background image

32

SERVICE

Periodic Maintenance Checklist

Monthly 

• Inspect air filter. Replace any filters.
• Inspect drain pan and clean if necessary.

Yearly 

• Inspect and clean coils.
• Inspect fan wheels and housing for damage.

Ensure that wheels move freely by hand.

• Clean and tighten all electrical connections.

Preventing Excessive Condensation on Unit

Excessive condensation can be caused by running chilled water

through a unit with the unit fan off. If fan cycling is used, a water

flow control valve should be installed to shut off the water when

the fan stops.
Other methods of control which avoid condensation problems

are as follows:
1. If condensation is forming on the unit, verify the chilled

water valve is closing off tightly. Dirt or debris may pre-
vent the valve from closing completely.

2. Continuous fan operation with motorized chilled water

valve controlled by a thermostat.

3. Continuous fan operation with thermostat control to

switch fan from high to low speed (instead of off).

Check Drain

Check drain pan, drain line, and trap at start of each cooling sea-

son. A standard type pipe cleaner for 

3

/

4

-in. ID pipe can be used

to be sure pipe is clear of obstruction so that condensate is car-

ried away. Check the drain line at filter cleaning time during the

cooling season. Be sure that debris has not fallen into unit

through supply air grille.

Fan Motor Bearings

Standard motors are permanent split capacitor, which are

equipped with permanently sealed and lubricated bearings. No

lubrication is required unless special motors have been supplied

or unusual operating conditions exist.

Fan Shaft Ball Bearing

The mid and inboard bearings are permanently sealed and lubri-

cated. No additional maintenance is required. The end bearings

must be lubricated at the start of each cooling and heating sea-

son. Add 5 to 10 drops of SAE 20 or 30 non-detergent based oil

to the bearing.

Clean Fan Wheel

For access to fan assembly, remove discharge grille (if supplied).

If unit is connected to ductwork, remove front (40UV) or bottom

(40UH) panel, separate fan shaft from motor at bushing, remove

motor, and slide fan assembly from track. Use a stiff brush or

vacuum to remove dirt and debris from scroll. Wipe all fan sur-

faces with a damp cloth. Reassemble as necessary.

Clean or Replace Air Filters

At the start of each cooling season and after each month of oper-

ation (more or less depending on operating conditions), replace

the throwaway filter or clean the permanent filter.
THROWAWAY FILTER 
Replace filter with a good quality filter of the correct size. Do not

attempt to clean and reuse disposable filters. See Table 1 for fil-

ter sizes.
PERMANENT FILTER (FIBER TYPE)
1. Tap on solid surface to dislodge heavy particles.
2. Wash in hot water. If needed, use mild solution of com-

mercial solvent such as sal soda or trisodium phosphate.

3. Set filter on end so that water drains out through slots in

frame. Allow filter to dry thoroughly.

4. Recharge filter with recharging oil. Three ounces is suffi-

cient for a medium size filter. Oil may be applied by
insect spray gun. For easier spraying, the oil can be

warmed.

5. If the filter is dipped in the recharging oil, remove it

immediately and allow to drain through slots in frame.

6. Replace filter in unit.
If another type of filter is used, follow the filter manufacturer’s

instructions.

ECM Motor Removal and Re-installation
(see Fig. 24)

Carrier unit ventilators utilize an electronically commutated mo-

tor (ECM) to drive the indoor fan.
The ECM is a factory-programmed motor that is standard with

factory-supplied UV Open controls and units without factory-

supplied controls that are used in high-static applications or

high-capacity coils.
The ECM is programmed with an algorithm that maintains a

constant torque, as the static pressure on the system varies. For

example, as the filter pressure drop increases due to dirt, the fan

will increase speed (rpm) to maintain the cfm.
The ECM is identified by the two electrical receptacles located

on the housing. See Fig. 18-24.
The first receptacle is a 5-row in-line connector that feeds the

motor line voltage. This may be either 115 volts or 230 volts.

Units that are wired for 230 volts have a jumper between termi-

nals 1 and 2 on this plug (see wiring diagram).
The second receptacle on the motor is a 16-pin connector and is

used for speed switching. This is a low voltage (24-v) connec-

tion. There is a jumper wire between terminals 1 and 3. This is a

24-v ground. Voltage is present at all times when the motor is en-

ergized.
NOTE: A time delay exists between the time the motor speed is

switched and the motor’s reaction. This is designed into the elec-

tronics and 

does not 

indicate motor problems.

When replacing the motor, note the following:

• Check the part number of the old motor against that of

the replacement. There is a tag indicating the eight-digit

part number and begins with UVE. This is the program

number used for this motor.

CAUTION

Ensure that the unit is protected against freezing condi-

tions. If locking quadrant manual damper operator is pro-

vided, set to desired position. If damper actuator is

provided, ensure that actuator opens the damper when the

fan turns on, and closes when the fan stops.

WARNING

Lock out and tag all power supplies to equipment and con-

trols prior to servicing unit. Follow all safety codes. Failure

to do so could result in personal injury.

Summary of Contents for 40UH050

Page 1: ...ters Only trained and qualified service personnel should perform all other operations See Fig 1 for Proposition 65 warning label When installing this unit observe precautions in the literature tags an...

Page 2: ...s 2 Make sure wall behind unit is smooth and plumb if necessary install furring strips on walls with irregular surfaces or mullions Furring strips must be positioned behind mounting holes in unit Fast...

Page 3: ...Nominal Size in 2 in thick 93 4 x 361 4 93 4 x 481 4 93 4 x 601 4 93 4 x 721 4 93 4 x 721 4 Quantity 1 1 1 1 1 40UV SHIPPING WEIGHT Approx lb 165 8 in Deep Unit 330 400 480 590 660 217 8 in Deep Unit...

Page 4: ...100 1000 74 48 46 74 480 460 125 1250 86 60 61 81 590 570 150 1500 98 72 78 47 660 640 2 95 2 00 12 10 TYP W1 SEE NOTE 2 1 00 UNIT SHOWN WITH 1 00 END PANELS MOTOR ELECTRICAL BOX RECESSED RETURN AIR K...

Page 5: ...non fused disconnect switch 5 Connection hand is determined by facing dis charge of unit 27 30 30 00 19 37 2 40 13 75 7 02 1 74 PIPING TUNNEL 2 00 3 00 12 00 TYP 1 00 UNIT SHOWN WITH 1 00 END PANELS W...

Page 6: ...62 36 31 67 420 405 100 1000 74 48 46 74 500 480 125 1250 86 60 61 81 620 600 150 1500 98 72 78 47 690 670 2 00 W1 SEE NOTE 2 BOTTOM VIEW LEFT SIDE VIEW REAR VIEW W2 0 92 18 59 TYP 21 86 TYP 6 75 TYP...

Page 7: ...AL BOTTOM SERVICE PANELS SEE NOTE 3 TOP VIEW SEE NOTE 2 LEFT SIDE VIEW SIZE 200 PIPE TUNNEL 4 00 7 50 39 50 43 50 W6 UNIT 40UH AIRFLOW cfm DEPTH in DIMENSIONS in APPROXIMATE SHIPPING WEIGHT lb APPROXI...

Page 8: ...TE 3 43 50 16 63 TOP VIEW SEE NOTE 2 LEFT SIDE VIEW SIZE 200 PIPE TUNNEL 47 50 4 00 7 50 NOTES 1 All dimensions are in inches 2 Dimension does not include end panels 3 Two bottom panels provided for s...

Page 9: ...ig 10 Drain Pan Connection Holes Outside View WATER SUPPLY RETURN CONNECTIONS Install piping in accordance with all applicable codes All piping must be supported separately from coils Water supply mus...

Page 10: ...applica tions Valve packages must always be field insulated to prevent sweating See Fig 12 for piping recommendations Step 3 Make Electrical Connections Refer to unit serial plate for required supply...

Page 11: ...GEND S Supply R Return Union NOTE Factory supplied vacuum breaker assembly Field install in vertical orientation with flow arrow up and piping down so that ball seats with gravity Equalizer line and t...

Page 12: ...110 24 4 25 6 3 240 3 60 3 12 1 97 15 1 20 4 2 4 17 9 106 22 4 25 5 6 5 22 2 115 27 8 30 7 0 6 22 2 124 27 8 30 8 4 460 3 60 3 6 0 97 7 5 15 4 2 4 8 9 106 11 1 15 5 6 5 11 0 115 13 8 15 7 0 6 11 0 124...

Page 13: ...3 45 11 9 240 3 60 3 21 3 96 26 6 30 8 0 4 32 4 104 40 5 45 10 7 5 40 5 112 50 7 60 13 3 6 40 5 121 50 7 60 16 0 460 3 60 3 10 6 96 13 2 15 8 0 4 16 1 104 20 1 25 10 7 5 20 2 112 25 2 30 13 3 6 20 2...

Page 14: ...74 2 102 92 8 100 15 0 6 88 7 108 110 8 125 18 0 240 1 60 3 52 0 96 65 0 70 12 0 4 68 7 104 85 8 90 16 0 5 85 3 113 106 7 110 20 0 6 277 1 60 3 44 9 96 56 2 60 12 0 4 59 4 104 74 2 80 16 0 5 73 8 113...

Page 15: ...1 4 97 14 3 15 4 2 4 17 2 106 21 6 25 5 6 5 21 5 115 26 9 30 7 0 6 21 5 124 26 9 30 8 4 460 3 60 3 5 4 97 6 8 15 4 2 4 8 3 106 10 4 15 5 6 5 10 5 115 13 1 15 7 0 6 10 5 124 13 1 15 8 4 40UV UH075 at 7...

Page 16: ...6 27 3 30 8 0 4 33 0 104 41 2 45 10 7 5 41 1 112 51 4 60 13 3 6 41 1 121 51 4 60 16 0 460 3 60 3 10 6 96 13 3 15 8 0 4 16 2 104 20 2 25 10 7 5 20 3 112 25 3 30 13 3 6 20 3 121 25 3 30 16 0 40UV UH125...

Page 17: ...3 32 2 96 40 3 45 12 0 4 48 9 104 61 1 70 16 0 5 61 1 113 76 4 80 20 0 6 61 1 121 76 4 80 24 0 460 3 60 3 15 6 96 19 5 20 12 0 4 24 0 104 30 0 30 16 0 5 30 1 113 37 6 40 20 0 6 30 1 121 37 6 40 24 0 4...

Page 18: ...5 265 1 6 2 0 3 6 15 150 1 5 115 3 7 4 6 8 3 15 208 230 2 0 2 5 4 5 15 265 1 6 2 0 3 6 15 UNIT 40UV UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP Amps MAX FUSE SIZE Amps 050 1 3 115 1 4 1 8 3 1 15 208 230 1 3...

Page 19: ...DX COILS Select Drawing NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all u...

Page 20: ...X COILS SELECT DRAWING NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all uni...

Page 21: ...FOR HARNESS WIRING BRN 513 SELECT DRAWING GRN NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT...

Page 22: ...CONNECTED TO REMOTE COMPRESSOR CONDENSER UNIT 3 1 DX1 BLU 517 3 LLR 3 1 2 8 9 ORN 518 GRA 519 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch DX Direct Expansion F...

Page 23: ...1 4 3 2 SEE CONTROL DIAGRAM FOR HARNESS WIRING BRN 513 GRN LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch FR Fan Relay FU Fuse GND Ground PSC Permanent Split Capa...

Page 24: ...LLED ONLY ON UNITS WITH DX COILS 2 RED 503 RED 502 WHT BLK GRN LEGEND DISC Disconnect Switch DX Direct Expansion ECM Electronically Commutated Motor ESP External Static Pressure FU Fuse GND Ground LLR...

Page 25: ...K BLK 109 SEE NOTE 2 2 1 NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all u...

Page 26: ...ESS WIRING BRN 505 BRN EC1 RED 514 RED 502 RED 503 MAX LOW HIGH LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch EC Electronically Commutated ECM Electronically Com...

Page 27: ...CTED TO REMOTE COMPRESSOR CONDENSER UNIT 3 1 DX1 BLU 517 3 BRN 506 LLR 3 1 2 8 9 ORN 518 GRA 519 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch DX Direct Expansio...

Page 28: ...OTOR 11 5 BLK BRN 504 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch EC Electronically Commutated ECM Electronically Commutated Motor ESP External Static Pressure...

Page 29: ...507 RED 508 RED 508 FR Optional Field Provided and Installed Fan Relay Break wire RED 507 and connect as shown Do NOT break motor power wiring to start stop the fan motor as this will significantly d...

Page 30: ...without intended ductwork attached Ensure that units ducted to multiple openings have sufficient straight duct immediately after the unit FACTORY SETTINGS CHILLED WATER COIL APPLICATIONS Unit Speed A...

Page 31: ...older than the dew point of the surrounding air If a unit is start ed and is piped with low temperature chilled water in a hot hu mid atmosphere condensation will form on many parts of the unit In ord...

Page 32: ...posable filters See Table 1 for fil ter sizes PERMANENT FILTER FIBER TYPE 1 Tap on solid surface to dislodge heavy particles 2 Wash in hot water If needed use mild solution of com mercial solvent such...

Page 33: ...motor wire plugs are front facing on a vertical plane 10 Secure the 3 setscrews on the shaft coupling when the motor is properly positioned and the blower wheels are centered within their housing 11 R...

Page 34: ...SHROUD OPENING OVER MOTOR ELECTRICAL CONNECTIONS INSTALL MOTOR AND COOLING SHROUD ELECTRICAL CONNECTIONS FACING UNIT FRONT MOTOR SHAFT COUPLING FAN SHAFT 125 032 0 500 0 063 1 000 0 063 NOTES 1 All di...

Page 35: ...6 4 Re install two carriage bolts that attach the front brace to the frame sides See Item 6 in Fig 25 5 Rotate the fan shaft by hand to ensure that fans are unrestricted and can rotate freely Check fo...

Page 36: ...EMPERATURE SENSOR OPTIONAL OPENING DISCHARGE AIR TEMPERATURE SENSOR OPTIONAL OPENING MOTOR COUPLING SETCREW ACCESS MOTOR MOTOR ELECTRICAL BOX NOTES 1 Unit shown in vertical orientation Drawing applies...

Page 37: ...VIEW DETAIL A NOTES 1 Not all components shown for clarity 2 This drawing applies to 1500 cfm units only 3 Remove shaft motor and coupling prior to bearing removal 4 Refer to Fig 24 and 31 for motor...

Page 38: ...nto frames assembly 2 Tighten the four 5 16 in nuts retaining coil section to frame 3 Reconnect electric heat wiring in electric heat control box 4 Reconnect wiring to low limit thermostat 5 Replace t...

Page 39: ...LECTRICAL BOX MOTOR MOTOR COUPLING SETSCREW ACCESS DISCHARGE AIR TEMPERATURE SENSOR OPENING RETURN AIR TEMPERATURE SENSOR OPENING FRONT COIL BAFFLE NOTES 1 Unit shown in vertical orientation Drawing a...

Page 40: ...24 15 Ensure that motor shaft is perpendicular to motor blower endplate Tighten 5 16 in motor mount Fig 28 Item 7 Fig 29 Item 2 Fig 30 Item 2 nut Fig 28 Item 3 Fig 29 Item 5 Fig 30 Item 6 and bolt Fig...

Page 41: ...move shaft motor and coupling prior to removing bearing Refer to Removal and Re installation instructions 4 Install sleeve bearing with oil cup facing up and towards the rear of the assembly 5 Refer t...

Page 42: ...for clarity 2 Items no 7 10 and associated hardware not required for 40UV UH150 Refer to Fig 26 for 40UV UH150 in board bearing replacement 3 Install motor with capacitor facing up 4 Install sleeve b...

Page 43: ...tems no 8 11 and associated hardware not required for 40UV UH150 Refer to Fig 26 for 40UV UH150 in board bearing replacement 3 Install motor with electrical connections facing front of assembly 4 Inst...

Page 44: ...0 063 125 032 FAN SHAFT COUPLING MOTOR SHAFT FACE OF MOTOR FLUSH WITH FACE OF INSULATION MOTOR PSC BLOWER SECTION FRONT VIEW SHAFTED END FACE COUPLING INSIDE FACE COUPLING FACE MOTOR BEARING FACE NOT...

Page 45: ...em 10 Fig 30 Item 11 Attach to bearing bracket using hex nuts and bolts Align oil cup port with matching cutout in bearing bracket 9 Use 7 16 in socket to slide replacement bearing Fig 28 Item 14 Fig...

Page 46: ...PERATURE LIMIT SWITCH SEE NOTES 2 3 SEE CAUTION CAUTION DO NOT CHANGE LIMIT SWITCH CAPILLARY TUBE LOCA TION LIMIT SWITCHES MAY NOT FUNCTION PROPERLY LEGEND 1 Insulation 2 Left Blower Section End 3 Blo...

Page 47: ...motor shroud sheet metal cover Fig 28 Item 6 Fig 30 Item 4 using two 5 16 in hex nuts if using ECM motor Align window with receptacles on motor Motor control module could overheat and fail if oper at...

Page 48: ...l 4 Replace 1 4 in head screws attaching OA actuator to damper shaft OR attaching locking quadrant assembly to damper shaft Replace OA actuator or locking quadrant assembly 5 Replace the two 1 4 in he...

Page 49: ...COIL BAFFLE DISCHARGE AIR TEMPERATURE SENSOR OPENING MOTOR COUPLING SETSCREW ACCESS MOTOR MOTOR ELECTRICAL BOX COIL SECTION DAMPER SECTION BLOWER SECTION DAMPER SECTION KICKPLATE NOTES 1 Unit shown in...

Page 50: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400048 01 Printed in U S A Form 40UV UH 11SI Pg 50 8 18 Replaces 40UV U...

Page 51: ...IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED PIPING CHECKLIST IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED IS UNIT PIPING CORRECTAND INSULATED TO PREVENT CONDENSATION ARE THE C...

Page 52: ...ge at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400048 01 Printed in U S A Form 40UV UH 11SI Pg CL 2 8 18 Replaces 40UV UH 10SI Carrier Corpor...

Reviews: