background image

13

ACB (Auxiliary Control Board) Interface — 

The

ACB interface is a dry contact board that can output up to four

signal  controlling  devices.  Refer  to  Fig.  15  and  24  for

connecting devices to the ACB interface board

Fig. 24 —ACB Interface

START-UP
Pre-Start Check — 

Once installation is complete, make

the following pre-start checks:

1. All indoor and outdoor units are properly installed.

2. All piping and insulation is complete.

3. All electrical  connections (both power and control) are

properly terminated.

4. All condensate drains are installed correctly.

5. The power supply is the right voltage and frequency. 

6. The  units  are  properly  grounded  in  accordance  with

current electrical codes.

7. Suction  and  liquid  line  service  valves  are  in  the  open

position.

System Operation Check — 

Once  the  installation

and pre-start checks are complete, perform the following steps:

1. Using  the  remote  controller,  select  cooling  or  heating

mode to check the operation of the system.

2. While the system is in operation, check the following on

the indoor unit:

a. Switches  or  buttons  on  the  remote  controller  are

easy to push.

b. Indicator light is showing normal operation and no

error is indicated.

c. Swing  mode  of  air  louvers  is  working  (if

applicable to unit).

d. Drain pump operation is normal (if applicable).

e. No abnormal vibration or noise.

3. While the system is in operation, check the following on

the outdoor unit:

a. No abnormal vibration or noise is noticed.

b. Condenser fan is in operation.

c. Indicator light is showing normal operation and no

error is indicated.

NOTE: 

If the unit is turned off or restarted, there is a time delay

of three minutes for the compressor to start from the time the

power is restored.

MAINTENANCE

EVERY 3 MONTHS:

• Check  the  air  filter  condition.  Clean  or  replace  if

necessary.

EVERY 6 MONTHS:

Follow the 3-month maintenance schedule. In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel, if applicable.

EVERY 12 MONTHS:

Follow the 6-month maintenance schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation.
• Check the heating and cooling action to confirm proper

operation.

INDOOR UNIT ADDRESSING

For  proper  system  operation,  each  indoor  unit  must  have  a

unique address set from 0 to 63. When setting an address by

remote  controller, the outdoor units, indoor units, and MDC

must be powered on. If 

FE

 is displayed on the LED screen or

display board, this unit has no address. After setting all indoor

unit addresses, turn off the power supply to all indoor units to

clear the errors.

Indoor unit addressing can be distributed automatically in the

heat pump system. When dip switch “S6” on the outdoor unit’s

main PCB board is set to 00 (default set  in factory), indoor

units are set for auto-addressing. When powering on for the

first time, it takes six minutes or more to finish auto-addressing

each indoor unit. The heat recovery system cannot accomplish

this function at this time.

IMPORTANT: The system can connect 64 indoor units,

with different system addresses. If two indoor units in the

same system have identical addresses, abnormal operation

will occur.

LEGEND
ACB

Auxiliary Control Board

FAN

Output for fan Operation

CTON

Output for Cooling Operation

HTON

Output for Heating Operation

AUXH

Output for Auxiliary Heat

MAX AMPS

1A

MAX VOLTAGE

24V

CN50

CN51

ACB interface 

FAN CTON HTON AUXH

CAUTION

When  servicing  or  repairing  this  unit,  use  only  factory-

approved  service  replacement  parts.  Refer  to  the  rating

plate on the unit  for complete unit model number, serial

number, and company address. Any substitution of parts or

controls not approved by the factory will be at the owner’s

risk and may result in equipment damage.

CAUTION

To avoid equipment damage, do not attempt to reuse any

mechanical  or  electrical  controllers  that  have  been  wet.

Replace defective controller.

Summary of Contents for 40VMU

Page 1: ...ll result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal i...

Page 2: ...ures may result in damage to equipment For information about replacement oil type and viscosity see the Installation Start Up and Service Instructions for the 38VMAH and 38VMAR outdoor units UNIT 40VM...

Page 3: ...Connect the drain hose to condensate connec tion Flexible conduit and connectors 1 Routing power lines Hanging bracket 4 Used for hanging the unit Installation guide for metallic flexible pipe 1 Mount...

Page 4: ...ns shown in inches Fig 2 40VMU012 030 Dimensions NOTE All dimensions shown in inches Fig 3 40VMU036 048 Dimensions 40VMU UNIT SIZE DIMENSION in A B C D 012 024 39 26 8 19 7 8 30 50 1 2 26 8 31 1 4 A B...

Page 5: ...SITE FOR UNIT INSTALLATION To save time and to reduce the possibility of costly errors set up a complete sample installation in a typical room at the job site Check all critical dimensions such as pip...

Page 6: ...h locknuts and washers on both sides Ensure the threaded rod does not protrude more than 1 in below the mounting hole on the hanging bracket as shown in Fig 7 Fig 7 Mounting the Hanging Bracket 3 Remo...

Page 7: ...the indoor and outdoor units If the difference between them is more than 33 ft consider mounting the outdoor unit above indoor unit Refrigerant piping connection between indoor and outdoor units shou...

Page 8: ...d cables to the unit s power terminal Be sure the power wiring and control wiring do not cross This might cause disturbance on the controls side See Fig 15 for wiring diagrams OUTSIDE DIAMETER IN RECO...

Page 9: ...iliary Heat CS Condensate Switch Optional CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor HTON Output for Heating Operation PUMP Pump...

Page 10: ...r to fix the communication wire on the outdoor unit communication terminal as shown in Fig 19 Fig 19 Connecting Communication Wire to Outdoor Unit Communication Terminal If communication wires are use...

Page 11: ...or To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit...

Page 12: ...L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resistor wired controller To...

Page 13: ...hedule In addition Clean condensate tray with suitable cleaning agent Clean the grille and panel if applicable EVERY 12 MONTHS Follow the 6 month maintenance schedule In addition Be sure all electrica...

Page 14: ...confirm and exit the setting interface Fig 27 Non Programmable Controller Setting IDU Address Programmable Controller When setting an address connect only one wired controller to an indoor unit 1 Pre...

Page 15: ...mmunication Error Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 T0 E4 Check Evaporator Temperature Sensor T2B E5 Check Evaporator Outlet Temperature Sensor T2A E6 Check...

Page 16: ...E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal...

Page 17: ...o Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard Indoor Unit...

Page 18: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 40VMU001 02 Printed in U S A Form 40VMU 2SI Pg 18 02 20 Replaces 40VMU...

Reviews: