No, Description
Setting
Unit
Display conditions
Access
level
Enumeration
By default
168 Heating or cooling change authorisation time
delay
1
min
2
170 Temperature setpoint 1 in cooling mode
25,0
°C
1
171 Temperature setpoint 2 in cooling mode
30,0
°C
P160 Setpoint 1/setpoint 2 selection
= time sched/CMS or ON/OFF input
or on/off override
and
P161 Application of setpoint 1/
setpoint 2 selection = temperature
or tempe ventilation
1
172
Temperature control PID proportional band
(P)
in cooling mode
5,0
°C
2
173 Temperature control PID integral time (I) in
cooling mode
150
s
2
174 Temperature control PID derivative time (D)
in cooling mode
0
s
2
180 Temperature setpoint 1 in heating mode
23,0
°C
1
181 Temperature setpoint 2 in heating mode
18,0
°C
P160 Setpoint 1/setpoint 2 selection
= time sched/CMS or ON/OFF input
or on/off override
and
P161 Application of setpoint 1/
setpoint 2 selection = temperature
or tempe ventilation
1
182
Temperature control PID proportional band
(P)
in heating mode
5,0
°C
2
183 Temperature control PID integral time (I) in
heating mode
150
s
2
184 Temperature control PID derivative time (D)
in heating mode
0
s
2
206
Free cooling and night cooling operating
differential compared to the controlled
temperature
3,0
°C
P150 Free cooling control = With
or
P151 Night cooling control = With
2
207 Temperature low limit for free cooling and
night cooling
15,0
°C
P150 Free cooling control = With
or
P151 Night cooling control = With
2
208 Mixing damper minimum setpoint 1
80
%
P27 Mixing damper = With
2
209 Mixing damper minimum setpoint 2
80
%
P27 Mixing damper = With
and
P160 Setpoint 1/setpoint 2 selection
= time sched/CMS or on/off input or
on/off override
and
P161 Application of setpoint 1/
setpoint 2 selection = ventilation or
tempe ventilation
2
210 Control setpoint in night cooling mode
17,0
°C
P151 Night cooling control = With
1
212
Air intake fan flow rate setpoint in night
cooling mode
P110
m
3
/h
Night cooling control = With
and
P104 Intake ventilation control
=Flow rate
2
213
Air extraction fan flow rate setpoint in night
cooling mode
P110
m
3
/h
Night cooling control = With
and
P104 Intake ventilation control
=Flow rate
2
214 Intake fan pressure setpoint in night cooling
mode
200
Pa
P151 Night cooling control = With
and
P104 Intake ventilation control =
Pressure
2
215 Exhaust fan pressure setpoint in night cooling
mode
200
Pa
P151 Night cooling control = With
and
P104 Intake ventilation control =
Pressure
and
P105 Exhaust ventilation control =
duct pressure
2
216 Air quality setpoint
800
ppm
P152 Air quality control = With
2
217 Air quality proportional band
100
ppm
P152 Air quality control = With
2
218
Air flow max setpoint on intake for air quality
P110
m
3
/h
P152 Air quality control = With
and
P104 Air intake ventilation control =
Flow rate
2
219
Air flow max setpoint on exhaust for air
quality
P110
m
3
/h
P152 Air quality control = With
and
P104 Air intake ventilation control =
Flow rate
2
8 - PARAMETERS
53