background image

 

6

 

Accessory description and usage (continued)

 

10. Liquid-LIne Solenoid Valve (LSV)

 

An electrically operated shutoff valve to be installed at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor 
operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

 

NOTE:

 

 Compressor Start Assist — Capacitor and Relay must be used also on reciprocating compressors.

SUGGESTED USE:  For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

In certain long-line applications. Refer to the Residential Split-System Long-Line Application Guideline.

 

11. Low-Ambient Pressure Switch

 

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure within normal
operating limits (approximately 100 psig to 225 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F when properly installed.

SUGGESTED USE:  Cooling operation at outdoor temperatures below 55°F (12.8°C).

 

12. MotorMaster® Control

 

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during
operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F.

SUGGESTED USE:  Cooling operation at outdoor temperatures below 55°F.

All commercial installations.

 

13. Outdoor Air Temperature Sensor

 

A device that allows the temperature at a remote location (outdoors) to be displayed on the thermostat.

SUGGESTED USE:  All Carrier programmable thermostats.

 

14. Outdoor Thermostat

 

An SPDT temperature-actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.

SUGGESTED USE:  Heat pump installations with multiple-stage supplemental heaters.

 

15. Secondary Outdoor Thermostat

 

An SPDT temperature actuated switch which turns on third-stage of supplemental electric heaters when outdoor air temperature drops below the second-stage set point.

SUGGESTED USE:  Heat pump installations where 3-stage operation of supplemental heaters is desired.

 

16. Sound Hood

 

Wraparound sound reducing cover for the compressor. Reduces the sound level by about 2 dBA.

SUGGESTED USE:  Unit installed closer than 15 ft to quiet areas—bedrooms, etc. 

Unit installed between 2 houses less than 10 ft apart.

 

17. Thermostatic Expansion Valve (TXV) Bi-Flow

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available. Do not use hard shutoff TXV with Liquid-Line Solenoid
Valve. Hard shutoff TXV requires Compressor Start Assist — Capacitor and Relay on units with single-phase reciprocating compressors.

SUGGESTED USE:  For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

18. Time-Delay Relay

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE:  For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

SOUND POWER (A-weighted, non-pure tone corrected.)

NOTE:

 Tested in accordance with ARI standard 270.95. (Not listed with ARI.)

UNIT SIZE

SOUND LEVEL

(dBA)

OCTAVE BAND CENTER FREQUENCY (Hz)

125

250

500

1000

2000

4000

8000

018

78

49.5

58.0

66.5

69.5

67.0

66.5

59.5

024

78

50.5

59.0

64.5

68.0

67.5

67.5

61.5

030

80

57.5

64.5

68.5

72.5

72.5

70.0

64.0

036

81

60.5

67.5

73.0

76.0

73.0

69.5

63.5

042

80

59.0

65.0

70.5

75.5

72.0

69.5

64.0

048

80

54.5

63.5

69.5

75.0

71.0

70.0

67.5

060

80

56.0

64.5

73.0

74.5

71.0

71.0

63.0

Summary of Contents for 38YCG Series

Page 1: ...son All models are listed with UL U S and Canada CEC and ARI FEATURES Electrical Range All sizes of the 38YCG are offered in single phase 208 230v Size Range The 38YCG is available in 7 nominal sizes...

Page 2: ...ection while not restricting airflow and maintaining ease of coil inspection and cleaning Unit Design All units are equipped with totally enclosed fan motors for greater reliability under adverse weat...

Page 3: ...ty CFM Motor HP Motor RPM 60 Hz Propeller Type Direct Drive Vertical 1900 1900 2300 3000 3000 3300 3300 1 12 1 12 1 4 1 4 1 4 1 4 1 4 1100 1125 1125 1100 1100 1100 1100 CONDENSER COIL Face Area Sq Ft...

Page 4: ...Sound Hood Size 060 34 KHAOT0301FST Outdoor Thermostat All Sizes KHAOT0201SEC Secondary Outdoor Thermostat All Sizes KSATX0601HSO TXV Hard Shutoff Size 018 042 KSATX0701HSO TXV Hard Shutoff Size 048...

Page 5: ...ol provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason including normal room thermostat cycling SUGGESTED USE Installations in areas where power in...

Page 6: ...ations with multiple stage supplemental heaters 15 Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on third stage of supplemental electric heaters when outdoor air tempera...

Page 7: ...tors compressors contain internal overload protection FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps OUTDOOR UNIT V PH 60 Hz OPERATING VOLTS COMPRESSOR FAN FLA M...

Page 8: ...22 1 2 030 33 22 1 2 33 15 16 3 3 16 3 4 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 12 1 2 12 14 22 1 2 X 22 1 2 036 33 34 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16...

Page 9: ...50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 38YCG01832 F A B 4BNF018 38YCG02432 F A B 4BNF024 38YCG03033 F A B 4BNF030...

Page 10: ...0 22 800 TDR TXV 10 00 8 80 22 800 3 22 14 000 2 30 7 0 FF1DNA024 22 000 TDR 10 00 9 05 22 800 3 18 14 100 2 28 7 0 FF1DNA030 23 000 TDR 10 00 9 05 22 800 3 24 14 200 2 30 7 0 FK4 C D NF001 23 000 TDR...

Page 11: ...4 000 3 28 20 000 2 38 7 4 CK3BA042 34 800 TDR 11 20 10 20 34 000 3 30 20 000 2 40 7 4 CK5A CK5BA042 34 800 TDR 11 20 10 25 34 000 3 30 20 000 2 40 7 4 CK5A CK5BT042 34 600 TDR 11 20 10 20 34 000 3 30...

Page 12: ...00 3 12 29 800 2 32 7 20 CE3AA048 45 000 NONE 10 00 10 00 9 35 47 000 3 12 29 600 2 34 7 20 CE3AA060 46 000 NONE 10 00 10 00 9 45 47 000 3 18 29 800 2 38 7 50 CF5AA048 44 500 NONE 10 00 10 00 9 30 46...

Page 13: ...R 10 50 9 65 56 000 3 14 38 000 2 46 7 2 CK3BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BT060 55 000 TDR 10 50 9 45...

Page 14: ...4 6 14 5 2 13 2 06 2 00 2 00 2 00 16 4 14 7 13 5 13 7 13 7 8 99 11 8 11 3 13 7 13 7 2 25 2 17 2 11 2 12 2 12 14 9 13 3 12 1 12 5 12 6 8 46 11 2 10 7 12 5 12 6 2 33 2 24 2 16 2 19 2 19 700 72 67 63 62...

Page 15: ...7 8 18 0 18 0 11 8 15 4 14 7 18 0 18 0 2 91 2 80 2 71 2 72 2 72 19 8 17 7 16 2 16 7 16 7 11 2 14 7 14 1 16 7 16 7 3 04 2 91 2 80 2 84 2 84 900 72 67 63 62 57 26 7 24 4 22 7 22 4 22 2 13 9 18 1 17 6 22...

Page 16: ...1 1 3 65 3 51 3 40 3 43 3 43 1150 72 67 63 62 57 33 1 30 4 28 0 27 7 27 5 17 1 22 5 21 7 27 1 27 5 2 99 2 91 2 85 2 84 2 84 31 4 28 5 26 2 26 1 26 0 16 6 21 8 21 0 26 0 26 0 3 18 3 09 3 02 3 01 3 01 2...

Page 17: ...0 3 4 19 4 03 3 92 3 93 3 93 34 2 30 8 28 3 28 8 28 8 18 9 25 0 24 0 28 8 28 8 4 41 4 24 4 12 4 14 4 14 32 1 28 8 26 4 27 3 27 3 18 2 24 2 23 2 27 3 27 3 4 63 4 45 4 32 4 37 4 37 Multipliers for Deter...

Page 18: ...15 5 04 4 93 4 93 4 94 39 9 36 7 33 9 34 5 34 5 22 2 30 0 28 8 34 5 34 5 5 57 5 43 5 30 5 33 5 33 37 6 34 3 31 6 32 6 32 6 21 5 29 1 27 8 32 6 32 6 5 99 5 82 5 67 5 72 5 72 Multipliers for Determinin...

Page 19: ...7 13 4 62 45 88 36 27 5 04 43 37 35 26 5 51 40 85 34 21 5 99 38 17 33 09 6 49 44 66 35 83 4 54 42 32 34 76 4 94 40 01 33 73 5 37 37 63 32 66 5 84 35 12 31 52 6 33 44 33 44 33 4 54 42 42 42 42 4 95 40...

Page 20: ...4 43 4 7 93 7 78 7 66 7 67 7 67 2000 72 67 63 62 57 64 4 58 8 54 7 54 0 53 5 33 1 43 1 41 7 52 4 53 5 5 79 5 67 5 58 5 56 5 55 61 5 56 0 52 1 51 6 51 4 32 1 42 0 40 6 51 0 51 4 6 29 6 15 6 06 6 04 6...

Page 21: ...1 45 1 46 1 48 12 6 12 7 12 9 11 2 11 3 11 4 1 53 1 54 1 56 14 9 15 0 15 2 13 5 13 7 13 8 1 62 1 63 1 64 17 3 17 5 17 6 17 3 17 5 17 6 1 72 1 73 1 74 20 3 20 5 20 7 20 3 20 5 20 7 1 86 1 87 1 88 23 4...

Page 22: ...1 86 1 89 1 91 19 1 19 5 19 7 17 4 17 7 18 0 1 96 1 98 1 99 22 2 22 6 22 9 22 2 22 6 22 9 2 06 2 07 2 09 26 0 26 5 26 9 26 0 26 5 26 9 2 20 2 21 2 21 29 8 29 9 30 0 29 8 29 9 30 0 2 34 2 30 2 30 75 70...

Page 23: ...34 4 34 8 33 9 34 4 34 8 2 87 2 87 2 89 39 2 39 8 40 3 39 2 39 8 40 3 3 07 3 07 3 08 75 950 1050 1150 10 6 10 8 11 0 9 78 9 97 10 1 2 07 2 11 2 14 13 7 14 0 14 2 12 6 12 8 13 0 2 20 2 23 2 26 16 9 17...

Page 24: ...4 6 25 0 21 4 21 8 22 2 2 96 3 01 3 06 28 7 29 2 29 7 26 1 26 6 27 0 3 20 3 24 3 28 33 8 34 4 34 8 33 8 34 4 34 8 3 46 3 49 3 53 39 2 39 8 40 3 39 2 39 8 40 3 3 76 3 78 3 81 45 2 45 9 46 4 45 2 45 9 4...

Page 25: ...2 27 0 27 4 27 7 3 82 3 84 3 88 35 4 35 8 36 2 32 2 32 6 33 0 4 10 4 11 4 13 40 7 41 3 41 8 40 7 41 3 41 8 4 41 4 41 4 42 46 8 47 4 47 9 46 8 47 4 47 9 4 79 4 77 4 77 53 5 54 2 54 8 53 5 54 2 54 8 5...

Page 26: ...71 33 51 29 76 3 93 39 35 35 81 4 19 45 79 45 79 4 50 53 31 53 31 4 89 62 02 62 02 5 38 1650 19 55 17 99 3 37 24 10 22 15 3 56 28 90 26 35 3 74 34 04 30 24 3 94 39 95 36 35 4 19 46 48 46 48 4 47 54 12...

Page 27: ...MBtuh Total Power Capacity MBtuh Total Power Capacity MBtuh Total Power EDB CFM Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW...

Page 28: ...al features required prior to field start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive pr...

Reviews: