Evaporator Anti-Freezing Protection

The evaporator anti-freezing protection condenser high temperature 
protection and outdoor unit frequency limit are active and the same as 
that in the 

COOLING

 mode.

Outdoor Fan

The outdoor fan operates the same as in the 

COOLING

 mode.

Forced OPERATION Function

When the air conditioner is off, press 

TOUCH

 to engage the 

Forced

 

AUTO

 mode. Press 

TOUCH

 again within 5 seconds to engage the 

Forced

 COOLING

 mode. In the 

Forced 

AUTO

Forced

 

COOLING

 or any other operation mode, press 

TOUCH

 to turn off the 

air conditioner.

Forced OPERATION Mode

In the 

Forced

 OPERATION

 mode, all the general protections and the 

remote controller are available.

Operation Rules

Forced COOLING Mode

The compressor runs at the F2 frequency and the indoor fan runs in the 

BREEZE

 mode. After running for 30 minutes. the air conditioner

enters the 

AUTO

 mode at the 75.2

F(24

C) setting temperature.

Forced AUTO Mode:

The 

Forced

 AUTO

 mode is the same as the normal 

AUTO 

mode with a 

75.2

F(24

C) setting temperature.

Forced DEFROSTING Mode:

1. Press and hold 

AUTO/COOL

 for 5s to enter the mode. The indoor 

fan stops and the defrosting lamp         illuminates. Use the remote 
controller to exit this mode and turn off the air conditioner to stop the 
normal 

DEFROSTING

 mode.

2. To exit the 

Forced

 DEFROSTING

 mode, press and hold 

AUTO/

COOL

 for 5s again.

AUTO-RESTART Function

The indoor unit is equipped with the 

AUTO-RESTART

 function,

which is carried out through an auto-restart module. In the event of a 
sudden power failure, the module memorizes the setting conditions prior 
to the power failure. The air conditioner resumes the previous operation 
setting (not including the 

SWING

 function) automatically three (3) 

minutes after the power returns.

If the memorization condition is the 

Forced

 COOLING 

mode, the air 

conditioner runs in the 

COOLING 

mode for 30 minutes and turns to the 

AUTO 

mode at the 75.2

F(24

C) setting temperature. If the air 

conditioner is off before the power turns off and the air conditioner is 
required to start up, the compressor delays start-up for 1 minute before 
powering on. In other instances, the compressor waits three (3) minutes 
before restarts.

Refrigerant Leakage Detection

With this new technology, the display area displays 

“EC”

 when the

outdoor unit detects a refrigerant leak. This function is only active in the 

COOLING

 mode. The function can further prevent the compressor 

from being damaged by a refrigerant leak or a compressor overload.

Open Condition: 

When the compressor is active, the value of the 

coil temperature of evaporator T2 experiences no to very little 
change.

Louver Position Memory Function

When starting the air conditioner again after a shut down, the louver 
returns to the angle originally set by the user, however the precondition 
is that the angle must be within the allowable range. If the louver 
exceeds the allowable range, the air conditioner memorizes the 
maximum angle of the louver. During operation, if the power fails or the 
end user shuts down the air conditioner in the 

TURBO 

mode, the louver 

returns to the default angle.

46

F (8

C) Heating

When the compressor is running, the indoor fan motor runs without the 

ANTI

COLD 

air function. When the compressor is  off, the indoor fan 

motor is off.

Silence Operation

Press 

SILENCE

 on the remote controller to initiate the 

SILENCE 

function. When 

SILENCE

 is activated, the compressor running 

frequency remains lower than 

F2

 and the indoor unit emits a faint 

breeze, which reduces the noise to the lowest level and creates a quiet 
and comfortable room for the user.

Point Check Function

Press the remote controller’s 

LED DISPLAY 

or 

LED 

or 

MUTE

button three times, and then press 

AIR DIRECTION 

or 

SWING

 three 

times within ten seconds. The buzzer rings for two seconds. The air 
conditioner enters the 

INFORMATION ENQUIRY

 status.

Press 

LED DISPLAY 

or 

AIR DIRECTION

 to check the next or front 

item’s information. When the air conditioner enters the 

INFORMATION ENQUIRY

 status, it displays the code name in 2 

seconds (see Table 8 on page 14).

Summary of Contents for 40MAHBQ06XA

Page 1: ...ol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify...

Page 2: ...MA H B Q 36 A 3 40 INDOOR UNIT MA MODEL VOLTAGE 1 115 1 60 3 208 230 1 60 INDOOR UNIT FAN COIL UNIT TYPE H HIGH WALL INDOOR FAN COIL TYPE Q HEAT PUMP NOMINAL CAPACITY 06 1 2 TON 09 3 4 TON 12 1 TON 18...

Page 3: ...Piping Pipe Connection Size Liquid in mm 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 3 8 9 52 3 8 9 52 3 8 9 52 Pipe Connection Size Suction in mm 1 2 12 7 3 8 9 52 3 8 9 52 1 2 12 7 1 2 12 7 5 8 16...

Page 4: ...8 230V 208 230V 208 230V 208 230V 208 230V 208 230V Height H in mm 11 61 295 11 61 295 11 61 295 11 61 295 12 56 319 14 57 370 14 57 370 14 57 370 Width W in mm 31 3 795 31 3 795 31 3 795 31 3 795 37...

Page 5: ...or 208 230 volt connection If installed in a high electromagnetic field area EMF and communication issues exist a 14 2 stranded shielded wire can be used to replace 2 and 3 polarity sensitive between...

Page 6: ...Fig 3 Connection Diagram 12K 115V Fig 4 Connection Diagram 6K 18K 208 230 1 60 Fig 5 Connection Diagram 24K 36K 208 230 1 60 NOTES 1 Do not use thermostat wire for any connection between indoor and o...

Page 7: ...0 130V AC input CN16 S connect to indoor unit CN60 Connect to 4 way valve 100 130V AC when is on CN17 Connect to compressor heater 100 130V when AC is on CN 15 Connect to chassis heater 100 130V AC wh...

Page 8: ...s 8 REFRIGERATION CYCLE DIAGRAM Fig 7 Refrigeration Cycle Diagram REFRIGERANT LINES IMPORTANT Both refrigerant lines must be insulated separately Table 2 on page 3 lists the pipe sizes for the indoor...

Page 9: ...ZKFP 58 8 1 6 Volts V 115 208 230 208 230 208 230 208 230 208 230 208 230 208 230 Phase 1 1 1 1 1 1 1 1 FLA 0 2 0 25 0 25 0 25 0 13 0 5 0 5 0 5 MCA 0 25 0 31 0 31 0 31 0 16 0 63 0 63 0 63 Type DC Ins...

Page 10: ...ethod is the most effective way of assuring a system is free of air and liquid water see Fig 10 Fig 10 Deep Vacuum Graph Triple Evacuation Method Refer to Fig 11 and proceed as follows 1 Pump the syst...

Page 11: ...disconnection If only one temperature sensor malfunctions the air conditioner continues to work however the error code appears on the LED in the event of any emergency use If more than one temperature...

Page 12: ...the indoor unit defrost lamp illuminates and appears Evaporator Coil Temperature Protection Fig 17 Evaporator Coil Temperature Protection When the evaporator temperature is higher than the setting pr...

Page 13: ...e for 30 minutes and turns to the AUTO mode at the 75 2 F 24 C setting temperature If the air conditioner is off before the power turns off and the air conditioner is required to start up the compress...

Page 14: ...Frequency Actual Frequency 1F 1E 1d 1c 1b 1A 25 24 23 22 21 20 1 The displaying temperature is the actual value 2 The temperature is C no matter what kind of remote controller is used 3 T1 T2 T3 T4 T...

Page 15: ...ply is shut off NOTE Remember to discharge the electricity power in capacitor Fig 19 Electrolytic Capacitors For other models please connect discharge resistance approximately 100 40W or a soldering i...

Page 16: ...odel dependent nF Filter replacement reminder FP Heating in room temperature under 8 C FC Forced cooling AP AP mode of WIFI connection CP Remote switched off LL Remote or Wire controller Lock On Time...

Page 17: ...n chip does not receive feedback from the EEPROM chip Possible Causes Installation error PCB faulty Troubleshooting EEPROM A read only memory whose contents can be erased and reprogrammed using a puls...

Page 18: ...ontinuously Possible Causes Wiring error Indoor or outdoor PCB faulty Troubleshooting Measure Vs Is it a positive fluctuation Vs represents the voltage S and N of the outdoor unit Red pan S Black pan...

Page 19: ...2 terminal while the black pin connects to the 3 terminal When the air conditioner is running normal the voltage moves alternately between approximately 50V to 50V If the outdoor unit malfunctions the...

Page 20: ...olution E2 Malfunction Decision Conditions When the PCB does not receive a zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal Possible Causes Connection...

Page 21: ...300RPM for a certain time the air conditioner stops and the LED displays the failure Possible Causes Wiring mistake Fan assembly faulty Fan motor faulty PCB faulty Troubleshooting Power off then rest...

Page 22: ...ir conditioner to ensure the fan runs normally If the fan runs normally the PCB has an issue and needs to be replaced If the fan does not run normally measure the resistance of each two pins If the re...

Page 23: ...olution E4 E5 F1 F2 F3 Malfunction Decision Conditions If the sampling voltage is lower than 0 06V or higher than 4 94V the LED displays the failure Possible Causes Wiring mistake Sensor faulty PCB fa...

Page 24: ...r the compressor starts if T2 Tcool 35 6 F Tcool 2 C does not run for 4 seconds and this situation occurs three times the display area displays EC and the air conditioner turns off Possible Causes Sys...

Page 25: ...d by checking the specified current detection circuit Possible Causes Power supply problems System blockage PCB faulty Wiring mistake Compressor malfunction Troubleshooting Check the power supply Chec...

Page 26: ...LED displays P0 and the air conditioner powers off Possible Causes Wiring mistake IPM malfunction Outdoor fan assembly faulty Compressor malfunction Outdoor PCB faulty Troubleshooting Check the wiring...

Page 27: ...SG 40MAHB 01 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 27 DIAGNOSIS AND SOLUTION CONT Fig 27 P U Fig 28 P V...

Page 28: ...SG 40MAHB 01 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 28 DIAGNOSIS AND SOLUTION CONT Fig 29 P W Fig 30 N U...

Page 29: ...SG 40MAHB 01 Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 29 DIAGNOSIS AND SOLUTION CONT Fig 31 N V Fig 32 N W...

Page 30: ...detected by checking the specified voltage detection circuit Possible Causes Power supply problems System leak or blockage PCB faulty Troubleshooting Fig 33 Test NOTE Measure the DC voltage between t...

Page 31: ...ssible Causes Power supply problems System leak or blockage PCB faulty Troubleshooting Check the air flow system of the indoor and outdoor units Clear up the air inlet and outlet or the heat exchanger...

Page 32: ...detection and compressor rotation speed signal detection Possible Causes Wiring mistake IPM malfunction Outdoor fan assembly faulty Compressor malfunction Outdoor PCB faulty Troubleshooting Check the...

Page 33: ...eck Temperature Sensor Checking Disconnect the temperature sensor from the PCB Measure the resistance value with a tester Fig 34 Tester Temperature sensors Room temp T1 sensor Indoor coil temp T2 sens...

Page 34: ...44 36 97 6 13059 76 169 1 34105 116 241 0 4006 3 27 41 5878 37 99 5 87359 77 171 1 29078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174...

Page 35: ...93 37 3 74 165 8 358 114 237 2 489 5 23 234 9 35 95 35 78 75 167 8 084 115 239 2 422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 1...

Page 36: ...1 6 2 5 36 5 30 86 61 141 8 92 197 6 123 253 4 3 37 4 31 87 8 62 143 6 93 199 4 124 255 2 3 5 38 3 32 89 6 63 145 4 94 201 2 125 257 4 39 2 33 91 4 64 147 2 95 203 126 258 8 4 5 40 1 34 93 2 65 149 96...

Page 37: ...part is for reference only and the photos may differ from your actual unit Procedure Illustration 1 Place your hands along the lter ssides pull the lter gently along the vertical direction and then re...

Page 38: ...ime specifications and designs without notice and without obligations 38 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 4 Open the panel assembly move the slider to secure the panel 5 Open the t...

Page 39: ...Pull the two sides of the bottom panel along the direction shown in the image to the right to remove it 8 Pull the panel s support bar to remove it 9 Remove the panel assembly Caution If you want to c...

Page 40: ...ons and designs without notice and without obligations 40 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 10 Remove 1 screw from the display board 11 Rotate the display board subassembly in the d...

Page 41: ...notice and without obligations 41 DISASSEMBLY INSTRUCTIONS CONT Electrical parts Anti static gloves must be worn Procedure Illustration 1 Pull the two ends of the electronic control box cover with yo...

Page 42: ...llustration 4 Disconnect the wires 5 Remove one screw used for the ground connection 6 Pull two clips of the electronic control box along the direction shown in the picture to the right to remove the...

Page 43: ...igations 43 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 7 Remove the other screw used for the ground connection 8 Collapse the support bar 9 Pull the electronic control box cover along the di...

Page 44: ...cifications and designs without notice and without obligations 44 DISASSEMBLY INSTRUCTIONS CONT Evaporator NOTE Remove the front panel electrical parts and the fan Procedure Illustration 1 Remove the...

Page 45: ...and without obligations 45 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 3 Remove the screw 1 on the evaporator located at the left xed plate 4 Remove the screw 1 on the evaporator located on t...

Page 46: ...ice and without obligations 46 DISASSEMBLY INSTRUCTIONS CONT Fan Motor and Fan Procedure Illustration 1 Open the two stop blocks of the chassis assembly see picture on the right 2 Remove the chassis a...

Page 47: ...ight to change at any time specifications and designs without notice and without obligations 47 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 4 Remove the bearing sleeve 5 Remove the screw 6 Pu...

Page 48: ...rved A Carrier company Edition Date 05 21 Catalog No SG 40MAHB 01 Replaces NEW SG 40MAHB 01 Service Manual Manufacturer reserves the right to change at any time specifications and designs without noti...

Reviews: