Installation and Maintenance Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

 . . . . . . . . . . . . . . . . . . . 1

GENERAL

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

DIMENSIONS

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

FAN CURVE CHARACTERISTICS

. . . . . . . . . . . . . . . 6

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Step 1 — Unpack and Inspect Units

 . . . . . . . . . . . . 8

Step 2 — Position the Unit

 . . . . . . . . . . . . . . . . . . . . . 9

Step 3 — Mount the Unit

s. . . . . . . . . . . . . . . . . . . . . . 9

Step 4 — Connect Piping

. . . . . . . . . . . . . . . . . . . . . 10

Step 5 — Complete the Electrical Connections

 . 11

Step 6 — Installing the LED Display Panel

 . . . . . 14

Step 7 — Position and Connect Controller

 . . . . . 14

ACB INTERFACE

 . . . . . . . . . . . . . . . . . . . . . . . . . . 18

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

MAINTENANCE

 . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Fan Assembly Maintenance

 . . . . . . . . . . . . . . . . . 18

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . 23

APPENDIX A - DIP SWITCH SETTINGS

 . . . . . . . . . . 25

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service,

maintenance, or use can cause explosion, fire, electrical shock,

or other conditions that may cause death, personal injury, or

property damage. The qualified installer or agency must use

factory-authorized kits or accessories when modifying this

product.
Follow all safety codes. Wear safety glasses, protective

clothing, and work gloves. Use quenching cloth for brazing

operations. Have fire extinguisher available. Read these

instructions thoroughly and follow all warnings or cautions

included in literature and attached to the unit. Consult local

building codes and the current editions of the National

Electrical Code (NEC) ANSI/NFPA (American National

Standards Institute/National Fire Protection Association) 70. In

Canada, refer to the current editions of the Canadian Electrical

Code CSA (Canadian Standards Association) C22.1.
Understand the signal words — 

DANGER

WARNING

, and

CAUTION

DANGER

 identifies the most serious hazards,

which will result in severe personal injury or death.

WARNING

 signifies hazards that could result in personal injury

or death. 

CAUTION

 is used to identify unsafe practices, which

would result in minor personal injury or product and property

damage.
Recognize safety information. This is the safety-alert

symbol (   ). When this symbol is displayed on the unit and in

instructions or manuals, be alert to the potential for personal

injury.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation. There

may be more than one disconnect switch. Tag all

disconnect locations to alert others not to restore power

until the work is completed.

WARNING

DO NOT re-use compressor oil or any oil that has been 

exposed to the atmosphere. Dispose of oil per local codes 

and regulations. DO NOT leave the refrigerant system open 

to air any longer than the actual time required to service the 

equipment. Seal circuits being serviced and charge with dry 

nitrogen to prevent oil contamination when timely repairs 

cannot be completed. 

Failure to follow these procedures may result in damage to 

equipment. For information about replacement oil type and 

viscosity, see the Installation, Start-Up, and Service 

Instructions for the 38VMAH and 38VMAR outdoor units.

WARNING

DO NOT USE TORCH to remove any component. System

contains oil and refrigerant under pressure.

To remove a component, wear protective gloves and

goggles and proceed as follows:

A. Shut off electrical power to unit.
B. Recover refrigerant to relieve all pressure from

system using both the high-pressure and low

pressure ports.

C. Traces of vapor should be displaced with nitrogen

and the work area should be well ventilated.

Refrigerant in contact with an open flame produces

toxic gases.

D. Cut the component connection tubing with a tubing

cutter and remove the component from unit. Use a

pan to catch any oil that may come out of the lines

and as a gage for how much oil to add to the system.

E. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch

flame.

Failure to follow procedures may result in personal injury

or even death.

WARNING

When installing the equipment in a small space, provide 

adequate measures to avoid refrigerant concentration 

exceeding safety limits due to refrigerant leak.
In case of refrigerant leak during installation, ventilate the 

space immediately. Failure to follow this procedure may 

lead to personal injury.

40VMA036-096

Outside Air Unit for

Variable Refrigerant Flow (VRF) Systems

Summary of Contents for 40VMA Series

Page 1: ...ert symbol When this symbol is displayed on the unit and in instructions or manuals be alert to the potential for personal injury WARNING Electrical shock can cause personal injury and death Shut off...

Page 2: ...size Figures 2 3 and 4 show the unit s dimensions Fig 4 Fig 8 shows fan performance curves Fig 1 Model Number Nomenclature Table 1 Components Shipped with Unit LEGEND VRF Variable refrigerant Flow NAM...

Page 3: ...Low 43 8 43 4 43 9 48 5 47 7 Medium 47 8 47 8 47 8 50 0 50 8 High 49 5 50 4 51 4 52 1 53 5 UNIT Unit Dimensions W x H x D in 51 3 16 X16 1 2 X27 3 16 56 11 16 X20 X36 3 8 Packing Dimensions W x H x D...

Page 4: ...4 DIMENSIONS Fig 2 40VMA036 054 Dimensions NOTE All dimensions are shown in inches...

Page 5: ...5 DIMENSIONS CONT Fig 3 40VMA072 096 Dimensions NOTE All dimensions are shown in inches...

Page 6: ...W G Upper Lim it of ESP 0 44 in W G Upper Limit of ESP 0 2 in WG Lower Limit of ESP 0 44 in WG Lower Limit of ESP 0 2 in WG ESP Fan Speed Range of Available Airflow Rate in H Speed Max Point Rating P...

Page 7: ...in WG H Speed M Speed L Speed H Speed M Speed L Speed H Speed M Speed L Speed ESP Fan Speed Range of Available Airflow Rate in H Speed Max Point Rating Point Min Point Max CFM SP in Mid CFM SP in Min...

Page 8: ...nit mounting point locations The unit must always be properly supported Temporary supports used during installation or service must be adequate to hold the unit securely To maintain warranty protect u...

Page 9: ...t should be installed in a position that is suitable to support the total weight of the unit refrigerant piping and condensate Proper access should be provided for maintenance for refrigerant piping E...

Page 10: ...t as possible See Fig 14 Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 inch per 100 inches See Fig 15 Fig 14 Condensate Piping When multiple...

Page 11: ...damage to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other con...

Page 12: ...T2B Outlet Pipe Temperature Sensor XP1 8 Connectors XS1 4 Connector XT1 2 Terminal Block Optional Component or Field Wiring SW8 3GOT HUGXJ CN3 CN18 CN24 CN11 CN5 CN52 CN54 CN12 CN15 CN9 CN26 CN8 EARTH...

Page 13: ...XS1 4 Connector XT1 2 Terminal Block Optional Component or Field Wiring SW8 3GOT HUGXJ CN3 CN18 CN24 CN11 CN5 CN52 CN54 CN12 CN15 CN9 CN26 CN8 EARTH 7 BLUE 7 WHITE 7 7 RED Display board To wired contr...

Page 14: ...rs should be installed in a position that maintains good temperature control Position the thermostat approximately 48 inches above floor level Do not position thermostat where it can be directly affec...

Page 15: ...connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig 26 See Fig 27 and 28 for typical communication wiring of the heat pump and he...

Page 16: ...RRU 7R 6XE 0 7R RXWGRRU L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 wired controller Maximum wiring length L1 L2...

Page 17: ...0 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Maximun wiring length IW RUH 6WUDQGHG 6KLHOG IW RUH 6WUDQGHG 6KLHOG IW RUH 6WUDQGHG 6KLHOG IW RUH...

Page 18: ...ration is normal if applicable e No abnormal vibration or noise is noticed 3 While the system is in operation check the following on the outdoor unit a No abnormal vibration or noise is noticed b Cond...

Page 19: ...vides an example of the unit 1 Remove the 12 screws from the fixed Safety Drain Tray and take off the tray as shown in Fig 31 2 Take off the tray along the direction of the arrow as shown in Fig 31 3...

Page 20: ...n tray as shown in Fig 32 2 Remove all four bolts from the fan assembly as shown in Fig 33 3 Horizontally push fan assembly until it cannot not move any further 4 Lift up slightly and take down to rem...

Page 21: ...ule In addition Ensure all the electrical connections are secure Check the condensate pump operation if applicable Check the heating and cooling action to confirm proper operation INDOOR UNIT ADDRESSI...

Page 22: ...nd hold LOCK for at least ten seconds and press to query the address Programmable Controller 40VM900003 When setting an address connect only one wired controller to an indoor unit 1 Press FAN and BACK...

Page 23: ...ystem Defrost OFF Operation Light ON Only FAN dd None Heating Cooling Mode Conflict E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 E3 Check Room T...

Page 24: ...d fault Replace PC board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagneti...

Page 25: ...atalog No 20 40VMA001 01 Printed in U S A Form 40VMA 2SI Pg 25 2 20 Replaces 40VMA 1SI Carrier Corporation 2020 APPENDIX A DIP SWITCH SETTINGS There are two DIP switches on the main board Figures A an...