background image

8

CENTRAL CONTROLLER —  The central controller is
connected to the indoor unit through outdoor unit with 3-core
shielded cable (see Fig. 8). For setup instructions, refer to the
controller installation manual.

START-UP

Pre-Start Check — 

Once installation is complete, make

the following pre-start checks:

1.

All indoor and outdoor units are properly installed.

2.

All piping and insulation is complete.

3.

All electrical connections (both power and control) are
properly terminated.

4.

All condensate drains are installed correctly.

5.

The power supply is of the right voltage and frequency. 

6.

The units are properly grounded in accordance with cur-
rent electrical codes. 

7.

Suction and liquid line isolation valves are in open posi-
tion.

System Operation Check — 

Once the installation

and pre-start checks are completed, follow these steps:

1.

Using remote controller, select cooling or heating mode
to check the operation of the system.

2.

While the system is in operation, check the following on
indoor unit:

a. Switches or buttons on the remote controller are easy to

push.

b. Indicator light is showing normal operation and no er-

ror is indicated.

c. Swing mode of air louvers is working (if applicable to

unit).

d. Drain pump operation is normal (if applicable).

e. No abnormal vibration or noise is noticed.

3.

While the system is in operation, check the following on
outdoor unit:

a. No abnormal vibration or noise is noticed.

b. Condenser fan is in operation.

c. Indicator light is showing normal operation and no er-

ror is indicated.

NOTE: If the unit is turned off or restarted, there is a time
delay of 3 minutes for the compressor to start from the time the
power is restored.

MAINTENANCE

EVERY 3 MONTHS:

• Check the air filter condition. Clean or replace if neces-

sary.

EVERY 6 MONTHS — Follow 3-month maintenance sched-
ule.  In addition:

• Clean condensate tray with suitable cleaning agent.

• Clean the grille and panel if applicable.
EVERY 12 MONTHS — Follow 6-month maintenance
schedule. In addition:

• Be sure all electrical connections are secure.

• Check condensate pump operation if applicable.

• Check the heating and cooling action to confirm proper

operation.

INDOOR UNIT
DISPLAY PANEL

5-CORE CABLE

5-CORE SHIELDED CABLE

INDOOR UNIT
ELECTRIC CONTROL BOX

INDOOR UNIT
ELECTRIC CONTROL
PANEL

WIRED CONTROLLER

BACK

A40-1714

5-CORE CABLE

Fig. 7 — Remote Wired Controller

(Non-Programmable) Wiring

X Y E F1 F2 E

FORCED ON

EMG. STOP

R

C

TO INDOOR UNIT

X,Y,E

DAISY CHAIN

NOT USED

FORCED
ON
SWITCH

EMERGENCY
STOP
SWITCH

24 VAC

a40-1774

Fig. 8 — Central Controller Wiring

CAUTION

When servicing or repairing this unit, use only factory-
approved service replacement parts. Refer to the rating
plate on the unit for complete unit model number, serial
number and company address. Any substitution of parts or
controls not approved by the factory will be at the owner’s
risk and may result in equipment damage.

CAUTION

To avoid equipment damage, do not attempt to reuse any
mechanical or electrical controllers that have been wet.
Replace defective controller.

Summary of Contents for 40WAV

Page 1: ...and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death CAUTION is used to...

Page 2: ...d charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed Failure to follow these proce dures may result in damage to equipment For information about replacement...

Page 3: ...ank Equipment Type Capacity Btuh 018 18 000 024 24 000 030 30 000 036 36 000 048 48 000 A40 1917 RIGHT SIDE FRONT A B C TOP D BOTTOM DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT PIPE LIQUID SIDE REFRIG...

Page 4: ...pipe wire and duct con nections requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their parts of the installation Units must be installed in complian...

Page 5: ...nimum gradient of 1 in per 100 inches Condensate piping should be installed in such a way that it does not block the front service panel A drain trap may be required by local codes and is rec ommended...

Page 6: ...ugh the appropriate casing holes or knockouts and connecting the supply and ground cables to the unit s power terminal Be sure the power wiring and control wiring do not cross as this might cause dist...

Page 7: ...from electrical box of indoor unit see Fig 6 For setup instructions refer to the controller installation manual REMOTE WIRED CONTROLLER NON PROGRAM MABLE To connect remote non programmable wired cont...

Page 8: ...ondenser fan is in operation c Indicator light is showing normal operation and no er ror is indicated NOTE If the unit is turned off or restarted there is a time delay of 3 minutes for the compressor...

Page 9: ...lashing Fast Heating Cooling Mode Conflict Error E1 Timer Light Flashing Fast Communication Error Between Indoor and Outdoor Unit E2 Operation Light Flashing Fast Check Indoor Ambient Temperature Sens...

Page 10: ...is short circuited Using multi meter measure resistance of the sen sor If the resistance is 100 ohms change the sensor PC board fault Replace PC board E6 Timer Light Flashing Slow DC motor fault Repla...

Page 11: ...OFF DC Fan Static Pressure 2 ON ON DC Fan Static Pressure 3 Fig A SW1 Settings Fig B SW2 Settings ON OFF 1 2 3 4 a40 1923 POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No H...

Page 12: ...ght to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400029 01 Printed in U S A Form 40WAV 2SI Pg 12 4 16 Replaces 40WAV...

Reviews: