background image

DCP

e

Installation – Commissioning – Maintenance

20180525

Accessories

Regulator unit:

REG. Combination unit with damper and sound attenuator.

Duct cover:

DCPT 1. For incorporation of the regulator unit and the 
connected spiral duct.

Base:

DBCT 2. For installation on the floor.

Decorative top:

DCPT 3. Removable top board in different materials and 
dimensions. Used as the termination on the top of the 
diffuser when the air diffuser is connected to the duct 
system via the floor. Please contact your nearest sales 
representative for further information.

Installation

Secure the air diffuser with screws to the floor from the 
inside of the diffuser. If a base is used, secure it with 
screws to the floor and then secure it to the bottom of 
the air diffuser with blind rivets. Press the regulator unit, 
which has a circular connection spigot with a rubber 
seal, into the inlet socket of the air diffuser. Secure the 
telescopic duct cover to the aluminium profiled section. 
Attach this section to the connected duct.  See Figure 1.  
 
If the duct casing is used for the duct connection from 
below, an assembly fixture is required between the air dif-
fuser and ceiling.As a suggestion, spiral duct of the same 
dimension as the diffuser connection can be used as the 
assembly fixture between the air diffuser and ceiling.

Commissioning

The measurement tapping is positioned on the one 
side of the air diffuser behind the aluminium strip. The 
K-factor (COP) is given on the product identification label 
on the diffuser to the side of the measurement tapping. 
K-factors can also be found in the relevant commission-
ing instructions available at www.swegon.com and in this 
product datasheet. We recommend that you use the REG 
regulator unit for adjusting the airflow. See Figure 2.
To regulate how the air is supplied to the room, turn the 
air diffuser’s Varizon

®

discs to make the air to flow in the 

desired direction. A straight air discharge can be achieved 
by taking the disc out of the diffuser, turning it 180° and 
reinserting it back into place. See Figure 3.

Maintenance

The air diffuser can be cleaned, if necessary, using luke-
warm water with dishwashing detergent added or by 
vacuum cleaning using a brush nozzle. The duct system is 
accessed by removing the front panel and the inspection 
cover of the air distribution panel. See Figure 2.

Figure 1. Installation.