Installation and Maintenance Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

 . . . . . . . . . . . . . . . . . . . 1

GENERAL

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Step 1 — Unpack and Inspect Units

 . . . . . . . . . . . . 5

Step 2 — Position the Unit 

 . . . . . . . . . . . . . . . . . . . . 5

Step 3 — Mount the Unit

 . . . . . . . . . . . . . . . . . . . . . . 6

Step 4 — Connect Piping

. . . . . . . . . . . . . . . . . . . . . . 7

Step 5 — Complete Electrical Connections

. . . . . . 8

Step 6 — Position and Connect Controller

 . . . . . 10

ACB (Auxiliary Control Board) Interface

 . . . . . . . 13

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Pre-Start Check 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

System Operation Check 

 . . . . . . . . . . . . . . . . . . . . 13

MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

INDOOR UNIT ADDRESSING

 . . . . . . . . . . . . . . . . 13

Wireless Remote Controller (40VM900001)

 . . . . . 14

Non-Programmable Controller

. . . . . . . . . . . . . . . 14

Programmable Controller

 . . . . . . . . . . . . . . . . . . . 14

TROUBLESHOOTING

 . . . . . . . . . . . . . . . . . . . . . . . . 15

Replacement Parts

 . . . . . . . . . . . . . . . . . . . . . . . . . . 16

APPENDIX A — DIP SWITCH SETTINGS

. . . . . . . . 17

SAFETY CONSIDERATIONS

Improper  installation,  adjustment,  alteration,  service,

maintenance, or use can cause explosion, fire, electrical shock,

or other  conditions that may cause  death, personal injury or

property damage. The qualified installer or agency must use

factory-authorized  kits  or  accessories  when  modifying  this

product.

Follow  all  safety  codes.  Wear  safety  glasses,  protective

clothing,  and  work  gloves.  Use  quenching  cloth  for  brazing

operations.  Have  fire  extinguisher  available.  Read  these

instructions  thoroughly  and  follow  all  warnings  or  cautions

included in  literature and  attached to  the  unit.  Consult  local

building  codes  and  the  current  editions  of  the  National

Electrical  Code  (NEC)  ANSI/NFPA  (American  National

Standards Institute/National Fire Protection Association) 70. In

Canada, refer to the current editions of the Canadian Electrical

Code CSA (Canadian Standards Association) C22.1.

Understand  the  signal  words  — 

DANGER

WARNING

,  and

CAUTION

DANGER

  identifies  the  most  serious  hazards,

which  will  result  in  severe  personal  injury  or  death.

WARNING

  signifies  hazards  that  could  result  in  personal

injury or death. 

CAUTION

 is used to identify unsafe practices,

which  would result in minor personal injury  or product and

property damage.

Recognize  safety  information.  This  is  the  safety-alert

symbol (    ). When this symbol is displayed on the unit and in

instructions or manuals, be alert to the potential for personal

injury. Installing, starting up, and servicing equipment can be

hazardous due to system pressure, electrical components, and

equipment location.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may  be  more  than  one  disconnect  switch.  Tag  all

disconnect  locations  to  alert  others  not  to  restore  power

until work is completed.

WARNING

When installing the equipment in a small space, provide

adequate  measures  to  avoid  refrigerant  concentration

exceeding safety limits due to refrigerant leak. In case of

refrigerant  leak  during  installation,  ventilate  the  space

immediately. Failure to follow this procedure may lead to

personal injury.

WARNING

DO NOT USE TORCH to remove any component. System

contains oil and refrigerant under pressure. 

To  remove  a  component,  wear  protective  gloves  and

goggles and proceed as follows:

a. Shut off electrical power to unit.

b. Recover  refrigerant  to  relieve  all  pressure  from

system using high-pressure and low pressure ports.

c. Traces  of  vapor  should  be  displaced  with  nitrogen

and work area should be well ventilated. Refrigerant

in contact with an open flame produces toxic gases.

d. Cut component connection tubing with tubing cutter

and remove component from unit. Use a pan to catch

any oil that may come out of the lines and as a gage

for how much oil to add to the system.

e. Carefully  unsweat  remaining  tubing  stubs  when

necessary.  Oil  can  ignite  when  exposed  to  torch

flame.

Failure to follow these procedures may result in personal

injury or death.

40VMU012-048

Under Ceiling/Floor Indoor Unit for

Variable Refrigerant Flow (VRF) Systems

Summary of Contents for 40VMU

Page 1: ...ll result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal i...

Page 2: ...ures may result in damage to equipment For information about replacement oil type and viscosity see the Installation Start Up and Service Instructions for the 38VMAH and 38VMAR outdoor units UNIT 40VM...

Page 3: ...Connect the drain hose to condensate connec tion Flexible conduit and connectors 1 Routing power lines Hanging bracket 4 Used for hanging the unit Installation guide for metallic flexible pipe 1 Mount...

Page 4: ...ns shown in inches Fig 2 40VMU012 030 Dimensions NOTE All dimensions shown in inches Fig 3 40VMU036 048 Dimensions 40VMU UNIT SIZE DIMENSION in A B C D 012 024 39 26 8 19 7 8 30 50 1 2 26 8 31 1 4 A B...

Page 5: ...SITE FOR UNIT INSTALLATION To save time and to reduce the possibility of costly errors set up a complete sample installation in a typical room at the job site Check all critical dimensions such as pip...

Page 6: ...h locknuts and washers on both sides Ensure the threaded rod does not protrude more than 1 in below the mounting hole on the hanging bracket as shown in Fig 7 Fig 7 Mounting the Hanging Bracket 3 Remo...

Page 7: ...the indoor and outdoor units If the difference between them is more than 33 ft consider mounting the outdoor unit above indoor unit Refrigerant piping connection between indoor and outdoor units shou...

Page 8: ...d cables to the unit s power terminal Be sure the power wiring and control wiring do not cross This might cause disturbance on the controls side See Fig 15 for wiring diagrams OUTSIDE DIAMETER IN RECO...

Page 9: ...iliary Heat CS Condensate Switch Optional CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor HTON Output for Heating Operation PUMP Pump...

Page 10: ...r to fix the communication wire on the outdoor unit communication terminal as shown in Fig 19 Fig 19 Connecting Communication Wire to Outdoor Unit Communication Terminal If communication wires are use...

Page 11: ...or To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit...

Page 12: ...L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resistor wired controller To...

Page 13: ...hedule In addition Clean condensate tray with suitable cleaning agent Clean the grille and panel if applicable EVERY 12 MONTHS Follow the 6 month maintenance schedule In addition Be sure all electrica...

Page 14: ...confirm and exit the setting interface Fig 27 Non Programmable Controller Setting IDU Address Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Pre...

Page 15: ...mmunication Error Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 T0 E4 Check Evaporator Temperature Sensor T2B E5 Check Evaporator Outlet Temperature Sensor T2A E6 Check...

Page 16: ...E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal...

Page 17: ...o Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard Indoor Unit...

Page 18: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 40VMU001 02 Printed in U S A Form 40VMU 2SI Pg 18 02 20 Replaces 40VMU...