37
Heat pump heating performance continued
Multipliers for Determining the Performance With Other Indoor Sections
* The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
† The kw values include the compressor, outdoor fan motor, and indoor blower motor. The kw from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB—Entering Dry Bulb
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55
°
F (12.8
°
C).
3. Maximum outdoor operating air temperature for cooling mode is 125
°
F (51.7
°
C).
4. Minimum outdoor operating air temperature for heating mode is –30
°
F (–34.4
°
C).
5. Maximum outdoor operating air temperature for heating mode is 66
°
F (18.9
°
C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft/indoor coil below = 150 ft (see items 8 and 9 following).
8. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.
9. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical rise to the valve
connections at the unit.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mixmatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°
F
–3
7
17
27
37
47
57
EDB
CFM
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Capacity
(MBtuh)
Total
Power
Total
Int*
Kw†
Total
Int*
Kw†
Total
Int*
Kw†
Total
Int*
Kw†
Total
Int*
Kw†
Total
Int*
Kw†
Total
Int*
Kw†
38YRA060-30 Outdoor Section With FK4CNB006 Indoor Section
65
1575
28.0
25.8
3.81
33.2
30.6
4.02
39.1
35.6
4.24
45.3
40.3
4.4
52.8
48.0
4.81
61.2
61.2
5.20
71.0
71.0
5.73
1750
28.3
26.0
3.82
33.5
30.8
4.01
39.4
35.9
4.22
45.7
40.5
4.4
53.2
48.4
4.76
61.7
61.7
5.14
71.7
71.7
5.65
2012
28.6
26.3
3.84
33.9
31.1
4.02
39.7
36.2
4.21
46.1
40.9
4.4
53.7
48.9
4.72
62.3
62.3
5.09
72.0
72.0
5.52
70
1575
27.7
25.5
3.98
32.9
30.3
4.21
38.7
35.3
4.45
44.9
39.8
4.7
52.1
47.5
5.05
60.5
60.5
5.45
70.2
70.2
5.99
1750
28.0
25.7
3.99
33.2
30.5
4.20
39.0
35.6
4.43
45.2
40.1
4.6
52.6
47.8
4.99
61.0
61.0
5.38
71.6
71.6
5.91
2012
28.3
26.0
4.02
33.5
30.8
4.21
39.4
35.9
4.42
45.6
40.5
4.6
53.1
48.3
4.95
61.6
61.6
5.32
71.5
71.5
5.84
75
1575
27.4
25.2
4.16
32.6
30.0
4.41
38.3
35.0
4.67
44.4
39.4
4.9
51.6
47.0
5.29
59.8
59.8
5.72
69.3
69.3
6.27
1750
27.6
25.4
4.16
32.9
30.2
4.40
38.6
35.2
4.64
44.7
39.7
4.9
52.0
47.3
5.23
60.3
60.3
5.64
70.0
70.0
6.17
2012
28.0
25.7
4.19
33.2
30.5
4.41
39.0
35.6
4.63
45.2
40.1
4.8
52.5
47.8
5.18
60.9
60.9
5.57
70.7
70.7
6.10
Indoor
Section
Size
Heating
Indoor
Section
Size
Heating
Capacity
Power
Capacity
Power
F(A,B)4AN(F,B,C)
060
1.00
1.09
CD3(A,B)A
060
1.00
1.19
FB4ANB
070
1.00
1.03
COILS + 58U(H,X)V100-20 VARIABLE-SPEED FURNACE
FC4BN(F,B)
060
1.00
1.09
CC5A/CD5A/CD5BA
060
1.00
1.17
FC4BNB
070
1.00
1.03
CC5A/CD5A/CD5BW
060
1.00
1.10
FG3AAA
060
1.00
1.13
CD3(A,B)A
060
1.00
1.17
FK4BNB
006
1.00
1.01
CE3AA
060
1.00
1.10
FK4CNB
006
1.00
1.00
CJ5A/CK5A/CK5BA
060
1.00
1.12
CC5A/CD5A/CD5BA
060
1.00
1.18
CJ5A/CK5A/CK5BX
060
1.00
1.06
CC5A/CD5A/CD5BW
060
1.00
1.11
CK3BA
060
1.00
1.12
CD3(A,B)A
060
1.00
1.18
COILS + 58U(H,X)V120-20 VARIABLE-SPEED FURNACE
CE3AA
060
1.00
1.11
CC5A/CD5A/CD5BA
060
1.00
1.19
CJ5A/CK5A/CK5BA
060
1.00
1.12
CC5A/CD5A/CD5BW
060
1.00
1.10
CJ5A/CK5A/CK5BN
060
1.00
1.12
CD3(A,B)A
060
1.00
1.19
CJ5A/CK5A/CK5BX
060
1.00
1.07
CE3AA
060
1.00
1.11
CK3BA
060
1.00
1.12
CJ5A/CK5A/CK5BA
060
1.00
1.11
COILS + 58MVP100-20 VARIABLE-SPEED FURNACE
CJ5A/CK5A/CK5BX
060
1.00
1.06
CC5A/CD5A/CD5BA
060
1.00
1.19
CK3BA
060
1.00
1.11
CC5A/CD5A/CD5BW
060
1.00
1.11
—
—
—
Summary of Contents for 38YRA