RIGHT SIDE FRONT A B C TOP D BOTTOM DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT PIPE LIQUID SIDE REFRIG...

Page 4: ...pipe wire and duct con nections requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their parts of the installation Units must be installed in complian...

Page 5: ...nimum gradient of 1 in per 100 inches Condensate piping should be installed in such a way that it does not block the front service panel A drain trap may be required by local codes and is rec ommended...

Page 6: ...ugh the appropriate casing holes or knockouts and connecting the supply and ground cables to the unit s power terminal Be sure the power wiring and control wiring do not cross as this might cause dist...

Page 7: ...from electrical box of indoor unit see Fig 6 For setup instructions refer to the controller installation manual REMOTE WIRED CONTROLLER NON PROGRAM MABLE To connect remote non programmable wired cont...

Page 8: ...ondenser fan is in operation c Indicator light is showing normal operation and no er ror is indicated NOTE If the unit is turned off or restarted there is a time delay of 3 minutes for the compressor...

Page 9: ...lashing Fast Heating Cooling Mode Conflict Error E1 Timer Light Flashing Fast Communication Error Between Indoor and Outdoor Unit E2 Operation Light Flashing Fast Check Indoor Ambient Temperature Sens...

Page 10: ...is short circuited Using multi meter measure resistance of the sen sor If the resistance is 100 ohms change the sensor PC board fault Replace PC board E6 Timer Light Flashing Slow DC motor fault Repla...

Page 11: ...OFF DC Fan Static Pressure 2 ON ON DC Fan Static Pressure 3 Fig A SW1 Settings Fig B SW2 Settings ON OFF 1 2 3 4 a40 1923 POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No H...

Page 12: ...ght to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400029 01 Printed in U S A Form 40WAV 2SI Pg 12 4 16 Replaces 40WAV...

Reviews: