FAN CURVE CHARACTERISTICS (CONT.)
Fig. 8 —Size 096
1. There are multiple ESP settings for each ducted unit.
2. All fan curves show examples of fan characteristics of the
MAX. ESP, RATING ESP, and MIN. ESP settings. These
curves are shown for High (H), Medium (M), and Low (S)
speeds as selected by the user at the controller.
3. All tables show air flows at H-Speed for each ESP setting.
4. ESP settings are listed in the first column of each table.
5. Select ESP setting according to connected ductwork
system.
6. Refer to Wired Controller manual for details on static
pressure settings.
INSTALLATION
Step 1 — Unpack the Inspect Units —
Units are
packaged for shipment to avoid damage during normal transit
and handling. It is the receiving party’s responsibility to inspect
the equipment upon arrival. Any obvious damage to the carton
and/or its contents should be reported on the bill of lading and a
claim should be filed with the transportation company and the
factory. The unit should always be stored in a dry place and in
the proper orientation as marked on the carton.
After determining the condition of the carton exterior, carefully
remove each unit from the carton and inspect for hidden
damage. Make sure that items such as the accessory kit,
thermostats, and controllers are accounted for whether
packaged separately or shipped at a later date. Any hidden
damage should be recorded, a claim should be filed with the
transportation company, and the factory should be notified.
If a claim for shipping damage is filed; the unit, shipping
carton, and all packing must be retained for physical inspection
by the transportation company. All units should be stored in the
factory shipping carton with internal packaging in place until
installation.
PROTECTING UNITS FROM DAMAGE — Do not apply
force or pressure to the coil, piping, or drain stub-outs during
handling. All units should be handled by the chassis or as close
as possible to the unit mounting point locations.
The unit must always be properly supported. Temporary
supports used during installation or service must be adequate to
hold the unit securely. To maintain warranty; protect units
against hostile environments (such as rain, snow, or extreme
temperature), theft, vandalism, and debris on job site.
Equipment covered in this manual is not suitable for outdoor
installations.
Do not allow foreign material to fall into the drain pan. Prevent
dust and debris from being deposited on motor, fan wheels, and
coils. Failure to do so may have serious adverse effects on unit
operation, and in the case of motor and blower assembly, may
result in immediate or premature failure. Failure of any unit
caused by deposits of foreign material on the motor or blower
wheels will not be covered by the manufacturer’s warranty.
Some units and/or job conditions may require some form of
temporary covering during construction.
ESP
Fan
Speed
Range of Available Airflow Rate in H-Speed
Max Point
Rating Point
Min Point
Max
CFM
SP
(in.)
Mid
CFM
SP
(in.)
Min
CFM
SP
(in.)
0.20
H
1488
0.15
1294
0.20
1100
0.24
0.24
0.19
0.24
0.28
0.28
0.23
0.28
0.32
0.32
0.27
0.32
0.36
0.36
0.31
0.36
0.40
0.40
0.35
0.40
0.44
0.44
0.40
0.44
0.47
0.48
0.44
0.48
0.51
0.52
0.48
0.52
0.55
0.56
0.52
0.56
0.59
0.60
0.56
0.60
0.63
0.64
0.60
0.64
0.67
0.68
0.64
0.68
0.71
0.72
0.67
0.72
0.76
0.76
0.70
0.76
0.80
0.80
0.73
0.80
0.84
0.84
0.77
0.84
0.88
0.88
0.81
0.88
0.92
0.92
0.85
0.92
0.96
0.96
0.89
0.96
1.00
1.00
0.93
1.00
1.04
LEGEND
ESP
— External Static Pressure
SP
— Static Pressure
0
0.08
0.16
0.24
0.32
0.4
0.48
0.56
0.64
0.72
0.8
0.88
0.96
1.04
1.12
800
900
1000
1100
1200
1300
1400
1500
1600
Air
Ň
ow
˄
CFM
˅
Ex
te
rn
al s
ta
Ɵ
c p
re
ssu
re
(in
W
G
)
40VMA096---3
Upper Limit of ESP (1.0 in WG)
H-Speed
Lower Limit of ESP (1.0 in WG)
M-Speed
L-Speed
Upper Limit of ESP (0.44 in WG)
Lower Limit of ESP (0.44 in WG)
Upper Limit of ESP (0.2 in WG)
Lower Limit of ESP (0.2 in WG)
H-Speed
M-Speed
L-Speed
H-Speed
M-Speed
L-Speed
CAUTION
To avoid equipment damage, do not lift unit by the drain
pipe or refrigerant piping. The unit should be lifted using
the mounting brackets.