background image

providing electrical potential to second heater sequencer (if used).
If outdoor temperature falls below setting of outdoor thermostat
(field-installed option), contacts close to complete circuit and bring
on second bank of supplemental electric heat.

When thermostat is satisfied, its contacts open, de-energizing
contactor and sequencer. All heaters and motors should stop.

Quiet Shift

Quiet Shift is a field-selectable defrost mode, which will eliminate
occasional noise that could be heard at the start of the defrost cycle
and restarting of heating cycle. It is selected by placing DIP switch
3 (on defrost board) in ON position.

When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Revers-
ing valve will energize, compressor will turn off for 30 sec, then
turn back on to complete defrost. At the start of heating cycle after
conclusion of defrost mode, reversing valve will de-energize, the
compressor will turn off for another 30 sec, and the fan will turn
off for 40 sec, before starting in the heating mode.

Defrost

The defrost control is a time/temperature control which includes a
field-selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at
90 minutes).

To initiate a forced defrost, two options are available depending on
the status of the defrost thermostat.

If defrost thermostat is closed, speedup pins (J1) must be shorted
by placing a flat head screwdriver in between for 5 sec and
releasing, to observe a complete defrost cycle. When the Quiet
Shift switch is selected, compressor will be turned off for two 30
sec intervals during this complete defrost cycle as explained
previously. When Quiet Shift switch is in factory default OFF
position, a normal and complete defrost cycle will be observed.

If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screwdriver) for 5 sec and released, a
short defrost cycle will be observed (actual length is dependent
upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 sec
compressor off period followed by 30 sec of defrost with com-
pressor operation). On return to heating operation, compressor will
again turn off for an additional 30 sec and the fan for 40 sec. When
the Quiet Shift is in OFF position, only a brief 30 sec cycle will be
observed.

If it is desirable to observe a complete defrost in warmer weather,
the thermostat must be closed as follows:

1. Turn off power to outdoor unit.

2. Disconnect outdoor fan motor lead from OF2 on control board

(See Fig. 15.) Tape to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate on

outdoor coil.

4. After a few minutes in heating mode, liquid line temperature

should drop below closing point of defrost thermostat (ap-
proximately 30°F).

NOTE:

Unit will remain in defrost until defrost thermostat

reopens at approximately 80°F coil temperature at liquid line or
remainder of defrost cycle time.

5. Turn off power to outdoor and reconnect fan motor lead to

OF2 on control board after above forced defrost cycle.

Step 13—Check Charge

Factory charge is shown on unit rating plate. To check charge in
cooling mode, refer to Cooling Mode Procedure. To check charge
in heating mode, refer to For Heating Only Procedure.

COOLING ONLY PROCEDURE

NOTE:

If subcooling charging conditions are not favorable,

charge must be weighed in accordance with unit rating plate

±

0.6

oz/ft of 3/8-in. liquid line above or below 15 ft respectively.

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

Units installed with cooling mode TXV require charging with the
subcooling method.

1. Operate unit a minimum of 10 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accurate

gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid line near
outdoor coil.

4. Refer to unit rating plate for required subcooling temperature.

5. Refer to Table 3. Find the point where required subcooling

temperature intersects measured liquid service valve pressure.

6. To obtain required subcooling temperature at a specific liquid

line pressure, add refrigerant if liquid line temperature is
higher than indicated or reclaim refrigerant if temperature is
lower. Allow a tolerance of

±

3°F.

HEATING ONLY PROCEDURE

1. Defrost unit before checking charge. Outdoor coil must be free

of frost and/or ice.

1. Accumulator may momentarily hold refrigerant after defrost

cycle, therefore, allow 15 min. of normal operation following
defrost cycle before checking charge.

2. This outdoor unit is equipped with a thermal expansion

device, therefore the subcooling chart (See Table 4) may be
used for checking purposes only.

OF2

CESO130076–00

OF1

ON

Q

UIET

SHIFT

120

30

60

60

30

90

INTER

V

AL  

TIMER

OFF

P3

DFT

O   R   

W

2

   

Y   C

T2 C  C  O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A99442

Fig. 14−Defrost Control

11

Summary of Contents for 38YSA

Page 1: ...nal injury or death INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows p...

Page 2: ...irflow a 6 in clearance on 1 side of unit and 12 in on all remaining sides must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall di...

Page 3: ...it Step 8 Make Piping Connections Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death Use all service ports and open all flow con...

Page 4: ...oltage See unit rating plate for recommended circuit protection device NOTE Operation of unit on improper line voltage constitutes abuse and could affect unit reliability See unit rating plate Do not...

Page 5: ...asses protective clothing and gloves when handling refrigerant and observe the following Back seating service valves are not equipped with Schrader valves Fully back seat counter clockwise valve stem...

Page 6: ...A FB FC FD FF FH FAN COIL HEAT PUMP G Y1 W2 L R O INDOOR FAN HEAT STAGE 2 COOL HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C IF AVAILABLE A98629 24 VAC HOT...

Page 7: ...W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA FB FC FD FF FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE A98630 24 VAC...

Page 8: ...VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A98631 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S 40FKA FK4C FAN COI...

Page 9: ...VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2...

Page 10: ...UMPER WIRE BETWEEN O W2 AND L THERMOSTAT TERMI NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL LEGEND 24 V FACTORY WIRI...

Page 11: ...observe a complete defrost in warmer weather the thermostat must be closed as follows 1 Turn off power to outdoor unit 2 Disconnect outdoor fan motor lead from OF2 on control board See Fig 15 Tape to...

Page 12: ...ature F LIQUID PRESSURE AT SERVICE VALVE PSIG REQUIRED SUBCOOLING TEMPERATURE F 5 10 15 20 134 71 66 61 56 141 74 69 64 59 148 77 72 67 62 156 80 75 70 65 163 83 78 73 68 171 86 81 76 71 179 89 84 79...

Reviews: