MANDATORY START-UP CHECK LIST AND RECORD

Yes

No

NA

Yes

No

NA

Fan Coil Unit
Indoor Entering Air dB(Dry Bulb) Temp
Indoor Entering Air dB(Wet Bulb) Temp
Indoor Leaving Air dB(Wet Bulb) Temp
Indoor Leaving Air dB(Wet Bulb) Temp

Check mounting of interface board, are standoffs used to maintain fixed sepration above sheet metal chassis?
Check connection of power supply plug (2-circuit molex plug) on interface board, is the blue lead connected to pin1?

IMPORTANT!

This page is a mandatory checklist & record – the check to be executed and data to be recorded for future reference incase of failure.

A copy of this checklist data has to be submitted to carrier representative. Completion of this checklist is a must for any field claim, no field support will be provided for incomplete or 

blank checklists.

Is condensate line connected?
Does condensate line drain freely?

Will this damage prevent the unit start-up?

If the unit is damaged, Please specifiy where:

                   Preliminary Information

Piping

Indoor Fan Coil Unit Piping

TE

AR A

LO

NG

 T

HE

 DO

TT

ED L

INE

Have all the refrigerant connections and piping joints checked for leaks?

                                    Pre-Start-Up Checklist

Is there any shipping damage?

Has the ground wire been properly connected?
Are the circuit protection to the unit sized and installed properly?
Are the power wires to the unit sized and intalled properly?

Are refrigerant lines connected to service valve sets?
Are control power lines connected to control power terminal block?
Are terminal snug in the housing?
Are the service valves opened and backseated ?
Are the Stem Valves Installed and snug?

Check if the accurater device is installed in fan coil unit?

Outdoor Unit

Check power supply to see if it matches the unit data plate?

Are fresh batteries intalled properly in the fan coil remote controller?
Does remote controller backlight illuminate when the button is pressed?

Does fan rotate freely?

Outdoor Serial Number:

Indoor Serial Number:

Technician Name:

Additional Accessories:

Startup Date:

Indoor Model Number:

Outdoor Model Number:

Are control power lines and control cables routed separately (Not in the same conduit and not in same multi-conductor cable?
Are control wires connected to the same circuit as associated refrigerant lines?
Check to make sure the subbase mounting to wall is secure? ( Don’t apply excessive force to mounting screw)

Have refrigerant connections been checked for leak?

Controls

Units With Wireless Remote Controller

Discharge Line Temp
Entering Outdoor Air Temp
Leaving  Outdoor Air Temp

Compressor Amps(L1/L2/L3)
Oil Pressure
Vapor Line Pressure
Vapor Line Temp
Discharge Pressure

Outdoor Unit

Select cooling mode and adjust set point to be below current room temperature, Observe operation of outdoor condensing unit

De-select cooling mode at indoor fan coil unit, after atleast 15 minutes of running time and record all information below:

Select fan mode, then initiate test sequence. Does the  fan coil start at low speed , then shift to medium then to high?

Start System Operation at the Fan Coil Unit

Does compressor start (After Initial Time Delay) and Run?
Does outdoor fan run or cycle according to space requirements?

                             Start-Up Checklist

Indoor Power Supply

Check Indoor Fan Operation Under Ceiling Fan Coil Units

Fan System

Does the power supply match the fan coil unit data plate?
Is ground wire connected?

Are air filters in place?

Page 26

Summary of Contents for 40RUM Series

Page 1: ...10A Refrigerant The 40RUM Series air handling units are the best choice for packaged air handlers Model 40RUM units have direct expansion coils All models offer excellent fan performance a unique comb...

Page 2: ...ich will result in severe personal injury of death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor perso...

Page 3: ...hes and other ignition sources away from refrigerants and oils Before performing service or maintenance operations on unit always turn off main power switch to unit and install lockout tag Unit may ha...

Page 4: ...15 0 Operating Weight kg Base Unit with TXV 4 Rows 181 183 193 315 323 Plenum Fans Qty Diameter mm Nominal Airflow L s 1133 1604 1888 2360 2831 Airflow Range L s 850 1416 1203 2006 1416 2360 1770 294...

Page 5: ...illimeter mm 2 Direction of airflow 3 Recommended clearance Rear 3 0 in 76 2mm Front 2 0ft 6 0in 762mm Right Side 2 0ft 6 0in 762mm Left Side 2 0ft 6 0in 762mm 4 Liquid piping not supplied by Carrier...

Page 6: ...illimeter mm 2 Direction of airflow 3 Recommended clearance Rear 3 0 in 76 2mm Front 2 0ft 6 0in 762mm Right Side 2 0ft 6 0in 762mm Left Side 2 0ft 6 0in 762mm 4 Liquid piping not supplied by Carrier...

Page 7: ...rvice access and airflow Rear 3 ft 914 mm 21 2 ft 762 mm with electric heat accessory Front 21 2 ft 762 mm Right Side 31 2 ft 1067 mm Left Side 21 2 ft 762 mm Be sure floor wall or ceiling can support...

Page 8: ...te return air locations are shown in Typical Unit Positioning Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air loca...

Page 9: ...ostatic expansion valves TXVs distributors and nozzles for use with R 410A Knockouts are provided in the unit corner posts for 40RUM refrigerant piping See Unit Dimensional Drawing which also lists re...

Page 10: ...Radius Elbow 40RUM 14 1 Suction Lower 1 1 8 Street Elbow 1 1 8 Nipple 75 8 L 1 1 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 1 7 16 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street...

Page 11: ...alled in the condensate drain line to ensure that the static pressure of fans is balanced with the water column in the drain line and that condensate can drain completely from pan Without a trap air c...

Page 12: ...eck the unit data plate to ensure that available power supply matches electrical characteristics of the unit See Electrical Data Table for unit electrical data Install power wiring in accordance with...

Page 13: ...on losses and air noise RETURN CONNECTIONS When using return air ductwork route return air duct to the unit s return air inlet near the filter rack using a canvas connection to prevent transmission of...

Page 14: ...cement of filters Testing for cooling heating system leaks Checking of all electrical connections Most unit service can be performed by removing one or both of the unit s side panels Coil cleaning or...

Page 15: ...Press down on belt with one finger midway between fan and motor pulleys to check deflection For units with motor sizes up to and including 3 7 Hp 2 76 kW correct deflection is 3 16 in 4 8 mm For larg...

Page 16: ...o obtain desired fan speed refer to the fan motor and drive data in and adjust fan motor pulley as follows 1 Remove belt from fan motor pulley after loosening motor from motor base 2 Loosen setscrew i...

Page 17: ...ot bypass coil Cleaning Insulation The insulation contains an immobilized antimicrobial agent that helps prevent the growth of bacteria and fungi Clean the inner surface of the insulation according to...

Page 18: ...ced 3 Phase Supply Voltage 392 404 395 Average Voltage 3 Use the following formula to determine the percentage of voltage imbalance 400 3 50 Unit 40RUM 07 40RUM 08 40RUM 12 40RUM 14 40RUM 16 400 3 50...

Page 19: ...8 1 20 13 9 13 9 28 9 46 3 50 7 5 5 59 11 4 20 13 9 13 9 28 9 50 4 60 2 9 2 16 3 4 30 13 9 6 9 20 8 30 1 41 9 50 5 0 3 73 8 1 30 13 9 6 9 20 8 30 1 47 8 50 5 0 3 73 8 1 30 13 9 6 9 20 8 30 1 47 8 50...

Page 20: ...TYPICAL WIRING SCHEMATIC 40RUM Unit Size 7 16 Page 20...

Page 21: ...86 2 100 927 1 21 983 1 38 1035 1 56 1084 1 74 1131 1 92 1175 2 11 2 400 944 1 41 999 1 59 1052 1 78 1101 1 98 1149 2 18 1193 2 38 2 700 964 1 63 1018 1 82 1069 2 03 1118 2 24 1165 2 45 3 000 989 1 8...

Page 22: ...kW r s kW 850 15 16 0 78 16 08 0 89 16 94 1 01 17 74 1 13 18 51 1 26 19 25 1 39 990 15 44 0 90 16 38 1 03 17 25 1 16 18 07 1 30 18 84 1 43 19 58 1 57 1130 15 73 1 05 16 65 1 19 17 53 1 33 18 36 1 48...

Page 23: ...2350 79 65 15 3750 0 07 0 04 0 01 1750 18 10 2 5000 0 12 0 07 0 02 2350 29 17 5 6250 0 17 0 11 0 02 2950 43 26 5 4500 0 10 0 06 0 01 2100 24 14 2 6000 0 16 0 10 0 02 2800 39 24 5 7500 0 23 0 15 0 03 3...

Page 24: ...line filter driers with rated working pressures less than 600 psig Do not leave R 410A refrigerant suction line filter driers in line longer than 72 hours Do not install a suction line filter drier in...

Page 25: ...e leak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Dirty drier filter Replace filter Dirty co...

Page 26: ...heck if the accurater device is installed in fan coil unit Outdoor Unit Check power supply to see if it matches the unit data plate Are fresh batteries intalled properly in the fan coil remote control...

Page 27: ...NOTES Page 27...

Page 28: ...rights to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version N A Catalog Number 40RUM IOM 50Hz V1 Effective Date 13 01...

Reviews: